Plan Review Notes For Permit 07090764 |
Permit Number |
07090764 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-03-11 15:31:54 | ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED, | | MECHANICAL PAGES WILL BE STAMPED. THE REVIEW WILLL | | REMAIN IN FAIL STATUS PENDING SATISFACTORY COMPLETION | | OF ENERGY CALCULATIONS. | | | | THE NEWLY SUBMITTED ENERGY CALCULATIONS ARE NOT | | ACCEPTABLE. THERE HAVE BEEN TWO SEPARATE SETS OF | | CALCULATIONS SUBMITTED. ONE SET IS METHOD A AND COVERS | | BOTH THE CONDITIONED AND UNCONDITIONED PORTIONS OF THE | | BUILDING. THE OTHER SET IS METHOD B AND ONLY COVERS ONE | | PORTION OF THE CONDITIONED SPACE IN THE BUILDING. IT IS | | NOT CLEAR WHY THE BUILDING IS BEING SPLIT FOR TWO | | DIFFERENT CALCULATIONS, YET ONE SECTION OF THE BUILDING | | IS INCLUDED IN BOTH CALCULATIONS (OFFICE AREA?). | | | | BASED ON THE FACT THAT THERE ARE UNFINISHED PORTIONS OF | | THE CONDITIONED SPACE, THE APPROPRIATE METHOD TO USE TO | | DEMONSTRATE CODE COMPLIANCE WOULD BE METHOD B OR METHOD | | C FOR THE ENTIRE BUILDING, INCLUDING ALL ENERGY | | UTILIZING SYSTEMS ON ONE REPORT. PLEASE CORRECT AND | | RESUBMIT. ONCE ALL DISCIPLINES HAVE FOUND THE ENERGY | | CALCULATIONS TO BE ACCURATELY COMPLETED AND VIA THE | | CORRECT METHOD, THIS REVIEW STATUS WILL BE CHANGED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|