2008-03-11 15:31:54ALL PREVIOUS REVIEW COMMENTS HAVE BEEN ADDRESSED,
 MECHANICAL PAGES WILL BE STAMPED. THE REVIEW WILLL
 REMAIN IN FAIL STATUS PENDING SATISFACTORY COMPLETION
 OF ENERGY CALCULATIONS.
  
 THE NEWLY SUBMITTED ENERGY CALCULATIONS ARE NOT
 ACCEPTABLE. THERE HAVE BEEN TWO SEPARATE SETS OF
 CALCULATIONS SUBMITTED. ONE SET IS METHOD A AND COVERS
 BOTH THE CONDITIONED AND UNCONDITIONED PORTIONS OF THE
 BUILDING. THE OTHER SET IS METHOD B AND ONLY COVERS ONE
 PORTION OF THE CONDITIONED SPACE IN THE BUILDING. IT IS
 NOT CLEAR WHY THE BUILDING IS BEING SPLIT FOR TWO
 DIFFERENT CALCULATIONS, YET ONE SECTION OF THE BUILDING
 IS INCLUDED IN BOTH CALCULATIONS (OFFICE AREA?).
  
 BASED ON THE FACT THAT THERE ARE UNFINISHED PORTIONS OF
 THE CONDITIONED SPACE, THE APPROPRIATE METHOD TO USE TO
 DEMONSTRATE CODE COMPLIANCE WOULD BE METHOD B OR METHOD
 C FOR THE ENTIRE BUILDING, INCLUDING ALL ENERGY
 UTILIZING SYSTEMS ON ONE REPORT. PLEASE CORRECT AND
 RESUBMIT. ONCE ALL DISCIPLINES HAVE FOUND THE ENERGY
 CALCULATIONS TO BE ACCURATELY COMPLETED AND VIA THE
 CORRECT METHOD, THIS REVIEW STATUS WILL BE CHANGED.
  