Plan Review Notes For Permit 07090764 |
Permit Number |
07090764 |
|
Review Stop |
ENG |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-02-28 13:39:43 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: | | | | | | 1.YOU NEED TO PROVETHAT YOUR FINISHED FLOOR IS HIGH | | ENOUGH TO TAKE ALL WORST FLOOD CONDITION.THEREFORE, | | PLEASE SHOW ON STORM WATER CALCULATTION THAT YOUR FF | | ELEVATION IS HIGH ENOUGH ANDHAVE CONSIDERED FLOOD | | ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA TO | | DETERMINE THE FIRST FLOOR ELEVATION, PARKING LOT | | ELEVATION, CROWN OF THE ROAD ELEVATION, SIDEWALK ETC. | | ALSO, PLEASE SHOW WORST CROWN OF THE ROAD ELEVATION ON | | THE DRAWINGS. PLEASE PROVIDE A COPY OFSTORM WATER | | CALS TO 1000 45TH STREET ENGINEERING FOR THEIR APPROVAL | | BEFORE WE APPROVE. | | | | PLEASE RESPOND EACH OF THE ABOVE ITEMSIN DETAIL TO | | EXPEDITE YOUR PERMITTING PROCESS | | | | RASIK CHOKSHI805-6723 |
|