Date |
Text |
2008-02-16 16:08:26 | ** DENIED 3RDREVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| ARE NOT CODE COMPLIANT. THE TWO PREVIOUS REVIEWS |
| REQUESTED ENERGY CALCULATIONS AND THIS IS THE FIRST |
| TIME THESE ARE BEING SUBMITTED FOR REVIEW. |
| NOW TWO COMPLETELY SEPARATE SETS ARE BEING SUBMITTED. |
| ONE FOR THE ADMINISTRATIVE OFFICE SPACE. |
| ONE FOR THE PARKING GARAGE. |
| PLEASE SEE THAT THE CALCULATIONS TO BE SUBMITTED ARE |
| FOR ONE BUILDING AND STRUCTURE. THE FOLLOWING WILL BE |
| BROKEN UP INTO SECTIONS FOR NOTES AND THE INPUT DATA |
| REPORT WILL BE NOTED AS IDR. |
| |
| A) PLEASE SEE THE CALCULATIONS WHICH WERE SUBMITTED FOR |
| THE ADMINISTRATIVE OFFICE SPACES ARE SHOWING ONLY TWO |
| INTERIOR LIGHT FIXTURES. TO BE EXACT THEY SHOW 2-35 |
| WATT FIXTURES WITH A TOTAL OF 70WATTS ON THE SUMMARY |
| SHEETS AS WELL AS THE IDR. THESE CALCULATIONS ARE |
| SUBMITTED AND SIGNED AND SEALED BY MR. WU. |
| HOW IS THIS POSSIBLE WHEN THE PLANS SHOW DOZENS OF |
| FIXTURES IN THESE SAME OFFICES?? |
| PLEASE SEE 13-400.3.B, 13-415.1.B, 13-415.2 |
| |
| B) PLEASE SEE THE CALCULATIONS FOR WHICH ARE REQUIRED |
| TO HAVE THE CERTIFICATION SHEET FILLED OUT IS NOT |
| DONE. |
| PLEASE KNOW AS THIS SHEET IS SENT INTO THE STATE FOR |
| AUDITING ALONG WITH THE COVER SHEET ALL INFORMATION ON |
| THE CERTIFICATION SHEET ALONG WITH BEING SIGNED, DATED |
| AND SEALED NEEDS TO BE DONE. |
| PLEASE BE SURE THE OWNER AGENT IS FILLED OUT AND |
| SIGNED. |
| FBC 13-103.1.1.1, FS 471.025, FAC 61G15-23.002 |
| |
| C) PLEASE SEE THE IDR REPORT FOR EXTERIOR SUBMITTED FOR |
| GARAGE NEEDS TO BE COORDINATE WITH THE ELECTRICAL |
| PLANS. |
| PLEASE SEE FOR EXAMPLE: EXTERIOR IDR WHICH ONLY SHOWS |
| 26-H FIXTURES WHICH IS OK, HOWEVER WHERE ARE THE |
| J-FIXTURES? |
| PLEASE SEE THE INTERIOR LIGHTING OF THE PARKING GARAGE |
| DOES NOT MATCH WITH THE COUNT OF FIXTURES, THE WATTAGE |
| OF FIXTURES AND THE METHOD OF CONTROL. |
| FOR EXAMPLE:PLEASE SEE THE IDR DOES NOT CONTAIN ANY |
| 150W OR 100W FIXTURES, YET THE FIXTURE LEGEND CONTAINS |
| THESE. |
| FOR EXAMPLE: PLEASE SEE THE IDR SHOWS 16-300W FIXTURES, |
| HOWEVER THE FIXTURE LEGEND DOES NOT SHOW ANY 300W |
| FIXTURES. |
| FOR EXAMPLE: THE IDR SHOWS METHODS OF CONTROL AS |
| DAYLIGHTINGON/OFF W/ OCCUPANCY SENSORS, PROGRAMMABLE |
| ETC HOWEVER BASED ON PLANS AND KNOWN TO THIS OFFICE |
| MANY OF THESE LOCATIONS ARE MANUAL ON/OFF, PHOTO-SENSOR |
| CONTROL, OR OCCUPANCY SENSOR WITHOUT DAYLIGHTING. |
| |
| D) PLEASE KNOW A NOTE WHICH WAS NOT MENTIONED BUT GIVEN |
| FOR INFORMATION. IF ANY LIGHTING IS DONE FROM AN |
| ASTRONOMICAL TIME CLOCK, BATTERY BACK OF CONTROLS IS |
| REQUIRED FOR TEN HOURS. THIS IS ONLY NOTED AS PLANS |
| INDICATE PHOTO-SENSOR CONTROLS FOR LIGHTING CONTROL |
| PANEL. 13-415.1.ABC.1.4 |
| |
| ** PLEASE COORDINATE ENERGY CALCULATIONS AND SUBMIT |
| ONLY ONE. ** THERE ARE OTHER FIXTURES WHICH NEED |
| COORDINATION. |
| |
| 2) NOTE: PLEASE SEE OFFICE AREAS WHICH SHOW ALL |
| LIGHTING BEING CONTROLLED BY SENTRY SWITCHING AND OVER |
| RIDES. |
| IN MEETING HELD BEFORE PLANS WERE RESUBMITTED THE |
| COMMENT WITH RESPECT TO EMERGENCY LIGHTING FOR EGRESS |
| TO CONTROLS WAS BROUGHT UP. IF AN OCCUPANT IS LOCATED |
| IN ANY AREA OF THESE OFFICES (EGRESS PATHS) AND TIME |
| SWEEPS LIGHTING OFF, AN OCCUPANT WOULD BE IN TOTAL |
| DARKNESS IN ORDER TO FIND THEIR WAY TO AN OVER RIDE. |
| THIS OFFICE WILL REQUIRE OCCUPANCY SENSORS OF SOME TYPE |
| FOR MINIMUM EGRESS TO OVER RIDES AS STATED IN THE |
| FOLLOWING SECTIONS OF THE FBC AND LIFE SAFETY CODES. |
| **PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2.2 WITH |
| RESPECT TO AUTOMATED DEVICES IN EGRESS PATHS. THIS IS |
| PERMITTED BY BOTH CODES HOWEVER THE COVERAGE OF SUCH |
| UNITS SHALL BE SUFFICIENT FOR ALL AREAS, THE DEVICES |
| ARE REQUIRED TO BE 15MINS OF TIME FOR ON AND SHALL ALSO |
| BE FAIL SAFE ON. |
| PLEASE KNOW AS MENTIONED ON PREVIOUS PROJECTS WITH |
| RESPECT TO FBC AND CHAPTER 13 THIS AHJ DOESHAVE AN |
| ISSUE WITH NIGHT LIGHTS AS LONG AS THE LIGHTING BEING |
| LEFT ON DOES NOT EXCEED THE MINIMUM LEVELS OF 1FT |
| CANDLES WITHIN REASON FOR EGRESS AREAS. |
| AS SHOWN AT THIS TIME, AN OCCUPANT ON STAIRS WOULD BE |
| OK AS A NIGHT LIGHT WAS DESIGNATED AND ADDED TO PLANS. |
| PLEASE SEE SOME OTHER EGRESS PATHS MAY NOT HAVE ANY |
| AMBIENT LIGHTING FROM OUTSIDE OR OTHER AREAS TO PROVIDE |
| NEEDED MINIMUM. |
| PLEASE INCLUDE OCCUPANCY DEVICES OR OTHER MEANS. |
| ** PLEASE KNOW THIS MAY BE PART OF A PROVISO IN ORDER |
| TO NOT HAVE TO REPRINT SHEETS HOWEVER COMMENT NUMBER 1 |
| ABOVE WILL KEEP FROM ISSUANCE AT THIS TIME. |
| |
| ** MAY CALL TO GO OVER. |
| |
| ** A CALL WAS PLACED TO THE ENGINEERS OFFICE AS OF |
| REVIEW AND LEFT VOICEMAIL. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |