Date |
Text |
2007-12-27 10:42:05 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT IR.1 SHOW THE LOCATION OF THE WATER SOURCE. IF |
| IT IS POTABLE WATER FROM THE CITY, SHOW THE WATER METER |
| LOCATION AND THE RPZV BACKFLOW LOCATION.THE NOTE |
| "CONNECT TO EXISTING SYSTEM". WHAT EXISTING SYSTEM? |
| PLEASE SHOW ALL PIPING FOR THE COMPLETE SYSTEM.(METER |
| 2 LOCATION IS INDICATED. IS THERE ANOTHER METER?). |
| PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2. |
| |
| 2. SHT IR.1 SOME INFORMATION ON THE SHEET IS NOT |
| LEGIBLE. PLEASE MAKE ALL INFORMATION LEGIBLE. SECTION |
| 106.1.1. |
| |
| 3. SHT IR.1 SHOWS CONTROLLER B,AND THE LEGEND |
| INDICATES A RAIN SENSOR ONE PER EACH CONTROLLER. PLEASE |
| CLARIFY. IS THERE MORE THAN ONE CONTROLLER. IF SO |
| PLEASE INDICATE THE LOCATION OF EACH CONTROLLER. |
| SECTION 106.1.1. |
| |
| 4. SHTS IR.1 & IR.2 ARE REQUIRED TO SEALED WITH AN |
| EMBOSSED TYPE SEAL THAT WILL IMPRESS ALL REQUIRED |
| INFORMATION ON EACH SHEET. A STAMP SEAL IS NOT |
| APPROVED. SECTION 106.1. FAC 61G1-16.001 & 61G1-16.002 |
| INDICATE THE REQUIREMENTS OF THE SEAL. PLEASE COMPLY. |
| FS 481.306. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |