Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-27 10:42:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT IR.1 SHOW THE LOCATION OF THE WATER SOURCE. IF
 IT IS POTABLE WATER FROM THE CITY, SHOW THE WATER METER
 LOCATION AND THE RPZV BACKFLOW LOCATION.THE NOTE
 "CONNECT TO EXISTING SYSTEM". WHAT EXISTING SYSTEM?
 PLEASE SHOW ALL PIPING FOR THE COMPLETE SYSTEM.(METER
 2 LOCATION IS INDICATED. IS THERE ANOTHER METER?).
 PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2.
  
 2. SHT IR.1 SOME INFORMATION ON THE SHEET IS NOT
 LEGIBLE. PLEASE MAKE ALL INFORMATION LEGIBLE. SECTION
 106.1.1.
  
 3. SHT IR.1 SHOWS CONTROLLER B,AND THE LEGEND
 INDICATES A RAIN SENSOR ONE PER EACH CONTROLLER. PLEASE
 CLARIFY. IS THERE MORE THAN ONE CONTROLLER. IF SO
 PLEASE INDICATE THE LOCATION OF EACH CONTROLLER.
 SECTION 106.1.1.
  
 4. SHTS IR.1 & IR.2 ARE REQUIRED TO SEALED WITH AN
 EMBOSSED TYPE SEAL THAT WILL IMPRESS ALL REQUIRED
 INFORMATION ON EACH SHEET. A STAMP SEAL IS NOT
 APPROVED. SECTION 106.1. FAC 61G1-16.001 & 61G1-16.002
 INDICATE THE REQUIREMENTS OF THE SEAL. PLEASE COMPLY.
 FS 481.306.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved