Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop M
Sequence Number 2
Notes
Date Text
2008-01-03 16:36:26REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. LS.1 AND LS.2: ONLY TWO OF THE 8 REFERENCES TO ?OPEN
 PARKING GARAGE? ON THESE PAGES HAVE BEEN CORRECTED. THE
 OTHER SIX ARE STILL INCORRECT. PLEASE CORRECT ALL
 REFERENCES TO AN OPEN PARKING GARAGE. FBC 406.2.1.
  
 2. M1.1: EF-2 LOCATION IS NOT SHOWN AS BEING PROTECTED
 BY BOLLARDS ON PG A1.1 OR M1.1. PLEASE SHOW THIS FAN TO
 BE PROTECTED FROM MECHANICAL DAMAGE IN ACCORDANCE WITH
 FBC, M 304.5. ALSO, EF-20 IS SHOWN IN THE WALL BETWEEN
 THE FIRE PUMP ROOM AND THE STORAGE ROOM AS WELL AS AT
 COLUMN LINE C. WHICH IS CORRECT? HOW WILL THIS PROVIDE
 THE REQUIRED VENTILATION FOR THE FIRE PUMP ROOM?
  
 3 & 4: OK
  
 5. OK EXCEPT, SEE COMMENT #2 REGARDING EF 20.
  
 6 - 9: OK
  
 10. IT IS NOT POSSIBLE TO ASCERTAIN THE DESIGN INTENT
 RELATED TO OCCUPANCY TYPES AND REQUIRED OCCUPANCY
 SEPARATIONS RELATED TO THIS BUILDING AS THE ENTIRE
 GARAGE IS BEING CALLED ?S2 INCIDENTAL USE? ON PG LS0.0.
 THE S2 OCCUPANCY IS NOT INCIDENTAL TO THE USE OF THE
 BUILDING. IT IS THE PRIMARY USE AND OCCUPANCY OF THE
 BUILDING. THERE ARE OTHER OCCUPANCIES WHICH MAY BE
 CONSIDERED INCIDENTAL OR ACCESSORY TO THE PRIMARY
 OCCUPANCY, BUT EITHER WAY A FIRE RATED SEPARATION
 BETWEEN THESE SPACES IS REQUIRED, INCLUDING THE TYPE B
 OCCUPANCY AREAS IN ACCORDANCE WITH FBC 302.1.1 AND
 302.2 AND 302.3.
  
 THE EXHAUST DUCT PENETRATIONS IN THIS AREA WILL REQUIRE
 OPENING PROTECTIVES IN ACCORDANCE WITH FBC 607.5 OR
 607.1.1. SHOW COMPLIANCE WITH THESE SECTIONS AND
 COORDINATE WITH ARCHITECTURAL AND LIFE SAFETY PLANS.
  
 11 & 12: OK
  
 13. TOILET ROOMS 1.205 AND 1.206 BOTH RECEIVE SUPPLY
 AIR FROM AHU #3. ALL AIR SUPPLIED TO SUCH SPACES SHALL
 BE EXHAUSTED IN ACCORDANCE WITH FBC, M 403.2.1(3). IF
 THE LIGHT SWITCHES ARE OFF AND AHU #3 IS RUNNING, HOW
 WILL THE AIR BEING SUPPLIED TO THESE SPACES BE
 EXHAUSTED IN ACCORDANCE WITH THIS SECTION? THE
 REQUIREMENTS OF401.3 AND 403.2.1(3) SHALL BE MET FOR
 THESE SPACES.
  
 14 - 17: OK
  
 18. OK PENDING BUILDING PLAN REVIEW.
  
 19. OK
  
 20. M4.1: DETAIL 03 SHOWS A SECONDARY DRAIN OFF A
 SECONDARY DRAIN PAN TIED INTO THE PRIMARY DRAIN LINE.
 THIS IS NOT AN ACCEPTABLE MEANS OF AUXILIARY OR
 SECONDARY DRAIN PROTECTION. SEE FBC, M 307.2.3 FOR A
 LIST OF APPROVED METHODS AND SHOW COMPLIANCE.
  
 21. MOTORIZED DAMPERS HAVE NOT BEEN SHOWN IN THE O.A.
 DUCT ON PLANS FOR AHU-1 OR AHU-2. SHOW COMPLIANCE WITH
 FBC 13-409.1.ABC.3.3. GRAVITY OPERATED DAMPERS
 (BACKDRAFT DAMPERS) ARE ACCEPTABLE ON BATHROOM EXHAUST
 DUCTS.
  
 22. OK
  
 23. NO ENERGY CODE COMPLIANCE FORM COULD BE FOUND IN
 THIS SUBMITTAL.
  
 24 ? 26: OK
  