2008-01-03 16:36:26 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. LS.1 AND LS.2: ONLY TWO OF THE 8 REFERENCES TO ?OPEN |
| PARKING GARAGE? ON THESE PAGES HAVE BEEN CORRECTED. THE |
| OTHER SIX ARE STILL INCORRECT. PLEASE CORRECT ALL |
| REFERENCES TO AN OPEN PARKING GARAGE. FBC 406.2.1. |
| |
| 2. M1.1: EF-2 LOCATION IS NOT SHOWN AS BEING PROTECTED |
| BY BOLLARDS ON PG A1.1 OR M1.1. PLEASE SHOW THIS FAN TO |
| BE PROTECTED FROM MECHANICAL DAMAGE IN ACCORDANCE WITH |
| FBC, M 304.5. ALSO, EF-20 IS SHOWN IN THE WALL BETWEEN |
| THE FIRE PUMP ROOM AND THE STORAGE ROOM AS WELL AS AT |
| COLUMN LINE C. WHICH IS CORRECT? HOW WILL THIS PROVIDE |
| THE REQUIRED VENTILATION FOR THE FIRE PUMP ROOM? |
| |
| 3 & 4: OK |
| |
| 5. OK EXCEPT, SEE COMMENT #2 REGARDING EF 20. |
| |
| 6 - 9: OK |
| |
| 10. IT IS NOT POSSIBLE TO ASCERTAIN THE DESIGN INTENT |
| RELATED TO OCCUPANCY TYPES AND REQUIRED OCCUPANCY |
| SEPARATIONS RELATED TO THIS BUILDING AS THE ENTIRE |
| GARAGE IS BEING CALLED ?S2 INCIDENTAL USE? ON PG LS0.0. |
| THE S2 OCCUPANCY IS NOT INCIDENTAL TO THE USE OF THE |
| BUILDING. IT IS THE PRIMARY USE AND OCCUPANCY OF THE |
| BUILDING. THERE ARE OTHER OCCUPANCIES WHICH MAY BE |
| CONSIDERED INCIDENTAL OR ACCESSORY TO THE PRIMARY |
| OCCUPANCY, BUT EITHER WAY A FIRE RATED SEPARATION |
| BETWEEN THESE SPACES IS REQUIRED, INCLUDING THE TYPE B |
| OCCUPANCY AREAS IN ACCORDANCE WITH FBC 302.1.1 AND |
| 302.2 AND 302.3. |
| |
| THE EXHAUST DUCT PENETRATIONS IN THIS AREA WILL REQUIRE |
| OPENING PROTECTIVES IN ACCORDANCE WITH FBC 607.5 OR |
| 607.1.1. SHOW COMPLIANCE WITH THESE SECTIONS AND |
| COORDINATE WITH ARCHITECTURAL AND LIFE SAFETY PLANS. |
| |
| 11 & 12: OK |
| |
| 13. TOILET ROOMS 1.205 AND 1.206 BOTH RECEIVE SUPPLY |
| AIR FROM AHU #3. ALL AIR SUPPLIED TO SUCH SPACES SHALL |
| BE EXHAUSTED IN ACCORDANCE WITH FBC, M 403.2.1(3). IF |
| THE LIGHT SWITCHES ARE OFF AND AHU #3 IS RUNNING, HOW |
| WILL THE AIR BEING SUPPLIED TO THESE SPACES BE |
| EXHAUSTED IN ACCORDANCE WITH THIS SECTION? THE |
| REQUIREMENTS OF401.3 AND 403.2.1(3) SHALL BE MET FOR |
| THESE SPACES. |
| |
| 14 - 17: OK |
| |
| 18. OK PENDING BUILDING PLAN REVIEW. |
| |
| 19. OK |
| |
| 20. M4.1: DETAIL 03 SHOWS A SECONDARY DRAIN OFF A |
| SECONDARY DRAIN PAN TIED INTO THE PRIMARY DRAIN LINE. |
| THIS IS NOT AN ACCEPTABLE MEANS OF AUXILIARY OR |
| SECONDARY DRAIN PROTECTION. SEE FBC, M 307.2.3 FOR A |
| LIST OF APPROVED METHODS AND SHOW COMPLIANCE. |
| |
| 21. MOTORIZED DAMPERS HAVE NOT BEEN SHOWN IN THE O.A. |
| DUCT ON PLANS FOR AHU-1 OR AHU-2. SHOW COMPLIANCE WITH |
| FBC 13-409.1.ABC.3.3. GRAVITY OPERATED DAMPERS |
| (BACKDRAFT DAMPERS) ARE ACCEPTABLE ON BATHROOM EXHAUST |
| DUCTS. |
| |
| 22. OK |
| |
| 23. NO ENERGY CODE COMPLIANCE FORM COULD BE FOUND IN |
| THIS SUBMITTAL. |
| |
| 24 ? 26: OK |
| |