Plan Review Notes For Permit 07090764 |
Permit Number |
07090764 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-01-04 11:27:15 | *****UNSAT***** | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED.CAPS BEHIND | | THE COMMENTS MAY BE USED AS GUIDELINES TO ADDRESS THE | | COMMENT. | | | | | | 07.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE | | BUILDING REACHES THREE STORIES OR THIRTY FEET IN | | HEIGHT.ADD COMMENT TO SHEET LS0.0 | | | | 17.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.ADD | | COMMENT TO SHEET FP0.1 | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|