Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-26 14:04:50 
 *** DENIED2ND REVIEW***
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE AS STATED ON PREVIOUS REVIEW THERE WERE
 ITEMS NOT YET SUBMITTED FOR REVIEW WHICH COULD CREATE
 NEW COMMENTS. THIS WILL ALSO REMAIN AS THERE ARE NEW
 ITEMS ONLY NOW BEING SUBMITTED FOR THE FIRST REVIEW
 ALONG WITH ITEMS WHICH HAVE STILL NOT BEEN SUBMITTED.
 REVIEW COMMENTS CAN ONLY BE MADE ON PLANS AND
 DOCUMENTATION PROVIDED.
  
  
 1) NOTE:THIS NOTE REMAINS AS THERE ARE STILL CODES
 REFLECTED ON PLANS WHICH ARE NOT CURRENT OR LATEST
 ADOPTED EDITIONS AS PREVIOUSLY NOTES: FOR EXAMPLE:
 PLEASE SEE LS0.0 WHICH SHOWS THE 2002 NEC/ NFPA-70.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
 2003 NFPA-20
  
 ** PLEASE SEE FOR EXAMPLE THE T-1 SHEET WHICH CONTAINS
 CODE WHICH IS NOT ACCURATE OR NO LONGER ADOPTED BY THE
 STATE.
 PLEASE SEE THE 2002 NEC NOTED, PLEASE SEE A 2004
 NFPA-101 WAS NOTED AND 2003 REVISIONS TO THE FBC.
 PLEASE SEE SOME OF THE CODE ON LS SHEET HAS BEEN
 UPDATED HOWEVER LS SHEET STILL INDICATES SOME CODE NO
 LONGER IN ADOPTION.
 ** MANY OF THESE ARE OK ON ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE PERMIT APPLICATIONS SUBMITTED
 AS PREVIOUSLY NOTED WERE NOT CORRECTED. PLEASE SEE THE
 DUPLICATE APPLICATION WHICH HAS CONTRACTORS SIGNED
 STILL NEEDS TO BE NOTARIZED.
 THIS WAS NOTED ON PREVIOUS REVIEW NOTE #34.
  
 3) NOTE: PLEASE SEE FPL VAULT IS STILL SHOWING POWER
 BEING FED INTO THIS ROOM WHICH IS NOT PERMITTED PER FPL
 VAULT STANDARDS AND VAULT SPECIFICATIONS. PLEASE SEE
 E2.1, REDLINED SET FOR THIS ENLARGED ROOM LAYOUT.
 ** PREVIOUS NOTE #6 **
  
 4) NOTE:PLEASE SEE SHEET E2.1, WHAT IS THE MSBE-3
 DESIGNATION ON THE PLANS AT THE FIRE PUMP ROOM?
 IT IS UNCLEAR WHAT THIS IS AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 EGRESS PATHS WHICH MEET THE MINIMUM LIGHTING LEVELS AS
 REQUIRED PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE 7.8.1.3, 7.9.2.2
 THE RESPONSE LETTER MENTIONS THIS WILL BE DONE AT A
 LATER DATE; HOWEVER THIS IS REQUIRED AT THIS TIME TO
 MEET THE MINIMUM FOR LIFE SAFETY.
 PLEASE SEE THE LIGHT FIXTURES SHOWN ON PLANS DO NOT
 CORRELATE WITH THE FIXTURE LEGEND.FOR EXAMPLE: PLEASE
 SEE B-EM WHICH IS NOT LISTED.
 PLEASE PROVIDE INFORMATION ON THE HID FIXTURES FOR BACK
 UP AND TIME RESPONSE AS THESE ARE LIFE SAFETY FIXTURES.
 HOW WILL THE FIXTURE PROVIDE REQUIRED LIGHTING IN THE
 TIME GIVEN IF THESE ARE HID?
 PLEASE SEE THE LIGHTING IN STAIRS STILL SHOW A STANDARD
 FIXTURE WITH NO BATTERY BACK UP OF ANY KIND. BATTERY
 BACK UP FOR THE 1FT CANDLE MINIMUM WILL BE REQUIRED.
 PLEASE SEE THE ROOMS ARE PREVIOUSLY SPECIFIED WILL
 REQUIRE BATTERY BACK UP FIXTURES OF SOME KIND. THE REST
 OF THE RESPONSE STATES A COMMENT ABOUT THE STAIRS.
 THE SECTION WITH RESPECT TO THE SPIRAL STAIR HAS BEEN
 REMOVED AND REQUIRED EGRESS WAS CONFIRMED WITH THE
 BUILDING REVIEWER.
 LS 101 7.8, 7.9 AND SECTIONS GIVEN IN PREVIOUS REVIEW
 NOTES BELOW.
 ** PREVIOUS REVIEW NOTES**
 MOST OF THESE WERE SUBMITTED HOWEVER PLEASE SEE THE
 MINIMUM AVERAGE ON SHEETS FOR NORMAL DO NOT MEET THE
 MINIMUM LEVELS.
 PLEASE SEE THE FOLLOWING LOCATIONS ARE REQUIRED TO
 CONTAIN SOME SORT OF BATTERY BACK UP LIGHTING FIXTURE.
 THE STAIR TOWERS WILL REQUIRE A BATTERY BACK UP FIXTURE
 OF SOME TYPE TO MEET THE MINIMUM OF 1FT CANDLE LEVEL
 UNDER EMERGENCY.7.8.2.1, 7.9.2.2
 PLEASE SEE THE OTHER LOCATIONS WILL BE THE GENERATOR
 ROOM, FIRE PUMP ROOM, MAIN ELECTRICAL ROOM, EMERGENCY
 MAIN ELECTRICAL ROOM, AND THE ELEVATOR EQUIPMENT ROOMS.
 (SOME OF THESE MAY ALREADY SHOW A BATTERY BACK UP
 FIXTURE, BUT MOST DO NOT).
 700.12F.
 PLEASE SEE 700.16 FOR THESE SAME ROOMS.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #8 WITH RESPECT TO
 THE WIND LOADS ON ROOF TOP POLES WITH THE EFFECTIVE
 PROJECTED AREA. THE LIGHT POLE DETAIL ON SHEET 7.1 DOES
 NOT CORRELATE WITH THE AMOUNT OF LIGHTING FIXTURES
 SHOWN ON POLES ON E1.2.
 RESPONSE MENTIONS CALCULATIONS SUBMITTED, HOWEVER THE
 LOCATION IN BINDER WHICH IS LABELED FOR POLE
 CALCULATIONS IS EMPTY??
 PLEASE KNOW THE ROOF TOP LIGHTING POLES WILL BE
 REQUIRED TO HAVE STRUCTURAL WIND LOAD CALCULATIONS AND
 WILL BE REVIEWED BY THE BUILDING REVIEWER.
 ** THIS IS NOTED FOR INFORMATION.
  
 7) NOTE:PLEASE SEE PREVIOUS NOTE #10. THE CODE
 SECTIONS GIVEN WERE FOR REQUIRED DEDICATED CIRCUITS.
 PLEASE SEE THE RESPONSE MENTIONS THIS WAS DONE.
 PLEASE SEE THE FOLLOWING FOR A COUPLE OF EXAMPLES:
 PLEASE SEE E1.1, AS CIRCUIT 1EGL-1 STILL FEEDS ELEVATOR
 PITS ON NORTH SIDE AS WELL AS SOUTH SIDE ELEVATOR
 PITS.
 PLEASE SEE CIRCUIT 1EGH-19 AS THIS CIRCUIT IS SHOWN ON
 E2.2 AS FEEDING BOTH ROOMS ON NORTH AND SOUTH SIDE
 ELEVATOR ROOMS.
 PLEASE SEE THE FOLLOWING COMMENT AND THE NOTE FROM
 PREVIOUS REVIEW.
  
 8) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #13. SAME
 COMMENT.
 RESPONSE MENTIONS TO SEE E1.1 AND DETAIL 01 AND ALSO
 SAYS TO SEE E0.1?
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23 AS THE EXPLANATORY NOTE IN THE
 HANDBOOK FOR ELEVATOR PIT LIGHTING REQUIRES A 5FT
 CANDLE LIGHTING LEVEL.
 PLEASE SEE THE FOLLOWING WHICH WAS EXTRACTED FOR THIS
 SECTION ON THE NEC.
 *ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 9) NOTE: PLEASE SEE LIGHTING SYSTEM IN OFFICES AS SOME
 AREAS DO NOT SHOW CONTROL/COMPLETED SYSTEM. PLEASE SEE
 SHEET E6.1 FOR EXAMPLE AS THE LCP IS BASICALLY BLANK.
 WHAT IS THIS?
 PLEASE SEE ALL AREAS PER CODE NOT DONE.
 PLEASE SEE NOTES FROM PREVIOUS REVIEW EVEN GAVE
 EXAMPLES AND SPECIFIC ROOMS SUCH AS RETAIL SPACES, YET
 NO CHANGES WERE MADE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND 1.3.
  
 10) NOTE: PLEASE SEE MISSING ENERGY CALCULATIONS/
 LIGHTING PERFORMANCE CALCULATIONS PER 13-415.2 AND
 13-415.2.ABC.1.3 ETC. RESPONSE MENTIONS TO SEE ATTACHED
 CALCULATIONS HOWEVER THIS REVIEWER HAS GONE THROUGH ALL
 BOOKS AS SUBMITTED. PLANS DO NOT SHOW MINIMUM
 COMPLIANCE FOR MAXIMUM LIGHTING LEVELS FOR INTERIOR OR
 EXTERIOR LIGHTING.
 PLEASE SEE SOME AREAS OF THIS BUILDING WILL HAVE
 CONDITIONED SPACE.
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #17.
 PLEASE PROVIDE COMPLETED INFORMATION FOR FIRE PUMP AND
 LOCKED ROTOR OVER CURRENT PROTECTION AND AMPERAGES. THE
 NOTE HERE FROM PREVIOUS REVIEW IS BASICALLY THE SAME.
 THE RESPONSE MENTIONS THESE ITEMS WERE REVISED AND
 ADJUSTED HOWEVER PLEASE SEE RISER SHEET E5.1. ??
 PLEASE SEE FP SHEET FP0.1 AS THIS SHEET STILL SHOWS THE
 SAME INFORMATION FROM PREVIOUS REVIEW WHICH DOES NOT
 CORRELATE WITH ELECTRICAL SHEETS NOR DOES IT COORDINATE
 WITH THE FIRE PUMP SUBMITTALS.
 PLEASE ADJUST PLANS AND IF THERE IS ANY QUESTION ON
 WHAT IS MEANT FROM THE TYPED COMMENT, PLEASE CALL TO GO
 OVER.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NEC 695.4B1, 9.3.2.2.3.2(A), (B) ETC PLEASE
 SEE THE ELECTRICAL PLANS INDICATE A DISCONNECT WITH
 OVER CURRENT PROTECTION AHEAD OF THE FIRE PUMP
 CONTROLLER WHICH WILL ALSO CONTAIN OVER CURRENT
 PROTECTION.
 PLEASE KNOW THERE MAY NOT BE OVER CURRENT PROTECTION ON
 THE LINE SIDE OF THE FIRE PUMP CONTROLLER. THE TYPICAL
 LISTED FIRE PUMP CONTROLLER CONTAINS THE LOCKED ROTOR
 CURRENT SETTING FOR THE SELECTED PUMP AND ASSEMBLY.
 10.4.4.1 NFPA-20
 PLEASE ALSO SEE THE FIRE PUMP IS BEING SHOWN AS 60 HP
 ON FP SHEETS AND 75HP ON ELECTRICAL SHEETS.
 PLEASE SEE PROVIDE INFORMATION ON WHAT TYPE OF BREAKERS
 ARE ON THE SECONDARY EMERGENCY SIDE FOR FIRE PUMP
 POWER. AS THE FIRE PUMP IS BEING FED THROUGH A TOTAL OF
 THREE BREAKERS ON THE EMERGENCY SIDE, THESE MAY CREATE
 AN ISSUE WITH SELECTIVE COORDINATION.
 PLEASE SEE THESE BREAKERS ARE TYPICALLY MAGNETIC TYPE.
 PLEASE SEE NEC 695 AND NFPA-20CHAPTER 9 AND 10.
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #22. THE
 RESPONSE STATES *THIS HAS BEEN VERIFIED WITH FPL AND
 CAN BE GRANTED*.
 PLEASE KNOW THAT FPL HAS NO AUTHORITY OVER SERVICES
 GRANTED BY THE NEC AND ARTICLE 230.2. THE NOTE WAS HOW
 DOES THIS SEPARATE SERVICE SHOWN MEET THE NEC AND 230.2
 NOT WHAT FPL WILL OR WILL NOT DO.
 PLEASE KNOW THIS SEPARATE SERVICE AS SHOWN IS NOT
 GRANTED.
  
 13) NOTE: NO ACTION NEEDED, ONLY A RESPONSE FOR LETTER
 RESPONSE FROM DESIGNER.
 PLEASE SEE PREVIOUS NOTE #27, THE REQUEST WAS TO
 COMPLETE EDP1 SCHEDULE FOR FEEDERS ETC FOR THE
 ELEVATORS AND BASE DISCONNECTS.THE NOTE/REQUEST WAS
 NOT FOR THE FINAL OVER CURRENT PROTECTION FROM THE
 DISCONNECT(S) TO THE ELEVATOR MOTORS.
 THE EDP1 SCHEDULE WAS BLANK ON PREVIOUS PLANS. THANK
 YOU FOR COMPLETING INFORMATION.
  
 14) NOTE: PLEASE SEE PREVIOUS NOTE #24 AS THE FIXTURES
 ON ROOF-TOP LIGHT POLES AND FIXTURE LEGEND DOES NOT
 CORRELATE.
 PLEASE SEE E1.2 FOR EXAMPLE AS THERE ARE FIXTURES ON
 PLANS WHICH ARE NOT ON THE FIXTURE LEGEND.
 PLEASE GO THROUGH CIRCUITING, FIXTURES, FIXTURE
 SCHEDULE, LIGHT POLE DETAILS ETC AND COORDINATE ALL.
 PLEASE SEE NOTE ABOVE WITH RESPECT TO OTHER PARKING
 GARAGE FIXTURES WHICH DO NOT COORDINATE WITH OTHER
 LOCATIONS.
 ** PLEASE COMPLETE.
 LS 101 7.8, 7.9, FBC 13-415.2.ABC.1.3, NEC 408.4,
 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 15) NOTE: PLEASE SEE THE GENERATOR SPECS SUBMITTED
 INDICATE A LOAD BANK WHICH WILL NOT BE PART OF THE
 GENERATOR UNIT AND WILL BE REQUIRED TO BE MOUNTED
 SEPARATELY. PLEASE SEE THE PLANS AS THE ELECTRICAL
 RISER DIAGRAM AND PLANS DO NOT SHOW ANY BREAKER, ANY
 LOCATION, ANY CONDUCTORS ETC.
 ** PLEASE SEE SUBMITTAL IN SPEC BOOKS FOR A UNIT WHICH
 NOTES BEING PART OF THE GENERATOR?
 PLEASE COMPLETE RISER AND ADJUST AS NEEDED.
 240.4, 310.16, 215.5, 110.3, 90.7 ETC
 FBC 106.1.2 FOR COORDINATION.
  
  
 16) NOTE: PLEASE SEE PREVIOUS NOTE #29.
 RESPONSE MENTIONS THIS WAS DONE, HOWEVER COULD NOT
 LOCATE ON RISER.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 230.2E, 700.8 ETC AS ALL MAINS ARE REQUIRED
 TO BE LABELED.
 PLEASE SEE 230.2 AS THE POWER FOR THE EMERGENCY SERVICE
 EQUIPMENT IS BEING TAPPED FROM THE NORMAL ELECTRICAL
 SERVICE. IF THERE ARE ANY CHANGES PLEASE BE SURE TO
 LABEL ALL MAINS ACCORDINGLY.
 PLEASE SEE COMMENT ABOVE WITH RESPECT TO RETAIL SERVICE
 PROPOSED.
  
 17) NOTE: PLEASE SEE PREVIOUS NOTE #31 WITH RESPECT TO
 COMPLETION OF RETAIL SERVICE CONDUCTORS ETC. AS THE
 RISER WILL BE CHANGING AND THE INFORMATION WAS NOT
 SHOWN ON REVISED RISER FOR TAPPED CONDUCTORS ETC, THEN
 PLEASE SEE 310.16, 240.4 , 250.6, ETC
  
 18) NOTE: PLEASE SEE FLORIDA STATUTES WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-25 14:30:472007-12-25 14:30:47
  
 REVIEW IN PROGRESS
2007-12-25 13:01:052007-12-25 13:01:05
  
 ONE SET IN ELECTRICAL FOR REVIEW.