Plan Review Notes For Permit 07090764 |
Permit Number |
07090764 |
|
Review Stop |
E |
Sequence Number |
10 |
|
Notes |
Date |
Text |
2008-09-29 09:29:46 | ** DENIED ** | | | | 1) NOTE: PLEASE COORDINATE THE SELECTIVE COORDINATION | | STUDY WITH LATEST REVISED RISER ON FILE. | | PLEASE SEE SDP SWITCHBOARD WHICH INDICATES FOUR 125 AMP | | BREAKERS TO ELEVATOR EQUIPMENT. EVEN IF ONLY ONE OF | | THESE IS LEGALLY REQUIRED THE OTHER THREE MAY AFFECT | | THE COORDINATION OF THE SYSTEM. | | PLEASE VERIFY. | | 700.27, 701.18, 240.12 | | | | 2) NOTE: PLEASE SEE THE LATEST ELECTRICAL RISER AS THIS | | INDICATES A 100 MCB FOR 10GH, YET COORDINATION STUDY | | SHOWS 60 AMP MCB. PLEASE SEE PANEL SCHEDULE AS THE | | LATEST REVISED PANEL SCHEDULE SHOWS THIS AS A 100AMP | | MAIN LUG ONLY PANEL. | | AS THE 10GH IS OF THE OPTIONAL STAND-BY SYSTEM, THIS IS | | NOT REQUIRED TO BE PART OF THE COORDINATION STUDY | | HOWEVER PLANS WILL NEED TO MATCH BEFORE CO. IF THIS | | WERE THE ONLY COMMENT A TCO COULD BE GRANTED AS THIS | | PARTICULAR PANEL IS NOT LIFE SAFETY OR LEGALLY | | REQUIRED. | | | | IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO | | CONTACT THIS OFFICE. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|