Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop E
Sequence Number 10
Notes
Date Text
2008-09-29 09:29:46** DENIED **
  
 1) NOTE: PLEASE COORDINATE THE SELECTIVE COORDINATION
 STUDY WITH LATEST REVISED RISER ON FILE.
 PLEASE SEE SDP SWITCHBOARD WHICH INDICATES FOUR 125 AMP
 BREAKERS TO ELEVATOR EQUIPMENT. EVEN IF ONLY ONE OF
 THESE IS LEGALLY REQUIRED THE OTHER THREE MAY AFFECT
 THE COORDINATION OF THE SYSTEM.
 PLEASE VERIFY.
 700.27, 701.18, 240.12
  
 2) NOTE: PLEASE SEE THE LATEST ELECTRICAL RISER AS THIS
 INDICATES A 100 MCB FOR 10GH, YET COORDINATION STUDY
 SHOWS 60 AMP MCB. PLEASE SEE PANEL SCHEDULE AS THE
 LATEST REVISED PANEL SCHEDULE SHOWS THIS AS A 100AMP
 MAIN LUG ONLY PANEL.
 AS THE 10GH IS OF THE OPTIONAL STAND-BY SYSTEM, THIS IS
 NOT REQUIRED TO BE PART OF THE COORDINATION STUDY
 HOWEVER PLANS WILL NEED TO MATCH BEFORE CO. IF THIS
 WERE THE ONLY COMMENT A TCO COULD BE GRANTED AS THIS
 PARTICULAR PANEL IS NOT LIFE SAFETY OR LEGALLY
 REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE TO
 CONTACT THIS OFFICE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  