2007-10-26 18:48:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT T-1 WHITE OUT NOT APPROVED ON SIGNED SEALED
 PLANS. SECTION 106.1.3.
  
 2. SHT T-1 THE SHEET INDEXSHOWS SHEETS LP-0, LP-1,
 LP-2, LP-3 & IRR-1 & IRR-2, BUT THESE SHEETS WERE NOT
 SUBMITTED. PLEASE CORRELATE INDEX WITH SHEETS
 SUBMITTED. SECTION 106.1.1.
  
 3. SURVEY SHEET. THE ADDRESS IN THE TITLE BLOCK DOES
 NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE
 DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCK OR THE DBPR
 WEBSITE PRIOR TO RESUBMITTING FOR REVIEW. FAC
 61G1-16.004(1), 61G15-23.002(2) & FS 472.025.
  
 4. SHT A2.1 DETAIL 05 SCUPPER SHOWS AN 8" OVERFLOW
 OPENING OPPOSITE THE SCUPPER OPENING FROM THE ROOF.
 THIS SEEMS LIKE THE WATER WILL DRAIN OUT THIS OPENING
 AS WELL AS DRAIN DOWN THE DOWNSPOUT. PLEASE CLARIFY.
 SECTION 106.1.2 & SECTION 1106.
  
 5. SHT A5-D.2 DETAIL 01 IDENTIFY THE DETAIL. NO DETAIL
 TITLE INDICATED. WHAT IS THE DRAIN FOR? PLEASE CLARIFY.
 SECTION 106.1.1 & TABLE 1106.3.
  
 6. SHT A9.1 DETAIL 02. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 7. SHTS P1.1 & P1.2 PLANS SHALL BE DRAWN TO A MINIMUM
 1/8TH SCALE. SECTION 106.1.3.
  
 8. SHTS P1.1 & P1.2 SHOW ALL RWL RISER DESIGNATIONS FOR
 EACH FLOOR. THIS WILL AID IN FOLLOWING THE RISERS THRU
 THE BUILDING AND DECREASE REVIEW TIME. SECTION
 106.1.2.
  
 9. SHT P1.1 SHOW THE SECONDARY ROOF DRAINS/OVERFLOW
 SCUPPERS FOR THE LOWER ROOF AT THE SOUTH SIDE OF THE
 BUILDING. SECTION 1107 & ALL SUBSECTIONS.
  
 10. SHT P1.2 DETAIL 03 SHOWS A LOWER ROOF ON THE SOUTH
 SIDE OF THE BUILDING, BUT NO PIPING IS SHOWN TO THE
 ROOF DRAINS. PLEASE CLARIFY. SECTION 106.1.1 & TABLE
 1106.3.
  
 11. SHT P3.2 RWL-3 MINIMUM 8" PIPE REQUIRED ON THE
 HORIZONTAL (9288SF). TABLE 1106.3.
  
 12. SHT P3.2 RWL-2 MINIMUM 8"PIPE REQUIRED ON THE
 HORIZONTAL (9288SF). TABLE 1106.3.
  
 13. SHT P3.2 RWL-1 MINIMUM 12"PIPE REQUIRED ON THE
 HORIZONTAL (23214SF). TABLE 1106.3.
  
 14. SHT P3.2 RWL-1 RISER DOES NOT REFLECT THE FLOOR
 PLAN. AREA DRAINS ARE SHOWN ON THE RIGHT SIDE OF THE
 RISER ON THE FLOOR PLAN AND THE OFFSET AT THE BASE OF
 THE RISER IS NOT SHOWN. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
  
 15. SHT P3.2 THE CONDENSATE SHALL RUN SEPARATELY TO THE
 CATCH BASIN, NOT DISCHARGE INTO THE STORM RISER
 DIAGRAM. PLEASE CONNECT THE CONDENSATE TO THE STORM.
 SECTION 1106.3 & TABLE 1106.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  