2007-10-26 18:48:02 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT T-1 WHITE OUT NOT APPROVED ON SIGNED SEALED |
| PLANS. SECTION 106.1.3. |
| |
| 2. SHT T-1 THE SHEET INDEXSHOWS SHEETS LP-0, LP-1, |
| LP-2, LP-3 & IRR-1 & IRR-2, BUT THESE SHEETS WERE NOT |
| SUBMITTED. PLEASE CORRELATE INDEX WITH SHEETS |
| SUBMITTED. SECTION 106.1.1. |
| |
| 3. SURVEY SHEET. THE ADDRESS IN THE TITLE BLOCK DOES |
| NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE |
| DBPR WEBSITE. PLEASE UPDATE THE TITLE BLOCK OR THE DBPR |
| WEBSITE PRIOR TO RESUBMITTING FOR REVIEW. FAC |
| 61G1-16.004(1), 61G15-23.002(2) & FS 472.025. |
| |
| 4. SHT A2.1 DETAIL 05 SCUPPER SHOWS AN 8" OVERFLOW |
| OPENING OPPOSITE THE SCUPPER OPENING FROM THE ROOF. |
| THIS SEEMS LIKE THE WATER WILL DRAIN OUT THIS OPENING |
| AS WELL AS DRAIN DOWN THE DOWNSPOUT. PLEASE CLARIFY. |
| SECTION 106.1.2 & SECTION 1106. |
| |
| 5. SHT A5-D.2 DETAIL 01 IDENTIFY THE DETAIL. NO DETAIL |
| TITLE INDICATED. WHAT IS THE DRAIN FOR? PLEASE CLARIFY. |
| SECTION 106.1.1 & TABLE 1106.3. |
| |
| 6. SHT A9.1 DETAIL 02. SHOW COMPLIANCE WITH THE |
| FOLLOWING: |
| A. 11-4.24.4 SINK DEPTH |
| B. 11-4.24.5 CLEAR FLOOR SPACE |
| C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| D. 11-4.24.7 FAUCETS |
| |
| 7. SHTS P1.1 & P1.2 PLANS SHALL BE DRAWN TO A MINIMUM |
| 1/8TH SCALE. SECTION 106.1.3. |
| |
| 8. SHTS P1.1 & P1.2 SHOW ALL RWL RISER DESIGNATIONS FOR |
| EACH FLOOR. THIS WILL AID IN FOLLOWING THE RISERS THRU |
| THE BUILDING AND DECREASE REVIEW TIME. SECTION |
| 106.1.2. |
| |
| 9. SHT P1.1 SHOW THE SECONDARY ROOF DRAINS/OVERFLOW |
| SCUPPERS FOR THE LOWER ROOF AT THE SOUTH SIDE OF THE |
| BUILDING. SECTION 1107 & ALL SUBSECTIONS. |
| |
| 10. SHT P1.2 DETAIL 03 SHOWS A LOWER ROOF ON THE SOUTH |
| SIDE OF THE BUILDING, BUT NO PIPING IS SHOWN TO THE |
| ROOF DRAINS. PLEASE CLARIFY. SECTION 106.1.1 & TABLE |
| 1106.3. |
| |
| 11. SHT P3.2 RWL-3 MINIMUM 8" PIPE REQUIRED ON THE |
| HORIZONTAL (9288SF). TABLE 1106.3. |
| |
| 12. SHT P3.2 RWL-2 MINIMUM 8"PIPE REQUIRED ON THE |
| HORIZONTAL (9288SF). TABLE 1106.3. |
| |
| 13. SHT P3.2 RWL-1 MINIMUM 12"PIPE REQUIRED ON THE |
| HORIZONTAL (23214SF). TABLE 1106.3. |
| |
| 14. SHT P3.2 RWL-1 RISER DOES NOT REFLECT THE FLOOR |
| PLAN. AREA DRAINS ARE SHOWN ON THE RIGHT SIDE OF THE |
| RISER ON THE FLOOR PLAN AND THE OFFSET AT THE BASE OF |
| THE RISER IS NOT SHOWN. PLEASE CORRELATE RISER AND |
| FLOOR PLAN. SECTION 106.1.1. |
| |
| 15. SHT P3.2 THE CONDENSATE SHALL RUN SEPARATELY TO THE |
| CATCH BASIN, NOT DISCHARGE INTO THE STORM RISER |
| DIAGRAM. PLEASE CONNECT THE CONDENSATE TO THE STORM. |
| SECTION 1106.3 & TABLE 1106.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |