2007-10-29 15:15:34REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG LS.0 DECLARES AN ENCLOSED PARKING GARAGE, BUT
 LS.1 AND LS.2 ARE SHOWING AN OPEN PARKING GARAGE.
 CORRECT ALL REFERENCES, SHOWING THIS TO BE AN ENCLOSED
 PARKING GARAGE. FBC 406.2.1
  
 2. PG M1.1: EF-1, EF-2, EF-20 AND RELATED DUCTWORK,
 WHAT IS THEIR ELEVATION? APPLIANCES LOCATED IN PUBLIC
 GARAGES OR OTHER AREAS FREQUENTED BY MOTOR VEHICLES,
 SHALL BE INSTALLED A MINIMUM OF 8 FEET ABOVE THE FLOOR.
 WHERE MOTOR VEHICLES EXCEED 6 FEET IN HEIGHT AND ARE
 CAPABLE OF PASSING UNDER AN APPLIANCE, APPLIANCES SHALL
 BE INSTALLED A MINIMUM OF 2 FEET HIGHER ABOVE THE FLOOR
 THAN THE HEIGHT OF THE TALLEST VEHICLE UNLESS THE
 APPLIANCES ARE PROTECTED FROM MOTOR VEHICLE IMPACT AND
 INSTALLED IN ACCORDANCE WITH NFPA 88B. FBC,M 304.5
  
 3. PG M1.1: EF-11 IN STORAGE ROOM 1.108 IS SHOWN TO
 DISCHARGE INSIDE THE ENCLOSED PARKING GARAGE. THE AIR
 REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM SHALL BE
 DISCHARGED OUTDOORS AT A POINT WHERE IT WILL NOT CAUSE
 A NUISANCE AND FROM WHICH IT CANNOT AGAIN BE READILY
 DRAWN IN BY A VENTILATING SYSTEM IN ACCORDANCE WITH
 FBC,M 501.2. AN ENCLOSED PARKING GARAGE IS NOT
 OUTDOORS. SHOW COMPLIANCE WITH THIS SECTION.
  
 4. PG M0.1: FAN SCHEDULE CALLS FOR EF-12 IN STORAGE
 ROOM 1.109. HOWEVER, EF-12 IS NOT SHOWN ON PG M1.1 AND
 PG M1.2 SHOWS EF-11 IN THIS ROOM. COORDINATE ALL FLOOR
 PLANS AND SCHEDULES. FBC,M 501.1 AND FBC 106.1.1. ALSO,
 EF-12 IN ROOM 1.109 IS DISCHARGING INTO THE ENCLOSED
 PARKING GARAGE. THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS AT A POINT
 WHERE IT WILL NOT CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM IN ACCORDANCE WITH FBC,M 501.2. AN ENCLOSED
 PARKING GARAGE IS NOT OUTDOORS. SHOW COMPLIANCE WITH
 THIS SECTTION.
  
 5. PG M1.1: EF-20 ON 1ST FLOOR, EF-21 ON 2ND FLOOR,
 EF-5A AND EF-22 ON 3RD FLOOR ARE NOT SHOWN TO BE
 PROTECTED FROM MECHANICAL DAMAGE. SHOW THESE FANS TO BE
 PROTECTED FROM VEHICLE IMPACT OR OTHER MECHANICAL
 DAMAGE IN ACCORDANCE WITH FBC,M 303.4 AND 304.5.
  
 6. PG M1.2: EF-23 ON 4TH FLOOR AND EF-24 ON 5TH FLOOR
 ARE NOT SHOWN TO BE PROTECTED FROM MECHANICAL DAMAGE.
 SHOW THESE FANS TO BE PROTECTED FROM VEHICLE IMPACT OR
 OTHER MECHANICAL DAMAGE IN ACCORDANCE WITH FBC,M 303.4
 AND 304.5.
  
 7. PG M2.1: KEY NOTE #3, WILL 7 FT BE AT LEAST 2 FT
 ABOVE THE HEIGHT OF THE TALLEST VEHICLE IN THE GARAGE?
 SHOW COMPLIANCE WITH FBC,M 304.5.
  
 8. PG M2.1 DETAIL 02: L-13 O.A INTAKE LOUVER IS
 ADJACENT TO THE PARKING GARAGE ENTRANCE. MECHANICAL
 OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM
 OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS
 IN ACCORDANCE WITH FBC,M 401.5.1. SHOW A LOCATION FOR
 THE O.A. INTAKE WHICH IS IN COMPLIANCE WITH THIS
 SECTION.
  
 9. PG M2.1 DETAIL 02: EF-13, 14 AND 16, ARE THESE
 EXHAUST OUTLETS DISCHARGING ONTO WALKWAYS? SHOW
 COMPLIANCE WITH FBC,M 401.5.2. ALSO, EF-16 SHALL
 DISCHARGE DIRCTLY TO THE OUTDOORS IN ACCORDANCE WITH
 FBC,M 501.2.
  
 10. PG M2.1 DETAIL 02: EF 13, 14 AND 16 EXHAUST DUCTS,
 IF THE WALL SEPARATING OFFICES FROM THE PARKING GARAGE
 ARE REQUIRED TO BE FIRE RESISTANCE RATED (SEE BUILDING
 REVIEW COMMENTS), SHOW HOW DUCT PENETRATIONS OF RATED
 WALL ASSEMBLIES ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBC,M 607.5 OR 607.1.1.
  
 11. PG M2.1 DETAIL 02: EF-17 IS DISCHARGING INTO AN
 ENCLOSED PARKING GARAGE. THE AIR REMOVED BY EVERY
 MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS
 AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM
 WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A
 VENTILATING SYSTEM IN ACCORDANCE WITH FBC,M 501.2. AN
 ENCLOSED PARKING GARAGE IS NOT OUTDOORS. SHOW
 COMPLIANCE WITH THIS SECTTION. ALSO, SEE COMMENT #10
 ABOVE REGARDING OPENING PROTECTION IN RATED WALL
 ASSEMBLIES.
  
 12. PG M2.1 DETAIL 01: EF-11 (OR EF-12, ACCORDING TO
 THE FAN SCHEDULE) IS DISCHARGING INTO AN ENCLOSED
 PARKING GARAGE. THE AIR REMOVED BY EVERY MECHANICAL
 EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS AT A POINT
 WHERE IT WILL NOT CAUSE A NUISANCE AND FROM WHICH IT
 CANNOT AGAIN BE READILY DRAWN IN BY A VENTILATING
 SYSTEM IN ACCORDANCE WITH FBC,M 501.2. AN ENCLOSED
 PARKING GARAGE IS NOT OUTDOORS. SHOW COMPLIANCE WITH
 THIS SECTTION. ALSO, SEE COMMENT #10 ABOVE REGARDING
 OPENING PROTECTION IN RATED WALL ASSEMBLIES.
  
 13. PG M2.1 DETAIL 02: EF-13 AND EF-14, WHAT IS THE
 METHOD OF CONTROL FOR THESE FANS? ALL AIR SUPPLIED TO
 THESE SPACES SHALL BE EXHAUSTED IN ACCORDANCE WITH
 FBC,M 403.2.1(3). THEY MAY BE INTERLOCKED WITH AHU-2,
 RUN CONTINUOUS OR BE PROVIDED WITH TRANSFER AIR FOR
 MAKE-UP OF EXHAUST. ALSO, VENTILATION SHALL BE PROVIDED
 DURING OCCUPANCY IN ACCORDANCE WITH FBC,M 401.3.
  
 14. PG M2.1 DETAIL 02: OFFICE 1.210, THERE IS NO RETURN
 SHOWN IN THE CEILING FOR THIS HABITABLE ROOM. SHOW
 COMPLIANCE WITH FBC,M 601.4. ALS, PLEASE SEE THE
 FOLLOWING COMMENT REGARDING RETURN AIR FLOW ABOVE THE
 CEILING.
  
 15. PG M2.1 DETAILS 02 AND 04: FLOOR PLANS SHOW PLENUM
 CEILINGS WITH FREE-FLOW RETURNS BACK TO AHU'S. HOWEVER,
 WALL TYPES AS SHWON ON PG A5-D.1 AND A6.1 SHOW
 PARTITIONS FROM FLOOR TO DECK IN MOST AREAS. HOW WILL
 RETURN AIR FLOW BACK TO AHU'SWHEN BLOCKED BY
 PARTITIONS? CHOW COMPLIANCE WITH FBC,M 601.4. NOTE: IF
 PARTITION TYPES ARE CHANGED, DUCTS FOR EF'S 13, 14 AND
 16 SHOULD NOT BE EXPOSED TO PLENUM IN ACCORDANCE WITH
 FBC,M 601.3.
  
 16. PG M2.1 DETAIL 02 AND 04: AHU'S 3 AND 4 ON 1ST
 FLOOR SHARE A COMMON RETURN PLENUM AND ARE REQUIRED TO
 HAVE FAN SHUT-DOWN BY SMOKE DETECTOR IN ACCORDANCE WITH
 FBC,M 606.2.2. THE SAME CONDITION OCCURS ON 2ND FLOOR
 WITH AHU'S 5 AND 6. SHOW COMPLIANCE WITH THIS SECTION
 IN THESE AREAS. NOTE: DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IF ONE IS
 REQUIRED BY CODE. FBC,M 606.4.1
  
 17. PG M2.1 DETAIL 03: AHU'S 1 AND 2 ARE EACH OVER 2000
 CFM AND REQUIRE FAN SHUT-DOWN BY SMOKE DETECTOR IN
 ACCORDANCE WITH FBC,M 606.2.1. SHOW COMPLIANCE WITH
 THIS SECTION. NOTE: DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IF ONE IS
 REQUIRED BY CODE. FBC,M 606.4.1
  
 18. PG M2.1 DETAIL 03: THE 12X10 O.A. DUCT IS PASSING
 THROUGH A TENANT SEPARATION WALL BETWEEN THE TWO
 MERCANTILE UNITS. IF THIS WALL REQURES A FIRE
 RESISTANCE RATING (SEE BUILDING REVIEW COMMENTS) PLEASE
 SHOW OPENING PROTECTIVES AT THIS PENETRATION IN
 ACCORDANCE WITH FBC,M 607.5.
  
 19. PG M2.1 DETAIL 03: THE 24X24 VERTICAL O.A. DUCT IS
 SHOWN PENETRATING A RATED FLOOR/CEILING ASSEMBLY (SEE
 BUILDING REVIEW COMMENTS). SHOW THIS PENETRATION TO BE
 PROTECTED IN ACCIRDANCE WITH FBC,M 607.6.
 NOTE: COORDINATE ANY CHANGES IN FLOOR PLANS BETWEEN
 ARCHITECTURAL AND MECHANICAL DESIGNERS TO ENSURE ALL
 PENETRATIONS OF RATED ASSEMBLIES ARE PROTECTED IN
 ACCORDANCE WITH FBC,M SEC.607 AND FBC CH.7.
  
 20. PG M2.1 DETAILS 02 AND 04: WHAT IS THE SIZE OF THE
 O.A. BRANCH DUCTS FEEDING AHU'S 3 AND 5? HOW WILL THIS
 DUCT BE TIED TO THE AHU'S SINCE THIS IS AN OPEN RETURN
 CEILING? PROVIDE HANGING DETAIL FOR AHU'S SHOWING DUCT
 CONNECTIONS, HOW UNITS ARE HING AND ATTACHED TO
 STRUCTURE AS WELL AS THE MEANS OF AUXILIARY DRAIN
 PROTECTION. FBC,M 301.1, 307.2.3, 603.1, FBC 106.1.2
  
 21. PG M2.1 DETAIL 02,03,04: AHU 1-6 OUTSIDE AIR DUCTS
 FOR VENTILATION SHALL BE DESIGNED TO BE CAPABLE OF
 REDUCING THE SUPPLY OF OUTDOOR AIR TO THE MINIMUM
 VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF ASHRAE
 62. SYSTEMS MAY BE DESIGNED TO SUPPLY OUTSIDE AIR
 QUANTITIES EXCEEDING MINIMUM LEVELS, BUT THEY SHALL BE
 CAPABLE OF OPERATING AT NO MORE THAN MINIMUM LEVELS
 THROUGH THE USE OF RETURN DUCTS, MANUALLY OR
 AUTOMATICALLY OPERATED CONTROL DAMPERS, FAN VOLUME
 CONTROLS, OR OTHER DEVICES IN ACCORDANCE WITH FBC
 13-409.1.ABC.1.1. ALSO, BOTH OUTDOOR AIR SUPPLY AND
 EXHAUST SYSTEMS SHALL BE EQUIPPED WITH MOTORIZED
 DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SYSTEMS
 OR SPACES SERVED ARE NOT IN USE. VENTILATION OUTSIDE
 AIR DAMPERS SHALL BE CAPABLE OF AUTOMATICALLY SHUTTING
 OFF DURING PREOCCUPANCY BUILDING WARMUP, COOLDOWN, AND
 SETBACK, EXCEPT WHEN VENTILATION REDUCES ENERGY COSTS
 (E.G., NIGHT PURGE) OR WHEN VENTILATION MUST BE
 SUPPLIED TO MEET CODE REQUIREMENTS. FBC
 13-409.1.ABC.3.3.
  
 22. PG M0.1 AND M2.1: AC SYSTEMS 1-6 SHALL BE EQUIPPED
 WITH AUTOMATIC SHUTDOWN CONTROLS IN ACCORDANCE WITH FBC
 13-407.1.ABC.2.4.1. SHOW COMPLIANCE WITH THIS SECTION.
  
 23. PROVIDE ENERGY CALCULATIONS IN THE FORM OF AN
 APPROVED ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH
 FBC 13-101.1.1 AND 13-103.2.
  
 24. BUILDING CAVITIES WHICH WILL BE USED AS RETURN AIR
 PLENUMS (CEILING SPACES) SHALL BE LINED WITH AN AIR
 BARRIER AND SEALED IN ACCORDANCE WITH SECTION
 410.1.ABC.3.7 AND SHALL BE INSULATED IN ACCORDANCE WITH
 SECTION 410.1.ABC.2. SEE FBC 13-410.1.ABC.3.6.
  
 25. PG M4.1: PROVIDE WALL MOUNTING DETAIL FOR DUCTLESS
 SPLIT SYSTEMS TW-1 THROUGH TW-7, SHOWING WALL BRACKET,
 ANCHORING, REQUIRED CLEARANCES FOR SRVICE AND PROPER
 AIRFLOW AS REQUIRED BY MANUFACTURER'S INSTRUCTIONS IN
 ACCORDANCE WITH FBC,M 304.1 AND FBC 106.1.2.
  
 26. PG M4.1: DETAIL 5 SHOWS A CONDENSER INSTALLED ON A
 BUILT-UP ROOF SYSTEM. THIS DETAIL IS NOT APPLICABLE TO
 THIS PROJECT. PG M1.2 6TH FL PLAN SHOWS CONDENSERS
 INSTALLED ON THE TOP LEVEL OF THE PARKING STRUCTURE.
 SHOW HOW THESE UNITS ARE TO BE SECURED TO THE STRUCTURE
 TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE WITH FBC,M
 301.13 AND FBC CH.16.
  