Plan Review Notes
Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-11-15 16:53:43*****DENIED*****
  
 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.ON SHEET T-1, MAKE REFERENCE TO NFPA 101 - 2003
 EDITION, NOT 2004.
  
 03.ON SHEET T-1, INCLUDE THE STANDARD FOR PARKING
 STRUCTURES NFPA 88A - 2002 EDITION.
  
 04.DOORWAYS AND OTHER OPENINGS IN FIRE WALLS AND FIRE
 PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE DOORS
 INSTALLED IN ACCORDANCE WITH NFPA 80, STANDARD FOR FIRE
 DOORS AND WINDOWS.
  
 05.CLEAR AISLE SPACE SHALL BE MAINTAINED TO PERMIT
 READY ACCESS TO, AND THE USE OF, FIRE-FIGHTING
 EQUIPMENT.
  
 06.FLOORS SHALL BE KEPT CLEAN AND FREE OF OIL AND
 GREASE.
  
 07.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 08.ON SHEET LS.O, PROVIDE DISTANCE (IN FEET) OF THE
 ADJACENT FIRE HYDRANT LOCATED AT CLEMATIS AND ROSEMARY
 TO THE PROPOSED STRUCTURE.
  
 09.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTER'S EMERGENCY REQUIREMENTS OF ASME A17.1.
  
 10.ELEVATOR WARNING SIGNS (DO NOT USE IN EVENT OF
 FIRE) SHALL BE REQUIRED.
  
 11.PLEASE PROVIDE EMERGENCY LIGHTING FACILITIES FOR
 THE MEANS OF EGRESS AREAS FOR THIS STRUCTURE.
  
 12.DISPLAY/ILLUSTRATE THE NUMERICAL ADDRESS ON THE
 APPROPIATE EXTERIOR ELEVATION WHICH FRONTS CLEMATIS
 STREET.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL
 BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 STROKE.
  
 13.ON SHEET A4.3, ILLUSTRATE THAT THE DOUBLE DETECTOR
 VALVE ASSEMBLY IS TO CHAINED AND LOCKED.
  
 14.ON SHEET E0.1, REFERENCE IS TO MADE TO NFPA 13 -
 2002 EDITION, NOT 1999.
  
 15.KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTIONS (FDC).FOR A APPLICATION,
 CONTACT WEST PALM BEACH FIRE PREVENTION AT
 561-804-4724.
  
 16.SEPARATE PLAN AND PERMIT WILL BE REQUIRED FO THE
 FIRE SPRINKLER SYSTEM INSTALLATION.
  
 17.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 18.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722