2007-11-15 16:53:43 | *****DENIED***** |
| |
| 01.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE |
| BLOCK OF EACH SUBMITTED PLAN SHEET. |
| |
| 02.ON SHEET T-1, MAKE REFERENCE TO NFPA 101 - 2003 |
| EDITION, NOT 2004. |
| |
| 03.ON SHEET T-1, INCLUDE THE STANDARD FOR PARKING |
| STRUCTURES NFPA 88A - 2002 EDITION. |
| |
| 04.DOORWAYS AND OTHER OPENINGS IN FIRE WALLS AND FIRE |
| PARTITIONS SHALL BE PROTECTED WITH APPROVED FIRE DOORS |
| INSTALLED IN ACCORDANCE WITH NFPA 80, STANDARD FOR FIRE |
| DOORS AND WINDOWS. |
| |
| 05.CLEAR AISLE SPACE SHALL BE MAINTAINED TO PERMIT |
| READY ACCESS TO, AND THE USE OF, FIRE-FIGHTING |
| EQUIPMENT. |
| |
| 06.FLOORS SHALL BE KEPT CLEAN AND FREE OF OIL AND |
| GREASE. |
| |
| 07.A TEMPORARY STANDPIPE SYSTEM IS REQUIRED WHEN THE |
| BUILDING REACHES THREE STORIES OR THIRTY FEET IN |
| HEIGHT. |
| |
| 08.ON SHEET LS.O, PROVIDE DISTANCE (IN FEET) OF THE |
| ADJACENT FIRE HYDRANT LOCATED AT CLEMATIS AND ROSEMARY |
| TO THE PROPOSED STRUCTURE. |
| |
| 09.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| FIGHTER'S EMERGENCY REQUIREMENTS OF ASME A17.1. |
| |
| 10.ELEVATOR WARNING SIGNS (DO NOT USE IN EVENT OF |
| FIRE) SHALL BE REQUIRED. |
| |
| 11.PLEASE PROVIDE EMERGENCY LIGHTING FACILITIES FOR |
| THE MEANS OF EGRESS AREAS FOR THIS STRUCTURE. |
| |
| 12.DISPLAY/ILLUSTRATE THE NUMERICAL ADDRESS ON THE |
| APPROPIATE EXTERIOR ELEVATION WHICH FRONTS CLEMATIS |
| STREET.AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL |
| BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN |
| STROKE. |
| |
| 13.ON SHEET A4.3, ILLUSTRATE THAT THE DOUBLE DETECTOR |
| VALVE ASSEMBLY IS TO CHAINED AND LOCKED. |
| |
| 14.ON SHEET E0.1, REFERENCE IS TO MADE TO NFPA 13 - |
| 2002 EDITION, NOT 1999. |
| |
| 15.KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE |
| DEPARTMENT CONNECTIONS (FDC).FOR A APPLICATION, |
| CONTACT WEST PALM BEACH FIRE PREVENTION AT |
| 561-804-4724. |
| |
| 16.SEPARATE PLAN AND PERMIT WILL BE REQUIRED FO THE |
| FIRE SPRINKLER SYSTEM INSTALLATION. |
| |
| 17.FIRE SPRINKLER SYSTEM IS TO BE MONITORED. |
| |
| 18.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND |
| OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |