Plan Review Notes For Permit 07090764
Permit Number 07090764
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-20 18:58:562007-10-20 18:58:56
  
 *** DENIED***
  
 **THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
  
 CITY PARKING GARAGE.
 500 BANYAN BLVD.
  
 ** PLEASE SEE THERE ARE ITEMS WHICH WERE NOT SUBMITTED
 FOR REVIEW OR WHICH WILL REQUIRE CHANGE ON PLANS WHICH
 MAY GENERATE NEW COMMENTS ON THE FOLLOWING REVIEW.
 THESE COMMENTS ARE BASED ON PLANS AND DOCUMENTATION
 PROVIDED.
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
 2003 NFPA-20
  
 ** PLEASE SEE FOR EXAMPLE THE T-1 SHEET WHICH CONTAINS
 CODE WHICH IS NOT ACCURATE OR NO LONGER ADOPTED BY THE
 STATE.
 PLEASE SEE THE 2002 NEC NOTED, PLEASE SEE A 2004
 NFPA-101 WAS NOTED AND 2003 REVISIONS TO THE FBC.
 PLEASE SEE SOME OF THE CODE ON LS SHEET HAS BEEN
 UPDATED HOWEVER LS SHEET STILL INDICATES SOME CODE NO
 LONGER IN ADOPTION.
 ** MANY OF THESE ARE OK ON ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE SHEET T-1 WHICH CONTAINS
 *WHITE-OUT* ON SHEETS COVERING FIRE ALARM ON LEGEND.
 PLEASE SEE THE FIRE ALARM PLANS ARE NEEDED AND REQUIRED
 WITH THE BASE BUILDING PLANS FOR REVIEW.
 PLEASE KNOW EVEN THOUGH THE FA IS UNDER SEPARATE PERMIT
 PLEASE SUBMIT THESE AT THIS TIME TO SHOW BASE DESIGN
 INTENT AND PROTECTION.
 PLEASE SEE FBC 11-4.28.1, .2, AND .3(4) AS THE MINIMUM
 DEVICE LOCATIONS AND LEVELS FOR ADA COMPLIANCE.
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEET
 FOR THE GENERATOR, FIRE PUMP, FIRE PUMP CONTROLLER, ATS
 AND SUB-BASE FUEL TANK.
 PLEASE SEE OTHER COMMENTS BELOW WHICH WILL AFFECT THE
 DOCUMENTS AND INFORMATION AS SHOWN ON PLANS. 110.3,
 90.7OF NEC,NFPA-20 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE:PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 THIS WAS DONE ON THE ARCHITECTS SHEETS HOWEVER NOT
 ALL.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 5) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 EGRESS PATHS WHICH MEET THE MINIMUM LIGHTING LEVELS AS
 REQUIRED PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE 7.8.1.3, 7.9.2.2
 MOST OF THESE WERE SUBMITTED HOWEVER PLEASE SEE THE
 MINIMUM AVERAGE ON SHEETS FOR NORMAL DO NOT MEET THE
 MINIMUM LEVELS.
 PLEASE ALSO SEE FOR EXAMPLE THE SPIRAL STAIRS LOCATED
 IN OFFICE LOCATIONS.
 PLEASE SEE THE FOLLOWING LOCATIONS ARE REQUIRED TO
 CONTAIN SOME SORT OF BATTERY BACK UP LIGHTING FIXTURE.
 THE STAIR TOWERS WILL REQUIRE A BATTERY BACK UP FIXTURE
 OF SOME TYPE TO MEET THE MINIMUM OF 1FT CANDLE LEVEL
 UNDER EMERGENCY.7.8.2.1, 7.9.2.2
 PLEASE SEE THE OTHER LOCATIONS WILL BE THE GENERATOR
 ROOM, FIRE PUMP ROOM, MAIN ELECTRICAL ROOM, EMERGENCY
 MAIN ELECTRICAL ROOM, AND THE ELEVATOR EQUIPMENT ROOMS.
 (SOME OF THESE MAY ALREADY SHOW A BATTERY BACK UP
 FIXTURE, BUT MOST DO NOT).
 700.12F.
 PLEASE SEE 700.16 FOR THESE SAME ROOMS.
  
 6) NOTE: PLEASE SEE THE PLANS FOR LIGHTING AND POWER
 INDICATES ELECTRICAL LIGHTING AND RECEPTACLE IN THE FPL
 VAULT WHICH IS NOT PERMITTED PER FPL. THIS ROOM IS ALSO
 FPL LEGAL EASEMENT AREA AND IS NOT CONSIDERED PART OF
 THE GARAGE BUILDING.
  
 7) NOTE: PLEASE SEE THE ADDRESS OF THIS STRUCTURE WAS
 GIVEN AS 500 BANYAN BLVD.
 PLEASE ADJUST ALL TITLE BLOCKS TO INCLUDE THE ADDRESS.
 PLEASE BE SURE TO SEE THAT THERE ARE SEVERAL LOCATIONS
 ON PLANS WHICH MENTIONS THE *CLEMATIS ST GARAGE*
 INCLUDING TITLE BLOCKS.
 IF THE ADDRESS IS ASSIGNED AS BANYAN BLVD, PLEASE
 ADJUST. (ANY REQUEST FOR LOCATION DESIGNATION CHANGE
 NEEDS TO GO THROUGH ADDRESSING REVIEWER).
 FAC 61G15-23.002, 61G1-16.004
 FBC 110.1.2, 106.5, ETC ADMIN SECTION.
  
 8) NOTE: PLEASE KNOW THE ROOF TOP LIGHTING POLES WILL
 BE REQUIRED TO HAVE STRUCTURAL WIND LOAD CALCULATIONS
 AND WILL BE REVIEWED BY THE BUILDING REVIEWER.
 ** THIS IS NOTED FOR INFORMATION.
  
 9) NOTE: PLEASE SEE THE EXHAUST FANS ON E1.1 ARE NOT
 SHOWN ON ENLARGED PLANS FOR THE SAME ROOM.
 FBC 106.1.2 FOR COORDINATION.
  
 10) NOTE: PLEASE SEE 620.22-620.24 AS THE REQUIRED
 DEDICATED CIRCUITS NEEDS TO BE FOR EACH ELEVATOR
 EQUIPMENT ROOM.
 PLEASE SEE THE PLANS CURRENTLY SHOW THE SAME CIRCUITS
 FOR BOTH ROOMS WHICH IS NOT PERMITTED.
  
 11) NOTE: PLEASE SEE 110.26C AS THE DOOR SWINGS ON
 ELECTRICAL ROOM DOORS MAY NOT SWING IN. PLEASE BE SURE
 TO ADJUST ON ELECTRICAL SHEETS AND BE SURE TO GIVE
 INFORMATION TO OTHER DESIGNERS FOR COORDINATION OF ALL
 SHEETS FOR ALL TRADES.
  
 12) NOTE: PLEASE CONTACT THE STATE OF FLORIDA GOVERNING
 ELEVATOR EQUIPMENT ROOMS. IT HAS COME TO THE ATTENTION
 ON THIS OFFICE THAT SEVERAL LOCATIONS WHEN BEING
 INSPECTED BY THE STATE FOR ELEVATOR CERTIFICATION ARE
 BEING REQUIRED TO HAVE THE EQUIPMENT ROOM AIR
 CONDITIONED. THIS IS NOT IN THE ELECTRICAL CODE.
  
 13) NOTE: PLEASE SEE 620.23 AS THE EXPLANATORY NOTE IN
 THE HANDBOOK FOR ELEVATOR PIT LIGHTING REQUIRES A 5FT
 CANDLE LIGHTING LEVEL.
 PLEASE SEE THE FOLLOWING WHICH WAS EXTRACTED FOR THIS
 SECTION ON THE NEC.
 *ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.*
  
 14) NOTE: PLEASE CLARIFY THE LIGHTING CONTROL SYSTEM
 BEING PROPOSED FOR THE ENTIRE PARKING GARAGE. PLEASE
 VERIFY WITH THE CITY IF THE GARAGE AREA WHICH DO NOT
 INCLUDE ROOMS AND OFFICES IS GOING TO BE A 24HR
 OPERATION.
 IF THIS IS 24 HR OPERATION AND USE, THEN NO LIGHTING
 CONTROL SYSTEM WOULD BE SHOWN FOR MANY OF THESE
 LIGHTING FIXTURES.
 PLEASE SE THERE ARE AREAS IN WHICH THE LIGHTING
 CONTROLS FOR DURING DAYLIGHT HOURS ARE IN QUESTION. IF
 THE LIGHTING LEVELS INSIDE THE GARAGE DURING THE DAY
 FALL BELOW MINIMUM SAFETY LEVELS FOR EGRESS, WHAT WILL
 TURN THE LIGHTING ON?
 PLEASE SEE THE CIRCUITING WILL NEED TO BE ADJUSTED
 ALONG WITH ANY LIGHTING CONTROLS.
 AS THERE ARE SEVERAL UNANSWERED QUESTIONS ON THIS NOTE,
 THIS MAY NEED TO BE GONE OVER WITH CITY STAFF OTHER
 THAN PLAN REVIEW. PLANS REVIEW WILL BE FOR MINIMUM
 LIGHTING LEVELS AND CONTROLS OF THOSE LEVELS. PLEASE
 SEE 13-415.1.ABC.1, 13-415.1.ABC.1.4 ETC
  
 15) NOTE: PLEASE SEE THAT MORE INFORMATION WILL BE
 NEEDED FOR LIGHTING IN OFFICES AND DUE TO THE
 ADJUSTMENTS POSSIBLY WITH NOTE #14 ABOVE, THE OFFICES,
 MEETINGS ROOMS ETC MAY NEED TO BE GONE OVER. PLEASE SEE
 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE MISSING
 LIGHTING CONTROLS IN RETAIL AREAS.
  
 16) NOTE: PLEASE SEE MISSING ENERGY CALCULATIONS,
 LIGHTING PERFORMANCE CALCULATIONS PER 13-415.2 AND
 13-415.2.ABC.1.3 ETC.
 PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER WHICH
 WILL BE FORTH COMING.
 PLEASE SEE SOME AREAS OF THIS BUILDING WILL HAVE
 CONDITIONED SPACE.
  
 17) NOTE: PLEASE PROVIDE COMPLETED INFORMATION FOR FIRE
 PUMP AND LOCKED ROTOR OVER CURRENT PROTECTION AND
 AMPERAGES.
 PLEASE SEE NEC 695.4B1, 9.3.2.2.3.2(A), (B) ETC PLEASE
 SEE THE ELECTRICAL PLANS INDICATE A DISCONNECT WITH
 OVER CURRENT PROTECTION AHEAD OF THE FIRE PUMP
 CONTROLLER WHICH WILL ALSO CONTAIN OVER CURRENT
 PROTECTION. PLEASE KNOW THERE MAY NOT BE OVER CURRENT
 PROTECTION ON THE LINE SIDE OF THE FIRE PUMP
 CONTROLLER. THE TYPICAL LISTED FIRE PUMP CONTROLLER
 CONTAINS THE LOCKED ROTOR CURRENT SETTING FOR THE
 SELECTED PUMP AND ASSEMBLY. 10.4.4.1 NFPA-20 PLEASE
 ALSO SEE THE FIRE PUMP IS BEING SHOWN AS 60 HP ON FP
 SHEETS AND 75HP ON ELECTRICAL SHEETS.
 PLEASE SEE PROVIDE INFORMATION ON WHAT TYPE OF BREAKERS
 ARE ON THE SECONDARY EMERGENCY SIDE FOR FIRE PUMP
 POWER. AS THE FIRE PUMP IS BEING FED THROUGH A TOTAL OF
 THREE BREAKERS ON THE EMERGENCY SIDE, THESE MAY CREATE
 AN ISSUE WITH SELECTIVE COORDINATION.
 PLEASE SEE THESE BREAKERS ARE TYPICALLY MAGNETIC TYPE.
 PLEASE SEE NEC 695 AND NFPA-20CHAPTER 9 AND 10.
  
 18) NOTE: PLEASE PROVIDE THE MINIMUM FUEL TIMES FOR
 EMERGENCY GENERATOR AND FUEL FOR FIRE PUMP. NFPA-20
 9.6.2.2. (8HRS PLUS OTHER LOADS)
  
 19) NOTE: PLEASE SEE THE RISER INDICATES THE NORMAL
 FEED FROM FPL TO THE EMERGENCY SIDE OF THE FIRE PUMP
 CONTROLLER/ATS.
 PLEASE SEE THIS APPEARS TO BE A MISPRINT AND WILL NEED
 TO BE REVISED.
 FBC 106.1.2 FOR COORDINATION.
 NEC 695.1
  
 20) NOTE: PLEASE SEE GROUNDING DETAIL FOR GENERATOR
 DOES NOT ACCURATELY REFLECT THE SERVICE EQUIPMENT. FBC
 106.1.2 FOR COORDINATION,
 230.2, 230.70, 250.50 ETC
  
 21) NOTE: PLEASE SEE AS THE RISER, PANELS AND EQUIPMENT
 NEED COORDINATION THERE ARE SOME ITEMS WHICH CAN NOT BE
 CONFIRMED AT THIS TIME.
 PLEASE SEE FOR EXAMPLE:
 A) THE RISER INDICATES THE MSB AS A 1200AMP WITH WHAT
 APPEARS TO BE A 800AMP BREAKER, HOWEVER THE MSB PANEL
 INDICATES THIS AS A 1200AMPS MAIN LUG ONLY DISTRIBUTION
 BOARD.
  
 B) PLEASE SEE 240.13, AND 230.95 CAN NOT BE CONFIRMED
 IF REQUIRED OR NOT.
  
 C) PLEASE SEE 250.30, 250.20 AND WHETHER OR NOT A
 4-POLE ATS IS REQUIRED CAN NOT BE CONFIRMED.
  
 D) PLEASE SEE 230.70, 230.71 ETC CAN ALSO NOT ME
 CONFIRMED. IF THIS MSB DOES NOT CONTAIN A MAIN, IT DOES
 NOT MEET EITHER OF THESE TWO SECTIONS OF CODE ALONG
 WITH SEVERAL OTHERS INCLUDING 240.4 AND 310.16
  
 THESE ARE SOME OF THE ITEMS WHICH NEED TO BE
 COORDINATED AND ADJUSTED ON PLANS.
  
 22) NOTE: PLEASE CLARIFY WHERE/HOW THE ADDITIONAL
 SERVICE FOR RETAIL CAN BE GRANTED PER 230.2.
  
 23) NOTE: PLEASE ADJUST AND PLACE ON THE LIGHTING
 PROTECTION PLANS. PLEASE KNOW ANY SYSTEM SHALL BE MEET
 NFPA-780. (UNDER SEPARATE PERMIT)
  
 24) NOTE: PLEASE CLARIFY FIXTURE SC ON LEGEND AND ON
 PLANS.
 PLEASE SEE THE CIRCUITING TO 5TH FLOOR LIGHTING WHICH
 IS CIRCUITED TO 1NGH-11 IS THE SAME AS THE CIRCUIT FOR
 WHAT APPEARS TO BE FEEDING THESE SC FIXTURES ON ROOF ON
 E6.1.
 PLEASE SEE ON PLANS ONLY ONE LOCATION SHOWS THE FIXTURE
 SC YET THE SYMBOL FOR THIS SAME FIXTURE APPEARS TO BE
 FOR OTHER FIXTURES BUT THEY ARE NOT LABELED OR
 IDENTIFIED.
 PLEASE COMPLETE, ADJUST AND COORDINATE.
 FBC 106.1.2.
 408.4, 310.16, 240.4 ETC
  
 25) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE
 OPERATION OF GATES.
 PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO
 OPERATION OF THESE GATES UNDER THE LOSS OF POWER.
 PLEASE SEE POSSIBLE CHAPTER 7 OF THE LS CODE.
 THIS IS ONLY BEING NOTED AS ANY CHANGES AND COMMENTS
 FROM OTHER TRADES SUCH AS BUILDING FOR CHAPTER 10 OF
 THE FBC AND CHAPTER 7 OF NFPA-101 WILL AFFECT THE
 ELECTRICAL PLANS.
  
 26) NOTE: PLEASE SEE THE SHEET E4.1 WHICH CONTAINS THE
 LOW VOLTAGE SYSTEMS/CONDUIT LOCATIONS IS LABELED AND
 IDENTIFIED AS LIGHTING PLANS AND DETAILS.
 FBC 106.1.2 FOR COORDINATION.
  
 27) NOTE: PLEASE SEE THE FEEDERS ON EDP1 IS NOT
 COMPLETE AT THIS TIME FOR MCC, AND ELEVATORS 1-4.
 PLEASE COMPLETE INFORMATION FOR THE SIZE OF THE
 ELEVATOR MOTORS SO THAT THE FEEDERS CAN BE SHOWN AND
 DETERMINED FOR CODE COMPLIANCE.
 PLEASE SEE THAT THE BASE OVER CURRENT PROTECTION AT THE
 ELEVATOR DISCONNECTS/CONTROLLERS ARE NOT REQUIRED AT
 THIS TIME UNLESS KNOWN. IF THIS INFORMATION IS KNOWN AT
 THIS TIME, THEN THIS WILL ALLEVIATE PLANS FROM HAVING
 TO BE REVISED AT A LATER DATE. AT SOME POINT IN TIME
 THE PLANS WILL BE REQUIRED TO SHOW AND INDICATE ALL OF
 THESE.
 PLEASE SEE NEC 620.1,240.4, 310.16, 408.4 ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 28) NOTE: PLEASE SEE THE MAIN MEANS OF DISCONNECT FOR
 THE FEEDERS FROM THE GENERATOR APPEARS TO BE FED
 THROUGH AND *BACK-FED* BREAKER IN MSBE.
 PLEASE NOTE REJECTION CLIP IF THIS IS INDEED THE CASE.
 PLEASE SEE FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 29) NOTE: PLEASE SEE 230.2E, 700.8 ETC AS ALL MAINS ARE
 REQUIRED TO BE LABELED.
 PLEASE SEE 230.2 AS THE POWER FOR THE EMERGENCY SERVICE
 EQUIPMENT IS BEING TAPPED FROM THE NORMAL ELECTRICAL
 SERVICE. IF THERE ARE ANY CHANGES PLEASE BE SURE TO
 LABEL ALL MAINS ACCORDINGLY.
 PLEASE SEE COMMENT ABOVE WITH RESPECT TO RETAIL SERVICE
 PROPOSED. AT THIS TIME THIS ADDITIONAL SERVICE AS SHOWN
 NOTED ON NOTE #22 ABOVE IS NOT GRANTED. EACH OF THOSE
 TENANT/RETAIL DISCONNECTS WOULD HAVE BEEN MAINS.
  
 30) NOTE: PLEASE SEE NOTE ABOVE WITH RESPECT TO
 LIGHTING CONTROLS AND EXTERIOR LIGHTING CONTROLS PER
 13-415.1.ABC.1.4.
 PLEASE CLARIFY HOW ALL LIGHTING ON FA?ADE IS BEING
 CONTROLLED.
 PLEASE SEE SOME OF THIS IS SHOWN BEING CONTROLLED FROM
 A PHOTO-CELL AS WELL AS A LIGHTING CONTROL PANEL. SEE
 CIRCUITING ON SCHEDULE.
 PLEASE SEE FBC 106.1.2 FOR COORDINATION.
  
 31) NOTE: PLEASE SEE NO INFORMATION FOR CONDUITS,
 CONDUCTORS, TAPS ETC ON THE RETAIL SERVICE EQUIPMENT IS
 SHOWN.
 PLEASE COMPLETE.
 PLEASE BE SURE TO SEE COMMENT #22 ETC FOR SERVICE.
  
 32) NOTE: PLEASE SEE NO GROUNDING ELECTRODE SYSTEM IS
 BEING SHOWN FOR THE SAME RETAIL SERVICE.
 250.50.
  
 33) NOTE: PLEASE SEE SELECTIVE COORDINATION IS NEEDED
 TO BE SHOWN FOR THE LIFE SAFETY ITEMS PER 240.12
  
 34) NOTE: PLEASE SEE TWO PERMIT APPLICATIONS WERE
 SUBMITTED AT TWO DIFFERENT TIMES ON THE SAME DAY. THE
 PERMIT APPLICATION WHICH DOES CONTAIN ALL OF THE
 SIGNATURES FOR SUB CONTRACTORS NEEDS TO BE NOTARIZED ON
 THE BACK WHERE THE CONTRACTORS AUTHORIZED AGENT IS
 SIGNED ON. THIS CAN BE DONE WHEN PLANS ARE RESUBMITTED.
 THE ORIGINAL APPLICATION WHICH WAS SUBMITTED WILL
 BECOME VOID.
 THIS CAN BE DONE AT ANY TIME BEFORE RESUBMISSION OF
 PLANS. IF THERE ARE ANY QUESTIONS, OR IF THE AUTHORIZED
 AGENT IS IN THE OFFICE, THIS CAN BE DONE AT THAT TIME.
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 ** PLEASE KNOW AS THERE ARE MANY CHANGES AND ITEMS NOT
 SUBMITTED; PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 WHICH HAVE NOT BEEN MADE AT THIS TIME.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-20 08:02:17 
  
 IN ELEC FOR REVIEW. 1-SET ONLY, AND 1-BOOK.