2007-10-20 18:58:56 | 2007-10-20 18:58:56 |
| |
| *** DENIED*** |
| |
| **THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION. |
| |
| CITY PARKING GARAGE. |
| 500 BANYAN BLVD. |
| |
| ** PLEASE SEE THERE ARE ITEMS WHICH WERE NOT SUBMITTED |
| FOR REVIEW OR WHICH WILL REQUIRE CHANGE ON PLANS WHICH |
| MAY GENERATE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| THESE COMMENTS ARE BASED ON PLANS AND DOCUMENTATION |
| PROVIDED. |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| 2002 NFPA-110 |
| 2003 NFPA-20 |
| |
| ** PLEASE SEE FOR EXAMPLE THE T-1 SHEET WHICH CONTAINS |
| CODE WHICH IS NOT ACCURATE OR NO LONGER ADOPTED BY THE |
| STATE. |
| PLEASE SEE THE 2002 NEC NOTED, PLEASE SEE A 2004 |
| NFPA-101 WAS NOTED AND 2003 REVISIONS TO THE FBC. |
| PLEASE SEE SOME OF THE CODE ON LS SHEET HAS BEEN |
| UPDATED HOWEVER LS SHEET STILL INDICATES SOME CODE NO |
| LONGER IN ADOPTION. |
| ** MANY OF THESE ARE OK ON ELECTRICAL PLANS. |
| |
| 2) NOTE: PLEASE SEE SHEET T-1 WHICH CONTAINS |
| *WHITE-OUT* ON SHEETS COVERING FIRE ALARM ON LEGEND. |
| PLEASE SEE THE FIRE ALARM PLANS ARE NEEDED AND REQUIRED |
| WITH THE BASE BUILDING PLANS FOR REVIEW. |
| PLEASE KNOW EVEN THOUGH THE FA IS UNDER SEPARATE PERMIT |
| PLEASE SUBMIT THESE AT THIS TIME TO SHOW BASE DESIGN |
| INTENT AND PROTECTION. |
| PLEASE SEE FBC 11-4.28.1, .2, AND .3(4) AS THE MINIMUM |
| DEVICE LOCATIONS AND LEVELS FOR ADA COMPLIANCE. |
| |
| 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEET |
| FOR THE GENERATOR, FIRE PUMP, FIRE PUMP CONTROLLER, ATS |
| AND SUB-BASE FUEL TANK. |
| PLEASE SEE OTHER COMMENTS BELOW WHICH WILL AFFECT THE |
| DOCUMENTS AND INFORMATION AS SHOWN ON PLANS. 110.3, |
| 90.7OF NEC,NFPA-20 ETC |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 4) NOTE:PLEASE SEE FBC ADMIN SECTION 109.3.6, |
| 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD |
| PROJECTS ON ALL ARCH AND ENG SHEETS. |
| THIS WAS DONE ON THE ARCHITECTS SHEETS HOWEVER NOT |
| ALL. |
| " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| 633 OF THE FLORIDA STATUTES". |
| THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| PLANS. |
| |
| 5) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| EGRESS PATHS WHICH MEET THE MINIMUM LIGHTING LEVELS AS |
| REQUIRED PER NFPA-101 7.8 AND 7.9. |
| PLEASE SEE 7.8.1.3, 7.9.2.2 |
| MOST OF THESE WERE SUBMITTED HOWEVER PLEASE SEE THE |
| MINIMUM AVERAGE ON SHEETS FOR NORMAL DO NOT MEET THE |
| MINIMUM LEVELS. |
| PLEASE ALSO SEE FOR EXAMPLE THE SPIRAL STAIRS LOCATED |
| IN OFFICE LOCATIONS. |
| PLEASE SEE THE FOLLOWING LOCATIONS ARE REQUIRED TO |
| CONTAIN SOME SORT OF BATTERY BACK UP LIGHTING FIXTURE. |
| THE STAIR TOWERS WILL REQUIRE A BATTERY BACK UP FIXTURE |
| OF SOME TYPE TO MEET THE MINIMUM OF 1FT CANDLE LEVEL |
| UNDER EMERGENCY.7.8.2.1, 7.9.2.2 |
| PLEASE SEE THE OTHER LOCATIONS WILL BE THE GENERATOR |
| ROOM, FIRE PUMP ROOM, MAIN ELECTRICAL ROOM, EMERGENCY |
| MAIN ELECTRICAL ROOM, AND THE ELEVATOR EQUIPMENT ROOMS. |
| (SOME OF THESE MAY ALREADY SHOW A BATTERY BACK UP |
| FIXTURE, BUT MOST DO NOT). |
| 700.12F. |
| PLEASE SEE 700.16 FOR THESE SAME ROOMS. |
| |
| 6) NOTE: PLEASE SEE THE PLANS FOR LIGHTING AND POWER |
| INDICATES ELECTRICAL LIGHTING AND RECEPTACLE IN THE FPL |
| VAULT WHICH IS NOT PERMITTED PER FPL. THIS ROOM IS ALSO |
| FPL LEGAL EASEMENT AREA AND IS NOT CONSIDERED PART OF |
| THE GARAGE BUILDING. |
| |
| 7) NOTE: PLEASE SEE THE ADDRESS OF THIS STRUCTURE WAS |
| GIVEN AS 500 BANYAN BLVD. |
| PLEASE ADJUST ALL TITLE BLOCKS TO INCLUDE THE ADDRESS. |
| PLEASE BE SURE TO SEE THAT THERE ARE SEVERAL LOCATIONS |
| ON PLANS WHICH MENTIONS THE *CLEMATIS ST GARAGE* |
| INCLUDING TITLE BLOCKS. |
| IF THE ADDRESS IS ASSIGNED AS BANYAN BLVD, PLEASE |
| ADJUST. (ANY REQUEST FOR LOCATION DESIGNATION CHANGE |
| NEEDS TO GO THROUGH ADDRESSING REVIEWER). |
| FAC 61G15-23.002, 61G1-16.004 |
| FBC 110.1.2, 106.5, ETC ADMIN SECTION. |
| |
| 8) NOTE: PLEASE KNOW THE ROOF TOP LIGHTING POLES WILL |
| BE REQUIRED TO HAVE STRUCTURAL WIND LOAD CALCULATIONS |
| AND WILL BE REVIEWED BY THE BUILDING REVIEWER. |
| ** THIS IS NOTED FOR INFORMATION. |
| |
| 9) NOTE: PLEASE SEE THE EXHAUST FANS ON E1.1 ARE NOT |
| SHOWN ON ENLARGED PLANS FOR THE SAME ROOM. |
| FBC 106.1.2 FOR COORDINATION. |
| |
| 10) NOTE: PLEASE SEE 620.22-620.24 AS THE REQUIRED |
| DEDICATED CIRCUITS NEEDS TO BE FOR EACH ELEVATOR |
| EQUIPMENT ROOM. |
| PLEASE SEE THE PLANS CURRENTLY SHOW THE SAME CIRCUITS |
| FOR BOTH ROOMS WHICH IS NOT PERMITTED. |
| |
| 11) NOTE: PLEASE SEE 110.26C AS THE DOOR SWINGS ON |
| ELECTRICAL ROOM DOORS MAY NOT SWING IN. PLEASE BE SURE |
| TO ADJUST ON ELECTRICAL SHEETS AND BE SURE TO GIVE |
| INFORMATION TO OTHER DESIGNERS FOR COORDINATION OF ALL |
| SHEETS FOR ALL TRADES. |
| |
| 12) NOTE: PLEASE CONTACT THE STATE OF FLORIDA GOVERNING |
| ELEVATOR EQUIPMENT ROOMS. IT HAS COME TO THE ATTENTION |
| ON THIS OFFICE THAT SEVERAL LOCATIONS WHEN BEING |
| INSPECTED BY THE STATE FOR ELEVATOR CERTIFICATION ARE |
| BEING REQUIRED TO HAVE THE EQUIPMENT ROOM AIR |
| CONDITIONED. THIS IS NOT IN THE ELECTRICAL CODE. |
| |
| 13) NOTE: PLEASE SEE 620.23 AS THE EXPLANATORY NOTE IN |
| THE HANDBOOK FOR ELEVATOR PIT LIGHTING REQUIRES A 5FT |
| CANDLE LIGHTING LEVEL. |
| PLEASE SEE THE FOLLOWING WHICH WAS EXTRACTED FOR THIS |
| SECTION ON THE NEC. |
| *ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND |
| ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) |
| AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE |
| EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.* |
| |
| 14) NOTE: PLEASE CLARIFY THE LIGHTING CONTROL SYSTEM |
| BEING PROPOSED FOR THE ENTIRE PARKING GARAGE. PLEASE |
| VERIFY WITH THE CITY IF THE GARAGE AREA WHICH DO NOT |
| INCLUDE ROOMS AND OFFICES IS GOING TO BE A 24HR |
| OPERATION. |
| IF THIS IS 24 HR OPERATION AND USE, THEN NO LIGHTING |
| CONTROL SYSTEM WOULD BE SHOWN FOR MANY OF THESE |
| LIGHTING FIXTURES. |
| PLEASE SE THERE ARE AREAS IN WHICH THE LIGHTING |
| CONTROLS FOR DURING DAYLIGHT HOURS ARE IN QUESTION. IF |
| THE LIGHTING LEVELS INSIDE THE GARAGE DURING THE DAY |
| FALL BELOW MINIMUM SAFETY LEVELS FOR EGRESS, WHAT WILL |
| TURN THE LIGHTING ON? |
| PLEASE SEE THE CIRCUITING WILL NEED TO BE ADJUSTED |
| ALONG WITH ANY LIGHTING CONTROLS. |
| AS THERE ARE SEVERAL UNANSWERED QUESTIONS ON THIS NOTE, |
| THIS MAY NEED TO BE GONE OVER WITH CITY STAFF OTHER |
| THAN PLAN REVIEW. PLANS REVIEW WILL BE FOR MINIMUM |
| LIGHTING LEVELS AND CONTROLS OF THOSE LEVELS. PLEASE |
| SEE 13-415.1.ABC.1, 13-415.1.ABC.1.4 ETC |
| |
| 15) NOTE: PLEASE SEE THAT MORE INFORMATION WILL BE |
| NEEDED FOR LIGHTING IN OFFICES AND DUE TO THE |
| ADJUSTMENTS POSSIBLY WITH NOTE #14 ABOVE, THE OFFICES, |
| MEETINGS ROOMS ETC MAY NEED TO BE GONE OVER. PLEASE SEE |
| 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE MISSING |
| LIGHTING CONTROLS IN RETAIL AREAS. |
| |
| 16) NOTE: PLEASE SEE MISSING ENERGY CALCULATIONS, |
| LIGHTING PERFORMANCE CALCULATIONS PER 13-415.2 AND |
| 13-415.2.ABC.1.3 ETC. |
| PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER WHICH |
| WILL BE FORTH COMING. |
| PLEASE SEE SOME AREAS OF THIS BUILDING WILL HAVE |
| CONDITIONED SPACE. |
| |
| 17) NOTE: PLEASE PROVIDE COMPLETED INFORMATION FOR FIRE |
| PUMP AND LOCKED ROTOR OVER CURRENT PROTECTION AND |
| AMPERAGES. |
| PLEASE SEE NEC 695.4B1, 9.3.2.2.3.2(A), (B) ETC PLEASE |
| SEE THE ELECTRICAL PLANS INDICATE A DISCONNECT WITH |
| OVER CURRENT PROTECTION AHEAD OF THE FIRE PUMP |
| CONTROLLER WHICH WILL ALSO CONTAIN OVER CURRENT |
| PROTECTION. PLEASE KNOW THERE MAY NOT BE OVER CURRENT |
| PROTECTION ON THE LINE SIDE OF THE FIRE PUMP |
| CONTROLLER. THE TYPICAL LISTED FIRE PUMP CONTROLLER |
| CONTAINS THE LOCKED ROTOR CURRENT SETTING FOR THE |
| SELECTED PUMP AND ASSEMBLY. 10.4.4.1 NFPA-20 PLEASE |
| ALSO SEE THE FIRE PUMP IS BEING SHOWN AS 60 HP ON FP |
| SHEETS AND 75HP ON ELECTRICAL SHEETS. |
| PLEASE SEE PROVIDE INFORMATION ON WHAT TYPE OF BREAKERS |
| ARE ON THE SECONDARY EMERGENCY SIDE FOR FIRE PUMP |
| POWER. AS THE FIRE PUMP IS BEING FED THROUGH A TOTAL OF |
| THREE BREAKERS ON THE EMERGENCY SIDE, THESE MAY CREATE |
| AN ISSUE WITH SELECTIVE COORDINATION. |
| PLEASE SEE THESE BREAKERS ARE TYPICALLY MAGNETIC TYPE. |
| PLEASE SEE NEC 695 AND NFPA-20CHAPTER 9 AND 10. |
| |
| 18) NOTE: PLEASE PROVIDE THE MINIMUM FUEL TIMES FOR |
| EMERGENCY GENERATOR AND FUEL FOR FIRE PUMP. NFPA-20 |
| 9.6.2.2. (8HRS PLUS OTHER LOADS) |
| |
| 19) NOTE: PLEASE SEE THE RISER INDICATES THE NORMAL |
| FEED FROM FPL TO THE EMERGENCY SIDE OF THE FIRE PUMP |
| CONTROLLER/ATS. |
| PLEASE SEE THIS APPEARS TO BE A MISPRINT AND WILL NEED |
| TO BE REVISED. |
| FBC 106.1.2 FOR COORDINATION. |
| NEC 695.1 |
| |
| 20) NOTE: PLEASE SEE GROUNDING DETAIL FOR GENERATOR |
| DOES NOT ACCURATELY REFLECT THE SERVICE EQUIPMENT. FBC |
| 106.1.2 FOR COORDINATION, |
| 230.2, 230.70, 250.50 ETC |
| |
| 21) NOTE: PLEASE SEE AS THE RISER, PANELS AND EQUIPMENT |
| NEED COORDINATION THERE ARE SOME ITEMS WHICH CAN NOT BE |
| CONFIRMED AT THIS TIME. |
| PLEASE SEE FOR EXAMPLE: |
| A) THE RISER INDICATES THE MSB AS A 1200AMP WITH WHAT |
| APPEARS TO BE A 800AMP BREAKER, HOWEVER THE MSB PANEL |
| INDICATES THIS AS A 1200AMPS MAIN LUG ONLY DISTRIBUTION |
| BOARD. |
| |
| B) PLEASE SEE 240.13, AND 230.95 CAN NOT BE CONFIRMED |
| IF REQUIRED OR NOT. |
| |
| C) PLEASE SEE 250.30, 250.20 AND WHETHER OR NOT A |
| 4-POLE ATS IS REQUIRED CAN NOT BE CONFIRMED. |
| |
| D) PLEASE SEE 230.70, 230.71 ETC CAN ALSO NOT ME |
| CONFIRMED. IF THIS MSB DOES NOT CONTAIN A MAIN, IT DOES |
| NOT MEET EITHER OF THESE TWO SECTIONS OF CODE ALONG |
| WITH SEVERAL OTHERS INCLUDING 240.4 AND 310.16 |
| |
| THESE ARE SOME OF THE ITEMS WHICH NEED TO BE |
| COORDINATED AND ADJUSTED ON PLANS. |
| |
| 22) NOTE: PLEASE CLARIFY WHERE/HOW THE ADDITIONAL |
| SERVICE FOR RETAIL CAN BE GRANTED PER 230.2. |
| |
| 23) NOTE: PLEASE ADJUST AND PLACE ON THE LIGHTING |
| PROTECTION PLANS. PLEASE KNOW ANY SYSTEM SHALL BE MEET |
| NFPA-780. (UNDER SEPARATE PERMIT) |
| |
| 24) NOTE: PLEASE CLARIFY FIXTURE SC ON LEGEND AND ON |
| PLANS. |
| PLEASE SEE THE CIRCUITING TO 5TH FLOOR LIGHTING WHICH |
| IS CIRCUITED TO 1NGH-11 IS THE SAME AS THE CIRCUIT FOR |
| WHAT APPEARS TO BE FEEDING THESE SC FIXTURES ON ROOF ON |
| E6.1. |
| PLEASE SEE ON PLANS ONLY ONE LOCATION SHOWS THE FIXTURE |
| SC YET THE SYMBOL FOR THIS SAME FIXTURE APPEARS TO BE |
| FOR OTHER FIXTURES BUT THEY ARE NOT LABELED OR |
| IDENTIFIED. |
| PLEASE COMPLETE, ADJUST AND COORDINATE. |
| FBC 106.1.2. |
| 408.4, 310.16, 240.4 ETC |
| |
| 25) NOTE: PLEASE PROVIDE INFORMATION FOR FAIL SAFE |
| OPERATION OF GATES. |
| PLEASE SEE COMMENTS FROM FIRE MARSHAL WITH RESPECT TO |
| OPERATION OF THESE GATES UNDER THE LOSS OF POWER. |
| PLEASE SEE POSSIBLE CHAPTER 7 OF THE LS CODE. |
| THIS IS ONLY BEING NOTED AS ANY CHANGES AND COMMENTS |
| FROM OTHER TRADES SUCH AS BUILDING FOR CHAPTER 10 OF |
| THE FBC AND CHAPTER 7 OF NFPA-101 WILL AFFECT THE |
| ELECTRICAL PLANS. |
| |
| 26) NOTE: PLEASE SEE THE SHEET E4.1 WHICH CONTAINS THE |
| LOW VOLTAGE SYSTEMS/CONDUIT LOCATIONS IS LABELED AND |
| IDENTIFIED AS LIGHTING PLANS AND DETAILS. |
| FBC 106.1.2 FOR COORDINATION. |
| |
| 27) NOTE: PLEASE SEE THE FEEDERS ON EDP1 IS NOT |
| COMPLETE AT THIS TIME FOR MCC, AND ELEVATORS 1-4. |
| PLEASE COMPLETE INFORMATION FOR THE SIZE OF THE |
| ELEVATOR MOTORS SO THAT THE FEEDERS CAN BE SHOWN AND |
| DETERMINED FOR CODE COMPLIANCE. |
| PLEASE SEE THAT THE BASE OVER CURRENT PROTECTION AT THE |
| ELEVATOR DISCONNECTS/CONTROLLERS ARE NOT REQUIRED AT |
| THIS TIME UNLESS KNOWN. IF THIS INFORMATION IS KNOWN AT |
| THIS TIME, THEN THIS WILL ALLEVIATE PLANS FROM HAVING |
| TO BE REVISED AT A LATER DATE. AT SOME POINT IN TIME |
| THE PLANS WILL BE REQUIRED TO SHOW AND INDICATE ALL OF |
| THESE. |
| PLEASE SEE NEC 620.1,240.4, 310.16, 408.4 ETC |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 28) NOTE: PLEASE SEE THE MAIN MEANS OF DISCONNECT FOR |
| THE FEEDERS FROM THE GENERATOR APPEARS TO BE FED |
| THROUGH AND *BACK-FED* BREAKER IN MSBE. |
| PLEASE NOTE REJECTION CLIP IF THIS IS INDEED THE CASE. |
| PLEASE SEE FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 29) NOTE: PLEASE SEE 230.2E, 700.8 ETC AS ALL MAINS ARE |
| REQUIRED TO BE LABELED. |
| PLEASE SEE 230.2 AS THE POWER FOR THE EMERGENCY SERVICE |
| EQUIPMENT IS BEING TAPPED FROM THE NORMAL ELECTRICAL |
| SERVICE. IF THERE ARE ANY CHANGES PLEASE BE SURE TO |
| LABEL ALL MAINS ACCORDINGLY. |
| PLEASE SEE COMMENT ABOVE WITH RESPECT TO RETAIL SERVICE |
| PROPOSED. AT THIS TIME THIS ADDITIONAL SERVICE AS SHOWN |
| NOTED ON NOTE #22 ABOVE IS NOT GRANTED. EACH OF THOSE |
| TENANT/RETAIL DISCONNECTS WOULD HAVE BEEN MAINS. |
| |
| 30) NOTE: PLEASE SEE NOTE ABOVE WITH RESPECT TO |
| LIGHTING CONTROLS AND EXTERIOR LIGHTING CONTROLS PER |
| 13-415.1.ABC.1.4. |
| PLEASE CLARIFY HOW ALL LIGHTING ON FA?ADE IS BEING |
| CONTROLLED. |
| PLEASE SEE SOME OF THIS IS SHOWN BEING CONTROLLED FROM |
| A PHOTO-CELL AS WELL AS A LIGHTING CONTROL PANEL. SEE |
| CIRCUITING ON SCHEDULE. |
| PLEASE SEE FBC 106.1.2 FOR COORDINATION. |
| |
| 31) NOTE: PLEASE SEE NO INFORMATION FOR CONDUITS, |
| CONDUCTORS, TAPS ETC ON THE RETAIL SERVICE EQUIPMENT IS |
| SHOWN. |
| PLEASE COMPLETE. |
| PLEASE BE SURE TO SEE COMMENT #22 ETC FOR SERVICE. |
| |
| 32) NOTE: PLEASE SEE NO GROUNDING ELECTRODE SYSTEM IS |
| BEING SHOWN FOR THE SAME RETAIL SERVICE. |
| 250.50. |
| |
| 33) NOTE: PLEASE SEE SELECTIVE COORDINATION IS NEEDED |
| TO BE SHOWN FOR THE LIFE SAFETY ITEMS PER 240.12 |
| |
| 34) NOTE: PLEASE SEE TWO PERMIT APPLICATIONS WERE |
| SUBMITTED AT TWO DIFFERENT TIMES ON THE SAME DAY. THE |
| PERMIT APPLICATION WHICH DOES CONTAIN ALL OF THE |
| SIGNATURES FOR SUB CONTRACTORS NEEDS TO BE NOTARIZED ON |
| THE BACK WHERE THE CONTRACTORS AUTHORIZED AGENT IS |
| SIGNED ON. THIS CAN BE DONE WHEN PLANS ARE RESUBMITTED. |
| THE ORIGINAL APPLICATION WHICH WAS SUBMITTED WILL |
| BECOME VOID. |
| THIS CAN BE DONE AT ANY TIME BEFORE RESUBMISSION OF |
| PLANS. IF THERE ARE ANY QUESTIONS, OR IF THE AUTHORIZED |
| AGENT IS IN THE OFFICE, THIS CAN BE DONE AT THAT TIME. |
| PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| |
| ** PLEASE KNOW AS THERE ARE MANY CHANGES AND ITEMS NOT |
| SUBMITTED; PLEASE BE AWARE OF ANY POSSIBLE COMMENTS |
| WHICH HAVE NOT BEEN MADE AT THIS TIME. |
| PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY HAVE AN |
| AFFECT ON ELECTRICAL PLANS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |