2007-10-21 14:17:51500 BANYAN BLVD
 CITY PARKING GARAGE
 OCT. 22/ 2007
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090764
 ADD: 500 BANYAN BLVD
 CONT: CATALFUMO
 TEL: (561)307-4746
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIEDWPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS, PLEASE SEE SHEET
 T-1& LS0.0 APPLICABLE CODES.
  
 1E) PLEASE SEE SHEET T-1 UNDER APPLICABLE CODES (2)(E)
 UPDATE THE STANDARD ASCE 7-98,SEE SECTION 1609.1.1 &
 CHAPTER 35 REFRENECE STANDARDS.
  
 2) NOTE, IMPACT FEE STAMP AND RADON FEES WERE PAID
 UNDER FOUNDATION PERMIT # 07070220.
  
 3)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S. 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED. ALTHOUGH
 THERE IS A ON GOING FOUNDATION PERMIT, A SECOND
 AGREEMENT WILL BE REQUIRED SINCE THESE ARE STAND ALONE
 PERMITS.
  
 4) NOTEICE TO CONTRACTOR:109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6) PLEASE REVIEW ALL SHEETS ARCHITTECTAL AND
 ENGINEERING SHEETS FOR THE REQUIRED ADDRESSIN THE
 TITLEBLOCK. FLORIDA ADMINISTRATIVE CODE 61G15-23.002 &
 61G1-16.004 , FBC 2004,
 110.1.2 & 106.5. NOTE SHEET S1 HAS 401 CLEMATIS ST ON
 SHEET.
  
 7) LS.1 VERSES A6.1 DETAIL# 01 THE RETAIL STORES 1.101
 & 1.102 BOTH INDICATE A 2 HR RATED WALL BETWEEN THE
 PARKING GARAGE AND RETAIL AREAS, A6.1 DOES NOT HAVE ANY
 WALL TAGS IDENTIFYING TYPES OF WALLS NOR RATING. FBC
 106.1.2 ADDITIONAL INFORMATION REQUIRED, TABLE 302.3.2
 & 706.3.6 & 708.1.
  
 8)LS.1 VERSES A6.1 DETAIL# 01 THE RETAIL STORES BOTH
 DO NOT INDICATE WALL RATINGS NOR WALL TAGS FOR THE
 TENANT SEPERATION WALLS BETWEEN THE TWO UNITS.FIRE
 PARTITIONS 708.1(5).
  
 9)PLANS FAIL TO PROVIDE THE OCCUPANCY SEPERATION
 BETWEEN THE RETAIL AREAS AND THE S2 STORAGE OCCUPANCY
 ON THE 2ND FLOOR, 711.3 FIRE RESISTANCERATINGS, SHEET
 A5-0.2 INDICATES THE USE OF
 HOLLOW CORE SLAB FOR A RATED ASSEMBLY PLEASE SEE
 721.2.2.1.1 FOR THE EQUIVALANT THICKNESS VALUE FOR TYPE
 OF SLABALSO SEE TABLE 721.2.2.1.
  
 10) SHEET A5-D.1 INDICATES THE USE OF T-JOIST FLOOR
 SYSTEM PLEASE PROVIDE THE HOURLY FIRE RATING FOR SUCH
 FLOOR SYSTEM , 721.2.2.1.2 / TABLE 721.2.2.1.
  
 11)LS.1 VERSES A6.1 DETAIL# 01 THE GENERATOR ROOM,
 LS.1 INDICATES A 2HR RATED WALL BETWEEN THE S2 STORAGE
 AND THE GENERATOR, SHEET A6.1 IT APPEARS THERE IS A
 LOUVER IN THIS WALL.
 SEE 702 FIRE DAMPERS, &716.3.1 FIRE PROTECTION
 RATING. FIRE DAMPERS SHALL HAVE THE MINIMUM FIRE
 PROTECTION RATING SPECIFIED IN TABLE 716.3.1 FOR THE
 TYPE OF PENETRATION.
  
 12) LS.1 VERSES A6.1 DETAIL# 01 THE EMERGENCY POWER
 SUPPLY ROOM # 1.106. LS.1 INDICATES A TWO HOUR RATED
 WALL WHERE AS THE DOOR SCHEDULE ON A-8.1 DOES NOT SHOW
 ANY FIRE RATING AT ALL.
 PLEASE SEE SECTION 715.3 AND TABLE 715.3.
  
 13) A6.1 DETAIL# 01 DOES NOT INDICATE WALL TAGS FOR THE
 2 HR RATED WALL SEPERATING THE S2 OCCUPANCY FROM THE
 SEPERATED USE ROOMS GENERATOR, ELECTRIC ROOM , ETC,
 PLEASE PROVIDE ADDITIONAL INFORMATION 106.1.2 & TABLE
 715.3 REQUIRED WALL RATINGS, MAIN ELECTRIC ROOM NFPA
 13:8.14.0, GENERATOR ROOM NFPA 110.7.2.2 & MAIN
 ELECTRIC ROOM NFPA 13.8.14.10.
  
 14)A6.1 DETAIL# 01 STORAGE ROOM 1.108 PLEASE PLACE
 WALL IDENTIFICATION TAGS ON COMMON WALLS TO THE S2
 ENCLOSED PARKING GARAGE WALLS. PLANS APPEAR TO HAVE
 OPENINGS IN THE EAST END OF THE STORAGE ROOM WALL, ARE
 THEY ENCLOSED OR RATED? WHAT TYPE OF STORAGE IS THIS S1
 OR S2? 106.1.2 ADDITIONAL INFORMATION REQUIRED.SECTION
 302.1.
  
 15) A6.1 DETAIL# 02 STORAGE ROOM 1.109 PLEASE INDICATE
 AS TO WHAT TYPE OF ITEMS ARE TO PLACED IN STORAGE
 CREATING EITHER A S1 OR S2 OCCUPANCY? SECTION302.1 .
  
 16) A6.1 DETAIL# 03 THE ELEVATOR MACHINE ROOM #
 2.003.1AND ROOM 2.005L DOESN'T INDICATE ANY WALL
 IDENTIFICATION TAGS NOR DOES THE DOOR SCHEDULE INDICATE
 A FIRE RATING ON DOOR# 2-003.1A SHEET A8.1.
 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR
 MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED
 WITH CONSTRUCTION HAVING A FIRE-RESISTANCE RATING NOT
 LESS THAN THE REQUIRED RATING OF THE HOISTWAY ENCLOSURE
 SERVED BY THE MACHINERY.
  
 17) PLEASE PROVIDE COMPLIANCE WITH, 3002.4 ELEVATOR CAR
 TO ACCOMMODATE AMBULANCE STRETCHER . IN BUILDINGS FOUR
 STORIES IN HEIGHT OR MORE, AT LEAST ONE ELEVATOR SHALL
 BE PROVIDED FOR FIRE DEPARTMENT EMERGENCY ACCESS TO ALL
 FLOORS. SUCH ELEVATOR CAR SHALL BE OF SUCH A SIZE AND
 ARRANGEMENT TO ACCOMMODATE A 24-INCH BY 76-INCH (610 MM
 BY 1930 MM) AMBULANCE STRETCHER IN THE HORIZONTAL, OPEN
 POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL
 SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE).
 THE SYMBOL SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH
 AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE
 HOISTWAY DOOR FRAME.
  
 18)3003.6.1 VENTS. HOISTWAYS OF ELEVATORS SERVING
 MORE THAN 3 FLOORS SHALL BEPROVIDED WITH MEANS OF
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 19)3003.6.2 VENTS SHALL BE LOCATED BELOW THE FLOOR OR
 FLOORS AT THE TOP OF THE HOISTWAY, AND SHALL BE EITHER
 DIRECTLY TO THE OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR.
  
 20) A6.1 DETAILS 02 AND 03 BOTH INDICATE THE VERTICAL
 EXIT ENCLOSURES AND ELEVATOR HOIST WAYS AGAIN THERE ARE
 NO WALL TYPE IDENTIFICATION TAGS INDICATING THESE WALLS
 ARE 2 HR RATED WALLS AND OF WHAT TYPE OF CONSTRUCTION.
 THE LIFE SAFETY PLAN DOES IDENTIFY THEM AS TWO HR RATED
 BUT WHAT TYPE OF CONSTRUCTION. 707.4.
  
 21) PLEASE PROVIDE INFORMATION ON THE SPIRAL STAIRWAY,
 RISERS, TREAD DEPTH, HEAD ROOM ETC, 1009.9.1.
  
 22) DELETED.10-26-07
 23) SHEET A2.1 DETAIL# 02 PLEASE PROVIDE WHAT TYPE OF
 MATERIAL THE ARCHITECTURAL TRIM IS DEPICTED IN THIS
 PICTURE? AND HOW WILLIT BE ATTACHED TO THE STRUCTURE.
 1406.2.2.
  
 24)PLEASE PROVIDE INFORMATION FOR CODE COMPLIANCE ON
 VAN ACCESSIBILITY AND IN COMPLIANCE WITH 11-4.6.3 VAN
 ACCESSIBLITY REQUIREMENTS
  
 25) SHEET A3.2 PROVIDE THE WIND LOAD INFORMATION
 (CALCULATIONS) FOR THE ROOFTOP LIGHT POLES. ASCE 7-02.
  
 26) A4.3 INDICATES VARIOUS PRECAST PILASTER DETAILS BUT
 THERE IS NO DETAILS FOR INSTALLATION PLEASE PROVIDE
 METHOD OF ATTACHMENT, 1405.6/ 1405.7/ 1405.9 .
  
 27)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 ALL OF THE PRODUCT APPROVALS ARE STAMPED WITH
 THORTON-TOMASETTIS' SHOP DRAWING STAMP THAT THEY WERE
 REVIEWED. THE ISSUE THAT IS NOT COMMONLY KNOWN THAT THE
 OLDER MIAMI-DADE
 NOA'S THAT WERE TESTED BEFORE THE 2004 FBC MAY OR MAY
 NOT MEET THE CURRENT 2004 FBC. 1605.3.1.1 LOAD
 REDUCTIONS. BEFORE THE 2004 FBC THE MANUFACTURERS WERE
 ALLOWED TO TAKE
 1.33 STEEL INCREASES AND DID SO WITH THERE FASTENERS.
 THE NEWER MIAMI-DADE REPORTS AND THE OLDER REPORTS THAT
 ARE BEING UPDATED ARE BEING REVIEWED FOR THE ANCHOR
 CONNECTIONS. THE
 STATEMENTIS SHOWN UNDER C CALCULATION, REVISED
 ANCHOR CALCULATIONS THAT HAVE BEEN REVIEWED UNDER THE
 2004 FBC WILL STATE THE ANCHOR CALCULATIONS HAVE BEEN
 REVIEWED TO THE 2004 FBC.
 PLEASE REVIEW THE INGERSOLL- RAND AND THE TRAINER GLASS
 FOR THE ANCHOR CONNECTIONS MEETING 1605.3.1.1/ 2004
 FBC. THIS MAY AFFECT THE PRESSURES LISTED IN THE
 REPORT.
  
 28) SHEET S0.30 PROVIDES THE ELEVATIONS WITH THE
 ILLUSTRATED INTERIOR ZONES AS WELL AS THE END ZONES,
 THE PLANS DO FAIL TO PROVIDE THE ZONE LOCATION AND
 ASSOCIATEDPRESSURES FOR THE DOORS LOCATED ON THE ROOF
 TOP STAIR TOWERS. PLEASE PROVIDE THIS ADDITIONAL
 INFORMATION TO REVIEW FOR WIND PRESSURES. 1609. 6.1.2.
  
 29A)THE EVALUATION REPORT FROM INGERSOLL-RAND REPORT#
 S07-001 IS A COPY AND NEEDS TO BE AN ORIGINAL (3) FOR
 THRESHOLD BUILDING) SIGNED AND SEALED REPORTS. 29B)
 THIS REPORT INDICATESUNDER PRODUCT COMPARISON TO BE A
 INSWING DOOR WHERE AS UNDER EVALUATION FOR A POSITIVE
 WIND APPLICATION THE WIND LOAD APPLIED TO THE DOOR
 PANEL WOULD BE DISTRIBUTED AROUND THE FRAME EQUALLY,
 THIS WOULD REQUIRE THE DOOR & FRAME TO BE INSTALLED IN
 A OUTSWING INSTALLATION. PLEASE CORRECT STATEMENTS.
 29C) PLEASE PROVIDE CALCULATIONS INDICATING THE
 EXTRAPOLATION OF PRESSURES OR INTERPALATION OF
 PRESSURES, DEPENDING ON REPORT.
 29D) IT APPEARS THAT A LOCAL PRODUCT APPROVAL WILL BE
 REQUIRED, PLEASE FILL OUT FORM FOR A LOCAL PRODUCT
 APPROVAL FOR WEST PALM BEACH, SEE FORM ATTACHED.
  
 30) THE PRODUCT APPROVAL FOR TRAINER GLASS WILL REQUIRE
 FLORIDA APPROVAL COVERSHEETS, PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72.
  
 31) LOUVERS,THE PRODUCT APPROVAL THST WAS SUBMITTED
 FORAMERICAN WARMING AND VENTILATING UNDER FL# 5121 IS
 NOT THE REPORT THAT WASSPSECED ON SHEET A8.2 / W-12,
 NOTE THERE IS A
 W-13 AND NO REPORT NUMBER SPECIFIED?
  
 32) ROOFING, NO ROOFING REPORT WAS SUBMITTED EVEN
 THOUGH THERE IS A ROOFER SIGNER ON THE PERMIT
 APPLICATION.
 THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH THE
 FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE PRODUCT APPROVAL
 REPORT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 2&3___ .
 __XX_ THE SYSTEM PROVIDED STATESLIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISEDFASTENER SPACING,
 PREPARED , SIGNEDAND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 __XX_ BE AWARE OF : THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCEDFASTENING ALLOWED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  