2007-10-21 14:17:51 | 500 BANYAN BLVD |
| CITY PARKING GARAGE |
| OCT. 22/ 2007 |
| |
| |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07090764 |
| ADD: 500 BANYAN BLVD |
| CONT: CATALFUMO |
| TEL: (561)307-4746 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIEDWPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. |
| IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE2007 REVISIONS, PLEASE SEE SHEET |
| T-1& LS0.0 APPLICABLE CODES. |
| |
| 1E) PLEASE SEE SHEET T-1 UNDER APPLICABLE CODES (2)(E) |
| UPDATE THE STANDARD ASCE 7-98,SEE SECTION 1609.1.1 & |
| CHAPTER 35 REFRENECE STANDARDS. |
| |
| 2) NOTE, IMPACT FEE STAMP AND RADON FEES WERE PAID |
| UNDER FOUNDATION PERMIT # 07070220. |
| |
| 3)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION |
| SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY FL S S. 553.79(5) |
| FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER |
| INFORMATION BEFORE THE PERMIT MAY BE ISSUED. ALTHOUGH |
| THERE IS A ON GOING FOUNDATION PERMIT, A SECOND |
| AGREEMENT WILL BE REQUIRED SINCE THESE ARE STAND ALONE |
| PERMITS. |
| |
| 4) NOTEICE TO CONTRACTOR:109.3.10* IMPACT OF |
| CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE |
| PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO |
| THE APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT |
| LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR |
| DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF |
| CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL |
| NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE |
| FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE |
| SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING |
| STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS,EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION |
| TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| SECTION 113 OF THIS CHAPTER. |
| |
| 6) PLEASE REVIEW ALL SHEETS ARCHITTECTAL AND |
| ENGINEERING SHEETS FOR THE REQUIRED ADDRESSIN THE |
| TITLEBLOCK. FLORIDA ADMINISTRATIVE CODE 61G15-23.002 & |
| 61G1-16.004 , FBC 2004, |
| 110.1.2 & 106.5. NOTE SHEET S1 HAS 401 CLEMATIS ST ON |
| SHEET. |
| |
| 7) LS.1 VERSES A6.1 DETAIL# 01 THE RETAIL STORES 1.101 |
| & 1.102 BOTH INDICATE A 2 HR RATED WALL BETWEEN THE |
| PARKING GARAGE AND RETAIL AREAS, A6.1 DOES NOT HAVE ANY |
| WALL TAGS IDENTIFYING TYPES OF WALLS NOR RATING. FBC |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED, TABLE 302.3.2 |
| & 706.3.6 & 708.1. |
| |
| 8)LS.1 VERSES A6.1 DETAIL# 01 THE RETAIL STORES BOTH |
| DO NOT INDICATE WALL RATINGS NOR WALL TAGS FOR THE |
| TENANT SEPERATION WALLS BETWEEN THE TWO UNITS.FIRE |
| PARTITIONS 708.1(5). |
| |
| 9)PLANS FAIL TO PROVIDE THE OCCUPANCY SEPERATION |
| BETWEEN THE RETAIL AREAS AND THE S2 STORAGE OCCUPANCY |
| ON THE 2ND FLOOR, 711.3 FIRE RESISTANCERATINGS, SHEET |
| A5-0.2 INDICATES THE USE OF |
| HOLLOW CORE SLAB FOR A RATED ASSEMBLY PLEASE SEE |
| 721.2.2.1.1 FOR THE EQUIVALANT THICKNESS VALUE FOR TYPE |
| OF SLABALSO SEE TABLE 721.2.2.1. |
| |
| 10) SHEET A5-D.1 INDICATES THE USE OF T-JOIST FLOOR |
| SYSTEM PLEASE PROVIDE THE HOURLY FIRE RATING FOR SUCH |
| FLOOR SYSTEM , 721.2.2.1.2 / TABLE 721.2.2.1. |
| |
| 11)LS.1 VERSES A6.1 DETAIL# 01 THE GENERATOR ROOM, |
| LS.1 INDICATES A 2HR RATED WALL BETWEEN THE S2 STORAGE |
| AND THE GENERATOR, SHEET A6.1 IT APPEARS THERE IS A |
| LOUVER IN THIS WALL. |
| SEE 702 FIRE DAMPERS, &716.3.1 FIRE PROTECTION |
| RATING. FIRE DAMPERS SHALL HAVE THE MINIMUM FIRE |
| PROTECTION RATING SPECIFIED IN TABLE 716.3.1 FOR THE |
| TYPE OF PENETRATION. |
| |
| 12) LS.1 VERSES A6.1 DETAIL# 01 THE EMERGENCY POWER |
| SUPPLY ROOM # 1.106. LS.1 INDICATES A TWO HOUR RATED |
| WALL WHERE AS THE DOOR SCHEDULE ON A-8.1 DOES NOT SHOW |
| ANY FIRE RATING AT ALL. |
| PLEASE SEE SECTION 715.3 AND TABLE 715.3. |
| |
| 13) A6.1 DETAIL# 01 DOES NOT INDICATE WALL TAGS FOR THE |
| 2 HR RATED WALL SEPERATING THE S2 OCCUPANCY FROM THE |
| SEPERATED USE ROOMS GENERATOR, ELECTRIC ROOM , ETC, |
| PLEASE PROVIDE ADDITIONAL INFORMATION 106.1.2 & TABLE |
| 715.3 REQUIRED WALL RATINGS, MAIN ELECTRIC ROOM NFPA |
| 13:8.14.0, GENERATOR ROOM NFPA 110.7.2.2 & MAIN |
| ELECTRIC ROOM NFPA 13.8.14.10. |
| |
| 14)A6.1 DETAIL# 01 STORAGE ROOM 1.108 PLEASE PLACE |
| WALL IDENTIFICATION TAGS ON COMMON WALLS TO THE S2 |
| ENCLOSED PARKING GARAGE WALLS. PLANS APPEAR TO HAVE |
| OPENINGS IN THE EAST END OF THE STORAGE ROOM WALL, ARE |
| THEY ENCLOSED OR RATED? WHAT TYPE OF STORAGE IS THIS S1 |
| OR S2? 106.1.2 ADDITIONAL INFORMATION REQUIRED.SECTION |
| 302.1. |
| |
| 15) A6.1 DETAIL# 02 STORAGE ROOM 1.109 PLEASE INDICATE |
| AS TO WHAT TYPE OF ITEMS ARE TO PLACED IN STORAGE |
| CREATING EITHER A S1 OR S2 OCCUPANCY? SECTION302.1 . |
| |
| 16) A6.1 DETAIL# 03 THE ELEVATOR MACHINE ROOM # |
| 2.003.1AND ROOM 2.005L DOESN'T INDICATE ANY WALL |
| IDENTIFICATION TAGS NOR DOES THE DOOR SCHEDULE INDICATE |
| A FIRE RATING ON DOOR# 2-003.1A SHEET A8.1. |
| 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR |
| MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED |
| WITH CONSTRUCTION HAVING A FIRE-RESISTANCE RATING NOT |
| LESS THAN THE REQUIRED RATING OF THE HOISTWAY ENCLOSURE |
| SERVED BY THE MACHINERY. |
| |
| 17) PLEASE PROVIDE COMPLIANCE WITH, 3002.4 ELEVATOR CAR |
| TO ACCOMMODATE AMBULANCE STRETCHER . IN BUILDINGS FOUR |
| STORIES IN HEIGHT OR MORE, AT LEAST ONE ELEVATOR SHALL |
| BE PROVIDED FOR FIRE DEPARTMENT EMERGENCY ACCESS TO ALL |
| FLOORS. SUCH ELEVATOR CAR SHALL BE OF SUCH A SIZE AND |
| ARRANGEMENT TO ACCOMMODATE A 24-INCH BY 76-INCH (610 MM |
| BY 1930 MM) AMBULANCE STRETCHER IN THE HORIZONTAL, OPEN |
| POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL |
| SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). |
| THE SYMBOL SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH |
| AND SHALL BE PLACED INSIDE ON BOTH SIDES OF THE |
| HOISTWAY DOOR FRAME. |
| |
| 18)3003.6.1 VENTS. HOISTWAYS OF ELEVATORS SERVING |
| MORE THAN 3 FLOORS SHALL BEPROVIDED WITH MEANS OF |
| VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF |
| FIRE. |
| |
| 19)3003.6.2 VENTS SHALL BE LOCATED BELOW THE FLOOR OR |
| FLOORS AT THE TOP OF THE HOISTWAY, AND SHALL BE EITHER |
| DIRECTLY TO THE OUTER AIR OR THROUGH NONCOMBUSTIBLE |
| DUCTS TO THE OUTER AIR. |
| |
| 20) A6.1 DETAILS 02 AND 03 BOTH INDICATE THE VERTICAL |
| EXIT ENCLOSURES AND ELEVATOR HOIST WAYS AGAIN THERE ARE |
| NO WALL TYPE IDENTIFICATION TAGS INDICATING THESE WALLS |
| ARE 2 HR RATED WALLS AND OF WHAT TYPE OF CONSTRUCTION. |
| THE LIFE SAFETY PLAN DOES IDENTIFY THEM AS TWO HR RATED |
| BUT WHAT TYPE OF CONSTRUCTION. 707.4. |
| |
| 21) PLEASE PROVIDE INFORMATION ON THE SPIRAL STAIRWAY, |
| RISERS, TREAD DEPTH, HEAD ROOM ETC, 1009.9.1. |
| |
| 22) DELETED.10-26-07 |
| 23) SHEET A2.1 DETAIL# 02 PLEASE PROVIDE WHAT TYPE OF |
| MATERIAL THE ARCHITECTURAL TRIM IS DEPICTED IN THIS |
| PICTURE? AND HOW WILLIT BE ATTACHED TO THE STRUCTURE. |
| 1406.2.2. |
| |
| 24)PLEASE PROVIDE INFORMATION FOR CODE COMPLIANCE ON |
| VAN ACCESSIBILITY AND IN COMPLIANCE WITH 11-4.6.3 VAN |
| ACCESSIBLITY REQUIREMENTS |
| |
| 25) SHEET A3.2 PROVIDE THE WIND LOAD INFORMATION |
| (CALCULATIONS) FOR THE ROOFTOP LIGHT POLES. ASCE 7-02. |
| |
| 26) A4.3 INDICATES VARIOUS PRECAST PILASTER DETAILS BUT |
| THERE IS NO DETAILS FOR INSTALLATION PLEASE PROVIDE |
| METHOD OF ATTACHMENT, 1405.6/ 1405.7/ 1405.9 . |
| |
| 27)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| ALL OF THE PRODUCT APPROVALS ARE STAMPED WITH |
| THORTON-TOMASETTIS' SHOP DRAWING STAMP THAT THEY WERE |
| REVIEWED. THE ISSUE THAT IS NOT COMMONLY KNOWN THAT THE |
| OLDER MIAMI-DADE |
| NOA'S THAT WERE TESTED BEFORE THE 2004 FBC MAY OR MAY |
| NOT MEET THE CURRENT 2004 FBC. 1605.3.1.1 LOAD |
| REDUCTIONS. BEFORE THE 2004 FBC THE MANUFACTURERS WERE |
| ALLOWED TO TAKE |
| 1.33 STEEL INCREASES AND DID SO WITH THERE FASTENERS. |
| THE NEWER MIAMI-DADE REPORTS AND THE OLDER REPORTS THAT |
| ARE BEING UPDATED ARE BEING REVIEWED FOR THE ANCHOR |
| CONNECTIONS. THE |
| STATEMENTIS SHOWN UNDER C CALCULATION, REVISED |
| ANCHOR CALCULATIONS THAT HAVE BEEN REVIEWED UNDER THE |
| 2004 FBC WILL STATE THE ANCHOR CALCULATIONS HAVE BEEN |
| REVIEWED TO THE 2004 FBC. |
| PLEASE REVIEW THE INGERSOLL- RAND AND THE TRAINER GLASS |
| FOR THE ANCHOR CONNECTIONS MEETING 1605.3.1.1/ 2004 |
| FBC. THIS MAY AFFECT THE PRESSURES LISTED IN THE |
| REPORT. |
| |
| 28) SHEET S0.30 PROVIDES THE ELEVATIONS WITH THE |
| ILLUSTRATED INTERIOR ZONES AS WELL AS THE END ZONES, |
| THE PLANS DO FAIL TO PROVIDE THE ZONE LOCATION AND |
| ASSOCIATEDPRESSURES FOR THE DOORS LOCATED ON THE ROOF |
| TOP STAIR TOWERS. PLEASE PROVIDE THIS ADDITIONAL |
| INFORMATION TO REVIEW FOR WIND PRESSURES. 1609. 6.1.2. |
| |
| 29A)THE EVALUATION REPORT FROM INGERSOLL-RAND REPORT# |
| S07-001 IS A COPY AND NEEDS TO BE AN ORIGINAL (3) FOR |
| THRESHOLD BUILDING) SIGNED AND SEALED REPORTS. 29B) |
| THIS REPORT INDICATESUNDER PRODUCT COMPARISON TO BE A |
| INSWING DOOR WHERE AS UNDER EVALUATION FOR A POSITIVE |
| WIND APPLICATION THE WIND LOAD APPLIED TO THE DOOR |
| PANEL WOULD BE DISTRIBUTED AROUND THE FRAME EQUALLY, |
| THIS WOULD REQUIRE THE DOOR & FRAME TO BE INSTALLED IN |
| A OUTSWING INSTALLATION. PLEASE CORRECT STATEMENTS. |
| 29C) PLEASE PROVIDE CALCULATIONS INDICATING THE |
| EXTRAPOLATION OF PRESSURES OR INTERPALATION OF |
| PRESSURES, DEPENDING ON REPORT. |
| 29D) IT APPEARS THAT A LOCAL PRODUCT APPROVAL WILL BE |
| REQUIRED, PLEASE FILL OUT FORM FOR A LOCAL PRODUCT |
| APPROVAL FOR WEST PALM BEACH, SEE FORM ATTACHED. |
| |
| 30) THE PRODUCT APPROVAL FOR TRAINER GLASS WILL REQUIRE |
| FLORIDA APPROVAL COVERSHEETS, PRODUCT APPROVALS |
| SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT |
| APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE |
| WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A |
| COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE |
| APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT |
| APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. |
| |
| 31) LOUVERS,THE PRODUCT APPROVAL THST WAS SUBMITTED |
| FORAMERICAN WARMING AND VENTILATING UNDER FL# 5121 IS |
| NOT THE REPORT THAT WASSPSECED ON SHEET A8.2 / W-12, |
| NOTE THERE IS A |
| W-13 AND NO REPORT NUMBER SPECIFIED? |
| |
| 32) ROOFING, NO ROOFING REPORT WAS SUBMITTED EVEN |
| THOUGH THERE IS A ROOFER SIGNER ON THE PERMIT |
| APPLICATION. |
| THIS ROOF IS MISSING OR NOT INCOMPLIANCE WITH THE |
| FOLLOW ITEMS: |
| __XX_ CONTRACTOR DID NOT PROVIDE PRODUCT APPROVAL |
| REPORT. |
| __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO |
| BE USED. |
| __XX_ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE |
| 2&3___ . |
| __XX_ THE SYSTEM PROVIDED STATESLIMITATION# 7, |
| SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THE |
| BUILDING OFFICIAL, A REVISEDFASTENER SPACING, |
| PREPARED , SIGNEDAND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE |
| SUBMITTED. |
| __XX_ BE AWARE OF : THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCEDFASTENING ALLOWED. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |