Plan Review Notes
Plan Review Notes For Permit 07090742
Permit Number 07090742
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-19 07:47:51 
  
 APPLICATION #07090742
 ELECTRICAL PLAN REVIEW
 6793 SPARROW HAWK DRIVE
 11/19/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE
 NOTED.
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW.
  
 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE
 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE
 CURRENT EDITION ADOPTED BY THE STATE. *HAND DRAWN
 CHANGES TO THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE
 DETERMINED THAT THE CHANGES WERE MADE WITH THE
 KNOWLEDGE OR CONSENT OF THE DESIGNER OF RECORD. 106.1.3
 FBC AS AMENDED.
  
 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B"
 IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80
 WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE
 INCREASED TO 1 1/4" TO MEET MINIMUM SIZE FOR FILL
 REQUIREMENTS OF ARTICLE 352.22. *HAND DRAWN CHANGES TO
 THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE DETERMINED
 THAT THE CHANGES WERE MADE WITH THE KNOWLEDGE OR
 CONSENT OF THE DESIGNER OF RECORD. 106.1.3 FBC AS
 AMENDED.
  
 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS.
 SEE 61G1-16.001 FAC. *THE INFORMATION ON THE SEAL STILL
 CANNOT BE READ.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718