| APPLICATION #07090742 |
| ELECTRICAL PLAN REVIEW |
| 6793 SPARROW HAWK DRIVE |
| 11/19/07 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| NOTED. |
| |
| ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE |
| NOTED. |
| |
| THESE COMMENTS ARE FROM THE PREVIOUS REVIEW. |
| |
| 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE |
| 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE |
| CURRENT EDITION ADOPTED BY THE STATE. *HAND DRAWN |
| CHANGES TO THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE |
| DETERMINED THAT THE CHANGES WERE MADE WITH THE |
| KNOWLEDGE OR CONSENT OF THE DESIGNER OF RECORD. 106.1.3 |
| FBC AS AMENDED. |
| |
| 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B" |
| IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80 |
| WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE |
| INCREASED TO 1 1/4" TO MEET MINIMUM SIZE FOR FILL |
| REQUIREMENTS OF ARTICLE 352.22. *HAND DRAWN CHANGES TO |
| THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE DETERMINED |
| THAT THE CHANGES WERE MADE WITH THE KNOWLEDGE OR |
| CONSENT OF THE DESIGNER OF RECORD. 106.1.3 FBC AS |
| AMENDED. |
| |
| 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS. |
| SEE 61G1-16.001 FAC. *THE INFORMATION ON THE SEAL STILL |
| CANNOT BE READ. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |