Plan Review Notes For Permit 07090742 |
Permit Number |
07090742 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-28 10:24:04 | DENIED; | | RISER DIAGRAM DOES NOT MATCH FLAT DRAWING. | | A) BATH #2 SHOWER IS PART OF THE BATHROOM GROUP | | ON RISER DIAGRAM PART OF THE 1/2 BATH ON FLOOR PLAN | | WITH OWN VENT. | | B) KITCHEN, RISER DIAGRAM SHOWS A LOOP VENT, | | FLAT DRAWING DOES NOT. | | C) MASTER BATH RISER DIAGRAM DOES NOT MATCH FLAT | | DRAWING | | RISER DIAGRAM SHOWS 2" AT BASE OF WAHER STACK WITH A 3" | | VENT THOUGH ROOF. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|