2007-09-28 09:49:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11B STATES THE AIR HANDLER
 IS INSTALLED IN THE INTERIOR, BUT THE PLANS SHOW THE
 AIR HANDLER TO BE INSTALLED IN THE ATTIC, THE TWO MUST
 COINCIDE. SEE F.B.C. 106.1.1CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS. PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS SHOW SYSTEM ONE TOTAL
 COOLING BTU'S TO BE 34,112, MECHANICAL PLANS SHOW
 SYSTEM ONE TO BE 46,500 TOTAL BTU'S. PER F.B.C.
 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE
 TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS,
 PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 3
 TON SYSTEM MAYMEET THIS REQUIREMENT).
  
 3) COOLING LOAD CALCULATIONS SHOW SYSTEM TWO TOTAL
 COOLING BTU'S TO BE 20,318, MECHANICAL PLANS SHOW
 SYSTEM TWO TO BE 29,200 TOTAL BTU'S. PER F.B.C.
 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE
 TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS,
 PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 2
 TON SYSTEM MAYMEET THIS REQUIREMENT).
  
 4) SEE MECHANICAL PLAN EQUIPMENT SCHEDULE, MODEL
 NUMBERS FOR THE CONDENSER UNITS COULD NOT BE FOUND IN
 THE ARI DIRECTORY, PLEASE CORRECT AND PROVIDE A ARI
 REFERENCE SHEET, SEE W.P.B AMEND. 106.2.
  
 MECHANICAL PLAN REVIEW BY;