 ELECTRICAL PLAN REVIEW
 6793 SPARROW HAWK DRIVE
  
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER
 THAN THE AVAILABLE FAULT.
  
 2} THE 13000VA HEAT CALCULATION GIVEN IN PANEL "A" DOES
 NOT CORRELATE TO THE 10000 VA LOADS SHOWN IN THE PANEL
 SCHEDULE OR IN THE MECHANICAL SPECIFICATIONS.
  
 3} THE 6' GROUND ROD INDICATED ON THE RISER DIAGRAM IS
 NOT IN COMPLIANCE WITH 250.53(G) "THE ELECTRODE SHALL
 BE INSTALLED SUCH THAT AT LEAST 2.44 M (8 FT) OF LENGTH
 IS IN CONTACT WITH THE SOIL".
  
 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE
 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE
 CURRENT EDITION ADOPTED BY THE STATE.
  
 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B"
 IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80
 WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE
 INCREASED TO 1 1/4"TO MEET MINIMUM SIZE FOR FILL
 REQUIREMENTS OF ARTICLE 352.22.
  
 6} THE ELECTRICAL NOTES ON SHEET D-1 INDICATE #12
 CONDUCTORS WILL BE THE MINIMUM SIZE FOR THIS PROJECT,
 THE PANEL SCHEDULE FOR PANEL "A" LISTS SEVERAL #14
 CONDUCTORS FOR BRANCH CIRCUITS. PLEASE CORRELATE SAME.
  
 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS.
 SEE 61G1-16.001 FAC.
  
 8} THE SIGNATURE OF THE REVIEWER FOR GFA CANNOT BE READ
 DUE TO THE LOCATION IN THE COMPLIANCE BLOCK.
  