2007-09-27 14:23:51 | |
| |
| APPLICATION #07090742 |
| ELECTRICAL PLAN REVIEW |
| 6793 SPARROW HAWK DRIVE |
| |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER |
| THAN THE AVAILABLE FAULT. |
| |
| 2} THE 13000VA HEAT CALCULATION GIVEN IN PANEL "A" DOES |
| NOT CORRELATE TO THE 10000 VA LOADS SHOWN IN THE PANEL |
| SCHEDULE OR IN THE MECHANICAL SPECIFICATIONS. |
| |
| 3} THE 6' GROUND ROD INDICATED ON THE RISER DIAGRAM IS |
| NOT IN COMPLIANCE WITH 250.53(G) "THE ELECTRODE SHALL |
| BE INSTALLED SUCH THAT AT LEAST 2.44 M (8 FT) OF LENGTH |
| IS IN CONTACT WITH THE SOIL". |
| |
| 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE |
| 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE |
| CURRENT EDITION ADOPTED BY THE STATE. |
| |
| 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B" |
| IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80 |
| WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE |
| INCREASED TO 1 1/4"TO MEET MINIMUM SIZE FOR FILL |
| REQUIREMENTS OF ARTICLE 352.22. |
| |
| 6} THE ELECTRICAL NOTES ON SHEET D-1 INDICATE #12 |
| CONDUCTORS WILL BE THE MINIMUM SIZE FOR THIS PROJECT, |
| THE PANEL SCHEDULE FOR PANEL "A" LISTS SEVERAL #14 |
| CONDUCTORS FOR BRANCH CIRCUITS. PLEASE CORRELATE SAME. |
| |
| 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS. |
| SEE 61G1-16.001 FAC. |
| |
| 8} THE SIGNATURE OF THE REVIEWER FOR GFA CANNOT BE READ |
| DUE TO THE LOCATION IN THE COMPLIANCE BLOCK. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |