Plan Review Notes
Plan Review Notes For Permit 07090742
Permit Number 07090742
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-01 17:54:362004 FBC W/2007 REVISIONS
 NSFR
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE INFORMATION IN REGARDS TO THE SURROUNDING
 TERRAIN. NOTE THAT THE DEFINITION FOR EXPOSURE C HAS
 CHANGED EFFECTIVE DECEMBER 8, 2006 (2006 AMENDMENTS TO
 THE FBC), FBC1609.4, FBC R301.2.1.4.
 IF THERE IS EXPOSURE C TYPE TERRAIN IN ANY QUADRANT
 FOR A DISTANCE OF MORE THAN 600 FEET THE STRUCTURE
 SHALL BE DESIGNED TO EXPOSURE C. NOTE: THE COMPONENT
 AND CLADDING PRESSURES WILL NEED TO BE INCREASED TO
 EXPOSURE C VALUES, WHICH MAY AFFECT THE PRODUCT
 APPROVALS.
  
 3) A ONE HOUR FIRE RATED GLASS BLOCK ASSEMBLY WILL BE
 REQUIRED AT THE ZERO LOT LINE PER R302.1. PLEASE
 SPECIFY ON THE PLANS.
  
 4) SUBMIT PRODUCT APPROVALS, MANUFACTURER'S
 SPECIFICATIONS AND LISTING FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK ASSEMBLY THAT WILL BE USED.
  
 5) SHOW COMPLIANCE WITH FBC R401.3 DRAINAGE.
  
 6) IN THE WINDOW SCHEDULE ON SHEET A-4.0, 2" X 4"
 MULLIONS ARE SPECIFIED. SUBMIT PRODUCT APPROVALS FOR
 THESE MULLS AS REQUIRED BY FAC RULE 9B-72 OR REVISE THE
 PLAN.
  
 7) THE PRODUCT APPROVAL FOR THE IMPACT SLIDING GLASS
 DOOR FL251-R5 HAS BEEN REVISED AS THE NOA EXPIRED ON
 11/9/05. SUBMIT THE NEW FL251-R7 AND CURRENT NOA.
  
 8) SPECIFY WHICH FASTENERS LISTED IN THE ICC ROOF TILE
 PRODUCT APPROVAL WILL BE USED TO ATTACH THE TILES.
 CIRCLE THE NUMBER AND TYPE ON THE PRODUCT APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]