Plan Review Notes For Permit 07090714 |
Permit Number |
07090714 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-01 13:15:08 | | | | | APPLICATION #07090714 | | ELECTRICAL PLAN REVIEW | | 1000 OKEECHOBEE ROAD | | | | WEST PALM BEACH, FL. | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE | | CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE | | INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE | | CABLE. | | | | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|