2007-12-20 14:51:23** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE NOTES FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 NOTES DUE TO CHANGES MADE TO PLANS WHICH WERE NOT ON
 PREVIOUS PLANS.
  
  
 1) NOTE: PLEASE SEE FBC R313 FOR SMOKE ALARMS REQUIRED
 TO MEET NFPA-72 11.5.1.1INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING ROOMS.
 PLEASE SHOW AND INDICATE THESE IN THE EXISTING DWELLING
 EITHER NEW TO BE INSTALLED OR EXISTING MEETING CURRENT
 CODE.
 THIS NOTE WAS ON PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE THE RISER DIAGRAM HAS COMPLETELY
 BEEN REVISED AND CHANGED FROM PREVIOUS PLANS.
 PLEASE SEE THERE ARE SEVERAL ITEMS SHOWN ON LOAD
 CALCULATIONS HOWEVER ARE NOT LISTED ON PANEL SCHEDULE.
 FOR EXAMPLE: PLEASE SEE DISHWASHER, WASHER, DRYER,
 SMALL APPLIANCE, ETC ETC WHICH ARE NOT LISTED ON THE
 PANEL SCHEDULE.
 PLEASE LIST.
 PLEASE KNOW THE MINIMUM OVER CURRENT PROTECTION, AND
 CONDUCTOR SIZES NEED TO BE VERIFIED AT THIS TIME FROM
 NEW PANEL.
 240.4, 310.16
 PLEASE SEE NEC 408.4 AS THIS REQUIRES ALL CIRCUITS TO
 BE IDENTIFIED ON PANEL SCHEDULE FOR ROOMS AND AREAS IN
 WHICH THEY FEED.
  
 3) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS, THE NOTE MENTIONS AT THE BOTTOM OF PANEL
 SCHEDULE HOWEVER AS NOTED ABOVE ON NOTE #2, THIS NEEDS
 TO BE LISTED FOR CIRCUITS. THIS ITEM COULD BE REDLINED
 FOR REVISION BEFORE FINAL HOWEVER MAY BE REVISED AT
 THIS TIME.
 THIS WAS NOTED ON PREVIOUS REVIEW.
  
 4) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE AND
 REQUIRED BY CODE ALL RECESSED LIGHTS NEED TO MEET FBC
 13-606.1.ABC.1.2.4 FOR TRANSFER OF AIR FROM CONDITIONED
 SPACE.
  
 ** PLEASE KNOW SOME OF THESE ITEMS COULD HAVE BEEN
 RED-LINED HOWEVER NOT ALL. PLANS ARE COMING BACK FOR
 COMMENTS FROM ZONING PLEASE ADDRESS AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved