2007-12-20 14:51:23 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME OF THE NOTES FROM PREVIOUS REVIEW |
| ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| NOTES DUE TO CHANGES MADE TO PLANS WHICH WERE NOT ON |
| PREVIOUS PLANS. |
| |
| |
| 1) NOTE: PLEASE SEE FBC R313 FOR SMOKE ALARMS REQUIRED |
| TO MEET NFPA-72 11.5.1.1INSIDE AND OUTSIDE ALL |
| EXISTING SLEEPING ROOMS. |
| PLEASE SHOW AND INDICATE THESE IN THE EXISTING DWELLING |
| EITHER NEW TO BE INSTALLED OR EXISTING MEETING CURRENT |
| CODE. |
| THIS NOTE WAS ON PREVIOUS REVIEW. |
| |
| 2) NOTE: PLEASE SEE THE RISER DIAGRAM HAS COMPLETELY |
| BEEN REVISED AND CHANGED FROM PREVIOUS PLANS. |
| PLEASE SEE THERE ARE SEVERAL ITEMS SHOWN ON LOAD |
| CALCULATIONS HOWEVER ARE NOT LISTED ON PANEL SCHEDULE. |
| FOR EXAMPLE: PLEASE SEE DISHWASHER, WASHER, DRYER, |
| SMALL APPLIANCE, ETC ETC WHICH ARE NOT LISTED ON THE |
| PANEL SCHEDULE. |
| PLEASE LIST. |
| PLEASE KNOW THE MINIMUM OVER CURRENT PROTECTION, AND |
| CONDUCTOR SIZES NEED TO BE VERIFIED AT THIS TIME FROM |
| NEW PANEL. |
| 240.4, 310.16 |
| PLEASE SEE NEC 408.4 AS THIS REQUIRES ALL CIRCUITS TO |
| BE IDENTIFIED ON PANEL SCHEDULE FOR ROOMS AND AREAS IN |
| WHICH THEY FEED. |
| |
| 3) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| CIRCUITS, THE NOTE MENTIONS AT THE BOTTOM OF PANEL |
| SCHEDULE HOWEVER AS NOTED ABOVE ON NOTE #2, THIS NEEDS |
| TO BE LISTED FOR CIRCUITS. THIS ITEM COULD BE REDLINED |
| FOR REVISION BEFORE FINAL HOWEVER MAY BE REVISED AT |
| THIS TIME. |
| THIS WAS NOTED ON PREVIOUS REVIEW. |
| |
| 4) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE AND |
| REQUIRED BY CODE ALL RECESSED LIGHTS NEED TO MEET FBC |
| 13-606.1.ABC.1.2.4 FOR TRANSFER OF AIR FROM CONDITIONED |
| SPACE. |
| |
| ** PLEASE KNOW SOME OF THESE ITEMS COULD HAVE BEEN |
| RED-LINED HOWEVER NOT ALL. PLANS ARE COMING BACK FOR |
| COMMENTS FROM ZONING PLEASE ADDRESS AT THIS TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |