Plan Review Notes
Plan Review Notes For Permit 07090685
Permit Number 07090685
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-27 07:53:562007-09-27 07:53:56
  
 ** DENIED**
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE PLANS ARE MISSING INDICATING
 LOCATIONS FOR NEW AND/OR EXISTING SMOKE ALARMS PER FBC
 R313 AND NFPA-72 11.5.1.1, 11.8.3.
 PLEASE SEE THE FIRST FLOOR OF THE NEW ADDITION IS
 MISSING A SMOKE ALARM ALSO IN THE VICINITY LEADING TO
 THE FLOOR ABOVE.
 PLEASE KNOW THE OFFICE IS CONSIDERED AN ADAPTABLE
 SLEEPING ROOM THIS WILL ALSO REQUIRE SMOKE ALARMS
 INSIDE AND OUTSIDE THIS ROOM.
 PLEASE SEE THE SMOKE DETECTION DEVICE IS REQUIRED TO BE
 WITHIN 3FT OG THE PEAK ON THE SLOPED CEILING OR WITHIN
 12INCHES FOR HIGHEST POINT ON FLAT OR TRAY CEILINGS.
 PLEASE SEE MINIMUM DISTANCES FROM CEILING FANS AS
 STATED IN NFPA-72 11.8.3.
 PLEASE KNOW THAT THE PLANS ARE SHOWING *SD* AND LEGEND
 STATES SMOKE DETECTORS. PLEASE VERIFY THIS AS BY
 NFPA-72 DEFINITIONS A SMOKE DETECTOR IS ONLY A DEVICE
 WHICH DETECTS AND DOES NOT SOUND AN ALARM. THE PLANS
 WOULD THEN NEED TO INDICATE THE HORN DEVICES ALONG WITH
 A FIRE ALARM PANEL. IF THIS IS THE INTENT PLEASE
 COMPLETE PLANS ACCORDINGLY. IF THESE ARE MEANT TO BE SA
 FOR SMOKE ALARMS WHICH ARE A DEVICE WHICH DETECTS AND
 SOUNDS AN ALARM PLEASE ADJUST SYMBOL AND LEGEND.
  
 3) NOTE: PLEASE SEE RISER MENTIONS NEW SERVICE, HOWEVER
 EXISTING METER. PLEASE INDICATE THE SIZE/AMPERAGE OF
 THIS METER.
 PLEASE SEE THE RISER IS MISSING ALL CONDUCTORS FROM
 METER TO GUTTER, GUTTER TO MAINS ETC.
 THIS SERVICE IS BEING SHOWN AS 225AMPS. PLEASE VERIFY.
 PLEASE COMPLETE RISER.
 240.4, 310.16
  
 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE
 LOCATIONS OF ALL SERVICE EQUIPMENT ALONG WITH THE
 LOCATION OF NEW PANEL.
 PLEASE SEE 230.70, 230.71, 230.72, 230.76 AND 230.76
 FOR MAINS AND GROUPING.
 PLEASE SEE 110.26, 240.24, FOR LOCATIONS WHICH NEED TO
 MEET THESE SECTIONS ALONG WITH OTHER SECTIONS OF THE
 NEC.
 PLEASE KNOW AS THE LOCATIONS OF EQUIPMENT HAVE NOT BEEN
 SHOWN, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
 5) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 SIZE IS TOO SMALL FOR THE SERVICE AS SHOWN.
 PLEASE SEE 250.66.
  
 6) NOTE: PLEASE SEE MISSING COMPLETE GROUNDING
 ELECTRODE SYSTEM PER 250.50.
 PLEASE SEE MISSING NEW FOOTER STEEL REQUIRED AND OTHER
 ELECTRODES.
  
 7) NOTE: PLEASE SEE MISSING AIC RATING(S) FOR NEW
 SERVICE EQUIPMENT PER 110.9.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE MISSING CONDENSING UNIT ON PLANS
 ALONG WITH REQUIRED DISCONNECT PER 440.11 AND MISSING
 GFI RECEPTACLE PER 210.63 AND 210.8A3
  
 9) NOTE: PLEASE SEE MISSING REQUIRED LISTED ARC FAULT
 PROTECTED CIRCUITS PER 210.12 FOR *ALL* OUTLETS IN
 DWELLING SLEEPING ROOMS.
  
 10) NOTE: PLEASE SEE MISSING THE REQUIRED DEDICATED
 BATH(S) CIRCUIT(S) PER 210.52D AND 210.11C3. PLEASE
 KNOW THESE MUST BE 20AMP AND #12. PLEASE ADJUST PANEL
 SCHEDULE.
  
 11) NOTE: PLEASE SE THE CLOSET LIGHT DOES NOT MEET THE
 MINIMUM CLEARANCE REQUIREMENTS PER 410.8.
 THIS IS FOR OFFICE CLOSET.
  
 12) NOTE: PLEASE 220.83B FOR LOAD CALCULATIONS AND
 ADJUST.
 PLEASE SEE 422.13 AS THE LOAD TO BE FIGURED FOR THE
 WATER HEATER IS TO BE SHOWN AT 125%. THIS WAS CHANGED
 IN THE 2005 NEC AS THIS IS NOW CONSIDERED A CONTINUOUS
 LOAD.
 PLEASE VERIFY SMALL APPLIANCE CIRCUITS PER 210.52B,
 210.11C1, 220.53 (SHOWN AS PORTABLE?)
 PLEASE ADJUST LOAD CALCULATIONS.
  
 13) NOTE: PLEASE SEE THE RISER IS MISSING THE EQUIPMENT
 GROUNDING CONDUCTORS FROM NEW MAIN TO NEW PANEL PER
 250.110, 250.122.
  
 14) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL
 MISSING RECEPTACLES PER 2FT OF WALL SPACE. SOME OF
 THESE LOCATIONS ARE REDLINED ON ONE SET OF PLANS.
 PLEASE SEE 2FT, 6FT, AND 12FT RULE.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS MISSING FROM
 PLANS A FULL AND COMPLETE REVIEW FOR CODE COMPLIANCE
 COULD NOT BE DONE AT THIS TIME. PLEASE KNOW THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-27 06:54:342007-09-27 06:54:34
  
 IN ELEC FOR REVIEW.