| ** DENIED** |
| |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| NOT MADE BY OTHER TRADE(S). |
| |
| 2) NOTE: PLEASE SEE THE PLANS ARE MISSING INDICATING |
| LOCATIONS FOR NEW AND/OR EXISTING SMOKE ALARMS PER FBC |
| R313 AND NFPA-72 11.5.1.1, 11.8.3. |
| PLEASE SEE THE FIRST FLOOR OF THE NEW ADDITION IS |
| MISSING A SMOKE ALARM ALSO IN THE VICINITY LEADING TO |
| THE FLOOR ABOVE. |
| PLEASE KNOW THE OFFICE IS CONSIDERED AN ADAPTABLE |
| SLEEPING ROOM THIS WILL ALSO REQUIRE SMOKE ALARMS |
| INSIDE AND OUTSIDE THIS ROOM. |
| PLEASE SEE THE SMOKE DETECTION DEVICE IS REQUIRED TO BE |
| WITHIN 3FT OG THE PEAK ON THE SLOPED CEILING OR WITHIN |
| 12INCHES FOR HIGHEST POINT ON FLAT OR TRAY CEILINGS. |
| PLEASE SEE MINIMUM DISTANCES FROM CEILING FANS AS |
| STATED IN NFPA-72 11.8.3. |
| PLEASE KNOW THAT THE PLANS ARE SHOWING *SD* AND LEGEND |
| STATES SMOKE DETECTORS. PLEASE VERIFY THIS AS BY |
| NFPA-72 DEFINITIONS A SMOKE DETECTOR IS ONLY A DEVICE |
| WHICH DETECTS AND DOES NOT SOUND AN ALARM. THE PLANS |
| WOULD THEN NEED TO INDICATE THE HORN DEVICES ALONG WITH |
| A FIRE ALARM PANEL. IF THIS IS THE INTENT PLEASE |
| COMPLETE PLANS ACCORDINGLY. IF THESE ARE MEANT TO BE SA |
| FOR SMOKE ALARMS WHICH ARE A DEVICE WHICH DETECTS AND |
| SOUNDS AN ALARM PLEASE ADJUST SYMBOL AND LEGEND. |
| |
| 3) NOTE: PLEASE SEE RISER MENTIONS NEW SERVICE, HOWEVER |
| EXISTING METER. PLEASE INDICATE THE SIZE/AMPERAGE OF |
| THIS METER. |
| PLEASE SEE THE RISER IS MISSING ALL CONDUCTORS FROM |
| METER TO GUTTER, GUTTER TO MAINS ETC. |
| THIS SERVICE IS BEING SHOWN AS 225AMPS. PLEASE VERIFY. |
| PLEASE COMPLETE RISER. |
| 240.4, 310.16 |
| |
| 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE |
| LOCATIONS OF ALL SERVICE EQUIPMENT ALONG WITH THE |
| LOCATION OF NEW PANEL. |
| PLEASE SEE 230.70, 230.71, 230.72, 230.76 AND 230.76 |
| FOR MAINS AND GROUPING. |
| PLEASE SEE 110.26, 240.24, FOR LOCATIONS WHICH NEED TO |
| MEET THESE SECTIONS ALONG WITH OTHER SECTIONS OF THE |
| NEC. |
| PLEASE KNOW AS THE LOCATIONS OF EQUIPMENT HAVE NOT BEEN |
| SHOWN, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT |
| THIS TIME. |
| |
| 5) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR |
| SIZE IS TOO SMALL FOR THE SERVICE AS SHOWN. |
| PLEASE SEE 250.66. |
| |
| 6) NOTE: PLEASE SEE MISSING COMPLETE GROUNDING |
| ELECTRODE SYSTEM PER 250.50. |
| PLEASE SEE MISSING NEW FOOTER STEEL REQUIRED AND OTHER |
| ELECTRODES. |
| |
| 7) NOTE: PLEASE SEE MISSING AIC RATING(S) FOR NEW |
| SERVICE EQUIPMENT PER 110.9. |
| FBC 106.1.2 |
| |
| 8) NOTE: PLEASE SEE MISSING CONDENSING UNIT ON PLANS |
| ALONG WITH REQUIRED DISCONNECT PER 440.11 AND MISSING |
| GFI RECEPTACLE PER 210.63 AND 210.8A3 |
| |
| 9) NOTE: PLEASE SEE MISSING REQUIRED LISTED ARC FAULT |
| PROTECTED CIRCUITS PER 210.12 FOR *ALL* OUTLETS IN |
| DWELLING SLEEPING ROOMS. |
| |
| 10) NOTE: PLEASE SEE MISSING THE REQUIRED DEDICATED |
| BATH(S) CIRCUIT(S) PER 210.52D AND 210.11C3. PLEASE |
| KNOW THESE MUST BE 20AMP AND #12. PLEASE ADJUST PANEL |
| SCHEDULE. |
| |
| 11) NOTE: PLEASE SE THE CLOSET LIGHT DOES NOT MEET THE |
| MINIMUM CLEARANCE REQUIREMENTS PER 410.8. |
| THIS IS FOR OFFICE CLOSET. |
| |
| 12) NOTE: PLEASE 220.83B FOR LOAD CALCULATIONS AND |
| ADJUST. |
| PLEASE SEE 422.13 AS THE LOAD TO BE FIGURED FOR THE |
| WATER HEATER IS TO BE SHOWN AT 125%. THIS WAS CHANGED |
| IN THE 2005 NEC AS THIS IS NOW CONSIDERED A CONTINUOUS |
| LOAD. |
| PLEASE VERIFY SMALL APPLIANCE CIRCUITS PER 210.52B, |
| 210.11C1, 220.53 (SHOWN AS PORTABLE?) |
| PLEASE ADJUST LOAD CALCULATIONS. |
| |
| 13) NOTE: PLEASE SEE THE RISER IS MISSING THE EQUIPMENT |
| GROUNDING CONDUCTORS FROM NEW MAIN TO NEW PANEL PER |
| 250.110, 250.122. |
| |
| 14) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL |
| MISSING RECEPTACLES PER 2FT OF WALL SPACE. SOME OF |
| THESE LOCATIONS ARE REDLINED ON ONE SET OF PLANS. |
| PLEASE SEE 2FT, 6FT, AND 12FT RULE. |
| |
| ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS MISSING FROM |
| PLANS A FULL AND COMPLETE REVIEW FOR CODE COMPLIANCE |
| COULD NOT BE DONE AT THIS TIME. PLEASE KNOW THERE MAY |
| VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |