Plan Review Notes
Plan Review Notes For Permit 07090662
Permit Number 07090662
Review Stop P
Sequence Number 2
Notes
Date Text
2007-11-05 17:00:59DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS:
  
 1. RESUBMITTED ISOMETRIC WATER RISER DIAGRAM IN PENCIL
 IS UNACCEPTABLE. PLEASE RESUBMIT IN PEN. PER *106.1.3
 QUALITY OF BUILDING PLANS.
  
 2. THERE WAS ONLY ONE BELLA PEDICURE SPAS SCHEMATIC IN
 THE RESUBMITTAL.
 PER *106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 3. THE WASTE FOR THE PEDICURE SPAS MUST DRAIN
 DOWNSTREAM OF THE EXISTING WET VENT BATHROOM. PER
 FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 4. PER DISCUSSION WITH ACTING CHIEF PLUMBING INSPECTOR
 LARRY WAGNER THE WASTE PIPE AND THE WASTE STACK FOR THE
 PEDICURE SPAS WILL NEED TO BE 3" AND THE TRAP WILL NEED
 TO BE 2" WITH A STANDPIPE, PER *422 HEALTH CARE
 FIXTURES AND EQUIPMENT, *406.3 WASTE CONNECTION, AND
 802.4 STANDPIPES.
  
 5. CLEANOUTS ARE REQUIRED FOR THE PEDICURE SPAS PER
 THE FOLLOWING:
  
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **NOTE: CLEANOUT FOR THE PEDICURE SPAS SHALL BE THREE
 INCH (3").
  
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE PEDICURE SPAS SHALL BE FOUR
 FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 6. VACUUM BREAKERS ARE REQUIRED FOR THE HOT AND COLD
 WATER TO THE PEDICURE SPAS. VACUUM BREAKERS SHALL BE
 INSTALLED A MINIMUM OF 6 INCHES ABOVE THE FLOOD LEVEL
 RIM OF THE FIXTURE OR DEVICE IN ACCORDANCE WITH SECTION
 *608. THE FLOOD LEVEL RIM OF HOSE CONNECTIONS SHALL BE
 THE MAXIMUM HEIGHT AT WHICH ANY HOSE IS UTILIZED.
 PLEASE INDICATE THESE ON THE RESUBMITTED WATER RISER
 DIAGRAM.
  
 7. RESUBMITTED PLANS INDICATE EXISTING BACKFLOW
 PREVENTERS. PER *607.3.2 WHERE A BACKFLOW PREVENTION
 DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING
 WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION
 CONTROL CAUSES AN INCREASED PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED. PLEASE
 INDICATE THIS ON THE RESUBMITTED WATER RISER DIAGRAM.
  
 8. PER *606.1(7) A FULL OPEN VALVE IS REQUIRED ON THE
 WATER SUPPLY PIPE TO EVERY WATER HEATER. PLEASE
 INDICATE THIS ON THE RESUBMITTED WATER RISER DIAGRAM.
  
 9. PLEASE CLEARLY INDICATE ON THE RESUBMITTED PLANS IF
 THE NEW WATER HEATER IS GAS OR ELECTRIC. *PER *106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 10. THE RESUBMITTED EXISTING FLOOR PLAN OR THE NEW
 FLOOR PLAN ARE NOT INDICATING A DRINKING FOUNTAIN. PER
 TABLE *403.1(2) ONE IS REQUIRED FOR BUILDINGS FOR THE
 TRANSACTION OF BUSINESS AND THEY MUST BE ACCESSIBLE.
 PLEASE INDICATE THAT THERE IS AN EXISTING DRINKING
 FOUNTAIN AND ITS LOCATION OR INDICATE THAT A NEW ONE
 WILL BE PROVIDED WITH THE FOLLOWING INFORMATION ON THE
 RESUBMITTED PLANS. IF A NEW ONE IS REQUIRED THE
 PLUMBING FOR THE NEW DRINKING FOUNTAIN WILL NEED TO BE
 ON THE RESUBMITTED SANITARY AND WATER RISER DIAGRAMS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  
  