2007-10-09 14:11:27 | DENIED |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| ** FLORIDA STATUTES (FS). |
| ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. VALUE OF THE PROPOSED WORK IS TO LOW PER FBC-2004, |
| CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. |
| NOTE: ONLINE SEARCH OF PEDICURE CHAIRS INDICATES COST |
| PER ONE CHAIR AT $2100.00 NOT TO MENTION THE COST OF |
| THE KITCHEN SINK AND WATER HEATER PLUS LABOR AND |
| MATERIALS. ADJUST THE COST AND PAY THE DIFFERENCE PRIOR |
| TO THE RESUBMITTAL. |
| |
| 2. SUBMIT (TWO COPIES) OF MINIMUM OF 1/8 INCH SCALE OF |
| THE EXISTING FLOOR PLAN LAYOUT OF BUILDING AND ANOTHER |
| WITH THE PROPOSED LAYOUT OF THE PEDICURE CHAIRS AND |
| KITCHEN SINK PER FBC-2004 CHAPTER 1, SECTION 106.1.3. |
| |
| 3. NEW PROPSED KITCHEN SINK NEEDS TO BE ACCESSIBLE AND |
| AN ELEVATION DETAIL IS REQUIRED WITH THE FOLLOWING |
| INFORMATION: |
| |
| **SINKS |
| A} 11-4.24.2 HEIGHT: 34 INCHES MAX TO RIM. |
| B} 11-4.24.3 KNEE CLEARANCE: 27 INCHES HIGH, 30 INCHES |
| WIDE, 19 INCHES DEEP. |
| C} 11-4.24.4 SINK DEPTH: 6-1/2 INCHES DEEP. |
| D} 11-4.24.5 CLEAR FLOOR SPACE: 30 INCHES X 48 INCHES. |
| (INDICATE CLEAR FLOOR SPACE ON PROPOSED LAYOUT FLOOR |
| PLAN) |
| E} 11-4.24.6 EXPOSED PIPES AND SURFACES: PROTECTION |
| REQUIRED. |
| F} 11-4.24.7 FAUCETS: LEVER-OPERATED, PUSH-TYPE, |
| TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED ARE |
| ACCEPTABLE. |
| |
| 4. PER FBC-2004 CHAPTER 1, SECTION106.3.5.1.3 PLEASE |
| INDICATE THE FOLLOWING INFORMATION PER THE FOLLOWING |
| SUBSECTIONS: |
| |
| (3) ISOMETRIC WATER RISER DIAGRAM INDICATING PIPE |
| SIZES, VALVE LOCATIONS, BACKFLOW PREVENTION (BACKFLOW |
| PREVENTOR LOCATION AND VACUUM BREAKERS FOR NEW PEDICURE |
| CHAIRS) |
| |
| (5) WATER HEATER SIZE AND LOCATION ON FLOOR PLAN. |
| |
| (8) BACKFLOW PREVENTER LOCATION ON SITE PLAN. |
| |
| (10) LOCATION OF THE WATER SUPPLY LINE. |
| |
| 5. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE |
| PROPOSED AIR ADMITTANCE VALVES ARE COMPLIANT WITH |
| FBC-2004 WITH 05 & 06 REV. SECTION 917.3.1 LOCATION OF |
| BRANCH: THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO |
| THE DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR |
| BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| |
| 6. 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |