Plan Review Notes
Plan Review Notes For Permit 07090662
Permit Number 07090662
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-09 14:11:27DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. VALUE OF THE PROPOSED WORK IS TO LOW PER FBC-2004,
 CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: ONLINE SEARCH OF PEDICURE CHAIRS INDICATES COST
 PER ONE CHAIR AT $2100.00 NOT TO MENTION THE COST OF
 THE KITCHEN SINK AND WATER HEATER PLUS LABOR AND
 MATERIALS. ADJUST THE COST AND PAY THE DIFFERENCE PRIOR
 TO THE RESUBMITTAL.
  
 2. SUBMIT (TWO COPIES) OF MINIMUM OF 1/8 INCH SCALE OF
 THE EXISTING FLOOR PLAN LAYOUT OF BUILDING AND ANOTHER
 WITH THE PROPOSED LAYOUT OF THE PEDICURE CHAIRS AND
 KITCHEN SINK PER FBC-2004 CHAPTER 1, SECTION 106.1.3.
  
 3. NEW PROPSED KITCHEN SINK NEEDS TO BE ACCESSIBLE AND
 AN ELEVATION DETAIL IS REQUIRED WITH THE FOLLOWING
 INFORMATION:
  
 **SINKS
 A} 11-4.24.2 HEIGHT: 34 INCHES MAX TO RIM.
 B} 11-4.24.3 KNEE CLEARANCE: 27 INCHES HIGH, 30 INCHES
 WIDE, 19 INCHES DEEP.
 C} 11-4.24.4 SINK DEPTH: 6-1/2 INCHES DEEP.
 D} 11-4.24.5 CLEAR FLOOR SPACE: 30 INCHES X 48 INCHES.
 (INDICATE CLEAR FLOOR SPACE ON PROPOSED LAYOUT FLOOR
 PLAN)
 E} 11-4.24.6 EXPOSED PIPES AND SURFACES: PROTECTION
 REQUIRED.
 F} 11-4.24.7 FAUCETS: LEVER-OPERATED, PUSH-TYPE,
 TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED ARE
 ACCEPTABLE.
  
 4. PER FBC-2004 CHAPTER 1, SECTION106.3.5.1.3 PLEASE
 INDICATE THE FOLLOWING INFORMATION PER THE FOLLOWING
 SUBSECTIONS:
  
 (3) ISOMETRIC WATER RISER DIAGRAM INDICATING PIPE
 SIZES, VALVE LOCATIONS, BACKFLOW PREVENTION (BACKFLOW
 PREVENTOR LOCATION AND VACUUM BREAKERS FOR NEW PEDICURE
 CHAIRS)
  
 (5) WATER HEATER SIZE AND LOCATION ON FLOOR PLAN.
  
 (8) BACKFLOW PREVENTER LOCATION ON SITE PLAN.
  
 (10) LOCATION OF THE WATER SUPPLY LINE.
  
 5. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE
 PROPOSED AIR ADMITTANCE VALVES ARE COMPLIANT WITH
 FBC-2004 WITH 05 & 06 REV. SECTION 917.3.1 LOCATION OF
 BRANCH: THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO
 THE DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
  
 6. 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  