Plan Review Notes
Plan Review Notes For Permit 07090657
Permit Number 07090657
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-15 16:49:44**** DENIED ****
  
  
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE
 ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING DATED FEBRUARY OF 2004 WHICH REQUIRED
 ALL SEALS FOR ENGINEERS WITH THE WORDING OF
 *CERTIFICATE* TO BE CHANGED TO *LICENSE*.
 61G15-23.001.
 PLEASE KNOW AN EXTENSION WAS GIVEN TO A DATE OF
 DECEMBER 31ST, 2005 HOWEVER PLANS MAY NOT USE THIS SEAL
 AFTER THIS DATE. ANY QUESTIONS SHOULD BE DIRECTED TO
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AS THIS
 RULING WAS CHANGED OVER THREE YEARS AGO.
 PLEASE OBTAIN NEW SEAL AND ADJUST FOR NOTES #2 AND #3.
  
 3) NOTE: PLEASE SEE FS 471.025 AS THIS AND FAC
 61G15-23.002 REQUIRES THE ENGINEER TO DATE PLANS WHEN
 SIGNING AND SEALING DOCUMENTS. THE PLANS WERE NOT
 DATED.
  
 4) NOTE: PLEASE SEE THE EQUIPMENT AS SUBMITTED AND
 SHOWN ON PLANS DO NOT INDICATE ANY LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY. NRTL.
 PLEASE SEE 110.3, 90.7
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 REVIEW.
 THIS IS FOR EQUIPMENT ON A-2.3
  
 5) NOTE: PLEASE BE SURE TO PROVIDE ELECTRICAL
 INFORMATION FOR EQUIPMENT ON SHEETS FOR VOLTAGE
 CONNECTIONS.
 PANEL IS BEING NOTED AS 277/480V AND UNTIL MANUFACTURES
 SPECS/CUT SHEETS CAN BE REVIEWED SIZING OF CIRCUITS,
 LOADS ETC CAN NOT BE CONFIRMED.
 ELECTRICAL PLANS DO NOT INDICATE SIZE OF CIRCUITS, OVER
 CURRENT PROTECTION, CONDUCTOR ETC.240.4, 310.16 ETC
 PLAN SHEET A-1.1 SHOWS ONE NEW RECEPTACLE BEING
 INSTALLED WHICH DOES NOT SEEM TO BE WHAT IS NEEDED
 BASED ON EQUIPMENT AS SHOWN. IS THIS A 277/480V
 RECEPTACLE? PLEASE SPECIFY TYPE. (NEMA RATING/NUMBER).
 ELECTRICAL PANEL SCHEDULE DOES NOT SHOW THE NEW
 CIRCUIT(S). 408.4
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]