2007-10-15 16:49:44 | **** DENIED **** |
| |
| |
| |
| 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| CODES ARE STATED ON PLANS. |
| PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| MINIMUM. |
| PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| |
| 2) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE |
| ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA. |
| PLEASE SEE RULING DATED FEBRUARY OF 2004 WHICH REQUIRED |
| ALL SEALS FOR ENGINEERS WITH THE WORDING OF |
| *CERTIFICATE* TO BE CHANGED TO *LICENSE*. |
| 61G15-23.001. |
| PLEASE KNOW AN EXTENSION WAS GIVEN TO A DATE OF |
| DECEMBER 31ST, 2005 HOWEVER PLANS MAY NOT USE THIS SEAL |
| AFTER THIS DATE. ANY QUESTIONS SHOULD BE DIRECTED TO |
| THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AS THIS |
| RULING WAS CHANGED OVER THREE YEARS AGO. |
| PLEASE OBTAIN NEW SEAL AND ADJUST FOR NOTES #2 AND #3. |
| |
| 3) NOTE: PLEASE SEE FS 471.025 AS THIS AND FAC |
| 61G15-23.002 REQUIRES THE ENGINEER TO DATE PLANS WHEN |
| SIGNING AND SEALING DOCUMENTS. THE PLANS WERE NOT |
| DATED. |
| |
| 4) NOTE: PLEASE SEE THE EQUIPMENT AS SUBMITTED AND |
| SHOWN ON PLANS DO NOT INDICATE ANY LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY. NRTL. |
| PLEASE SEE 110.3, 90.7 |
| PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| REVIEW. |
| THIS IS FOR EQUIPMENT ON A-2.3 |
| |
| 5) NOTE: PLEASE BE SURE TO PROVIDE ELECTRICAL |
| INFORMATION FOR EQUIPMENT ON SHEETS FOR VOLTAGE |
| CONNECTIONS. |
| PANEL IS BEING NOTED AS 277/480V AND UNTIL MANUFACTURES |
| SPECS/CUT SHEETS CAN BE REVIEWED SIZING OF CIRCUITS, |
| LOADS ETC CAN NOT BE CONFIRMED. |
| ELECTRICAL PLANS DO NOT INDICATE SIZE OF CIRCUITS, OVER |
| CURRENT PROTECTION, CONDUCTOR ETC.240.4, 310.16 ETC |
| PLAN SHEET A-1.1 SHOWS ONE NEW RECEPTACLE BEING |
| INSTALLED WHICH DOES NOT SEEM TO BE WHAT IS NEEDED |
| BASED ON EQUIPMENT AS SHOWN. IS THIS A 277/480V |
| RECEPTACLE? PLEASE SPECIFY TYPE. (NEMA RATING/NUMBER). |
| ELECTRICAL PANEL SCHEDULE DOES NOT SHOW THE NEW |
| CIRCUIT(S). 408.4 |
| FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| |
| |
| |
| ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| PLANS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |