2008-12-19 10:19:45 | DENIED |
| REFERENCE: |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHT P2.1 THE REVISIONS ON FILE FOR PUBLIC RECORD |
| SHOW REVISIONS 07/25/07, 1, 3, 11/12/07, 4, 5, 6, |
| REVISION 7 (DATED 4/7/08), 4/29/08, 5/22/08 & 9 DATED |
| 5/30/08 BUT THE SHEET SUBMITTED FOR REVISION HAS |
| DELETED THE REVISION NUMBERS 7 & 9 FROM THE REVISION |
| INDEX AND ADDED 2 REVISION DATED 6/19/08 & 10/20/08 |
| (INDICATED AS #SK-P1 BUT NOT FOUND). IN ORDER TO REVIEW |
| THE REVISIONS, EACH REVISION AFTER REVISION 7 SHALL BE |
| INDICATED WITH A REVISION NUMBER AND EACH REVISION |
| SHALL BE CLOUDED ON THE FLOOR PLAN AND A REVISION |
| NUMBER INDICATED ON EACH CLOUDED REVISION. REVISION 7 |
| NUMBER SHALL BE INDICATED ON THE REVISION INDEX FOR |
| DATE 4/7/08. SECTION 106.1.3. |
| FBC-2004 106.1.3 QUALITY OF BUILDING PLANS. |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| |
| 2. SHT P2.1 THE GAS PIPING IS INCORRECT FOR THE 3/4" |
| PIPE WITH 68 CFH. PER TABLE 402.4(1) 1" PIPE IS |
| REQUIRED. -- THE GAS PIPING IS INCORRECT FOR THE 1 PIPE |
| WITH 106 CFH. PER TABLE 402.4(1) 1-1/4" IS REQUIRED. |
| THIS IS FOR THE GAS PIPING CHANGED AT THE PATIO |
| HEATERS. |
| |
| 3. SHT P3.1 THE REVISIONS ON FILE FOR PUBLIC RECORD |
| SHOW REVISIONS 07/25/07, 1, 3, 11/12/07, 4, 5, 6 & |
| REVISION 7 (DATED 4/7/08, BUT THE SHEET SUBMITTED FOR |
| REVISION HAS DELETED THE REVISION NUMBER 7 FROM THE |
| REVISION INDEX AND ADDED 5 REVISIONS DATED 4/29/08, |
| 5/22/08, 5/30/08, 6/19/08 & 10/20/08 (INDICATED AS |
| #SK-P1 BUT NOT FOUND). IN ORDER TO REVIEW THE |
| REVISIONS, EACH REVISION AFTER REVISION 7 SHALL BE |
| INDICATED WITH A REVISION NUMBER AND EACH REVISION |
| SHALL BE CLOUDED ON THE FLOOR PLAN AND A REVISION |
| NUMBER INDICATED ON EACH CLOUDED REVISION. REVISION 7 |
| NUMBER SHALL BE INDICATED ON THE REVISION INDEX FOR |
| DATE 4/7/08. SECTION 106.1.3. |
| FBC-2004 106.1.3 QUALITY OF BUILDING PLANS. |
| BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| |
| 4. SHT P3.1 SHT P2.1 THE GAS PIPING IS INCORRECT FOR |
| THE 3/4" PIPE WITH 68 CFH. PER TABLE 402.4(1) 1" PIPE |
| IS REQUIRED. -- THE GAS PIPING IS INCORRECT FOR THE 1 |
| PIPE WITH 106 CFH. PER TABLE 402.4(1) 1-1/4" IS |
| REQUIRED. THIS IS FOR THE GAS PIPING CHANGED AT THE |
| PATIO HEATERS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |