Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop B
Sequence Number 4
Notes
Date Text
2008-04-28 11:18:534-25-08
 COMMENT 1F)IN REVIEWING THIS COMMENT WITH THE
 BUILDING OFFICIAL, NEIL HAS DIRECTED THAT THIS COMMENT
 IS IRRELEVENT AND NOT BE INCLUDED IN THIS REVIEW. THE
 CBC WOULD BE ABLE TO HAVE THE CGC AS A SUB-CONTRACTOR
 AND THE ENGINEERING FIRM COULD CONTRACT WITH THE CBC .
2008-04-21 13:15:05BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1A)NOTE, INFORMATIONAL, WHEN RESUBMITTING PLANS
 PLEASE INDICATE THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) NOTE INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) NOTE INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D )NOTE INFORMATIONAL, FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION. 2)SHEET T1.1,CODE ANALYSIS PLEASE UPDATE
 THE 2004 TO THE 2007 FBC, BUILDING WITH 2007
 REVISIONS.
  
 1E) PARTIALLY COMPLIED, THEEXTERIOR WORK THAT COULD
 NOT BE COMPLETED UNDER A CBC LICENSE DOES NOT ONLY
 APPLY TO THE CANOPY BUT THE EXTERIOR GLAZING AND DOOR
 SYSTEMS SINCE THE PRESSURES ASSOCIATED WITH THE DOOR
 AND WINDOW SYSTEM DO EFFECT THE STRUCTURAL INTEGRITY OF
 THE BUILDING. THE CGC WOULD ALSO NEED TO INCORPORATE
 THE INSTALLATION OF THE EXTERIOR COMPONENTS UNDER THE
 CGC LICENSURE. PLEASE ADD THIS WORK TO THE PERMIT
 APPLICATION UNDER THE DESCRIPTION OF PROJECT.
  
 1F)THE SECOND LICENSING ISSUE IS THE WINGERTER
 LABORTIES THAT WILL BE COMPLETING THE THRESHOLD
 INSPECTIONS WILL NEED TO CONTRACT THROUGH THE CGC, NOT
 THE CBC, PLEASE CHANGE OUT THE WINGERTER LABORATORIES
 COVER SHEET,(3) COPIES OF RAISED SIGNED AND SEALED
 COVER SHEETS, THE MENTION OF IN MOTION BUILDERS SHOULD
 TRUELY REFLECT THE NEW CGC AND IT WOULD BE WITHIN THE
 CGC'S LICENSE SCOPE OF WORK.
  
 2-9) COMPLIED.
  
 10-16) COMPLIED.
 17) ***FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES (FOR THRESHOLD BUILDINGS (3 COPIES) OF
 PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
  
 17A-G) COMPLIED.
  
 17H) ROOFING ASSEMBLIES W / INSULATION,NONE OF THE
 SUB-SYSTEMS WERE HIGHLIGHTED INDICATING WHICH SYSTEM
 WAS TO BE INSTALLED. 2ND ISSUE ISALL SUB-SYSTEMS WILL
 REQUIRE RAS 117 CALCULATIONS FOR THE REQUIRED ENHANCED
 FASTENING, PLEASE PROVIDE 3 COPIES OF THE ENHANCED
 FASTENING SCHEDULE FOR ZONES 2 & 3. TABLE 1609.2.1(2) *
 TABLE 1609.2.1(4). TO BE REVIEWED BY CAPRI THEN
 SUBMITTED TO THE CITY.
  
 18-19) COMPLIED.
  
 20) COMPLIED.
  
 21-22) COMPLIED.
  
 23) THIS COMMENT DIDN'T APPEAR ON THE COMMENT RESPONCE
 SHEET, SHEET A6.3 PLEASE PROVIDE PRODUCT INFORMATION ON
 THE STUCCO TAPE TO BE USED ON STC-1 WALLS? ADDITIONAL
 INFORMATION REQUIRED.
  
 24) BUILDING PROVISO:A6.4 DETAIL # 2 & S5.0 FOR A
 BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP
 DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE
 DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE
 140 MPH PROVISIONS OF 1609.6.2.1(2) & 1609.2.1(4) THIS
 CAN BE SUBMITTED FOR REVIEW TO CAPRIFOR REVIEW THEN
 TO WPB CONSTRUCTION SEERVICES DEPARTMENT.
  
 25)COMPLIED.
  
 26-27) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.