2008-04-28 11:18:53 | 4-25-08 |
| COMMENT 1F)IN REVIEWING THIS COMMENT WITH THE |
| BUILDING OFFICIAL, NEIL HAS DIRECTED THAT THIS COMMENT |
| IS IRRELEVENT AND NOT BE INCLUDED IN THIS REVIEW. THE |
| CBC WOULD BE ABLE TO HAVE THE CGC AS A SUB-CONTRACTOR |
| AND THE ENGINEERING FIRM COULD CONTRACT WITH THE CBC . |
2008-04-21 13:15:05 | BUILDING PLAN REVIEW |
| PERMIT: 07090648 |
| ADD: 700 S ROSEMARY AVE# 100 |
| CONT: IN MOTION BUILDERS, INC. |
| TEL: (954)698-0900 |
| MARCH 18/2008 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RDREVIEW |
| ACTION: DENIED |
| |
| 1A)NOTE, INFORMATIONAL, WHEN RESUBMITTING PLANS |
| PLEASE INDICATE THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| 1B) NOTE INFORMATIONAL, PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C) NOTE INFORMATIONAL, 106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D )NOTE INFORMATIONAL, FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. 2)SHEET T1.1,CODE ANALYSIS PLEASE UPDATE |
| THE 2004 TO THE 2007 FBC, BUILDING WITH 2007 |
| REVISIONS. |
| |
| 1E) PARTIALLY COMPLIED, THEEXTERIOR WORK THAT COULD |
| NOT BE COMPLETED UNDER A CBC LICENSE DOES NOT ONLY |
| APPLY TO THE CANOPY BUT THE EXTERIOR GLAZING AND DOOR |
| SYSTEMS SINCE THE PRESSURES ASSOCIATED WITH THE DOOR |
| AND WINDOW SYSTEM DO EFFECT THE STRUCTURAL INTEGRITY OF |
| THE BUILDING. THE CGC WOULD ALSO NEED TO INCORPORATE |
| THE INSTALLATION OF THE EXTERIOR COMPONENTS UNDER THE |
| CGC LICENSURE. PLEASE ADD THIS WORK TO THE PERMIT |
| APPLICATION UNDER THE DESCRIPTION OF PROJECT. |
| |
| 1F)THE SECOND LICENSING ISSUE IS THE WINGERTER |
| LABORTIES THAT WILL BE COMPLETING THE THRESHOLD |
| INSPECTIONS WILL NEED TO CONTRACT THROUGH THE CGC, NOT |
| THE CBC, PLEASE CHANGE OUT THE WINGERTER LABORATORIES |
| COVER SHEET,(3) COPIES OF RAISED SIGNED AND SEALED |
| COVER SHEETS, THE MENTION OF IN MOTION BUILDERS SHOULD |
| TRUELY REFLECT THE NEW CGC AND IT WOULD BE WITHIN THE |
| CGC'S LICENSE SCOPE OF WORK. |
| |
| 2-9) COMPLIED. |
| |
| 10-16) COMPLIED. |
| 17) ***FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES (FOR THRESHOLD BUILDINGS (3 COPIES) OF |
| PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| FOLLOWS: |
| |
| 17A-G) COMPLIED. |
| |
| 17H) ROOFING ASSEMBLIES W / INSULATION,NONE OF THE |
| SUB-SYSTEMS WERE HIGHLIGHTED INDICATING WHICH SYSTEM |
| WAS TO BE INSTALLED. 2ND ISSUE ISALL SUB-SYSTEMS WILL |
| REQUIRE RAS 117 CALCULATIONS FOR THE REQUIRED ENHANCED |
| FASTENING, PLEASE PROVIDE 3 COPIES OF THE ENHANCED |
| FASTENING SCHEDULE FOR ZONES 2 & 3. TABLE 1609.2.1(2) * |
| TABLE 1609.2.1(4). TO BE REVIEWED BY CAPRI THEN |
| SUBMITTED TO THE CITY. |
| |
| 18-19) COMPLIED. |
| |
| 20) COMPLIED. |
| |
| 21-22) COMPLIED. |
| |
| 23) THIS COMMENT DIDN'T APPEAR ON THE COMMENT RESPONCE |
| SHEET, SHEET A6.3 PLEASE PROVIDE PRODUCT INFORMATION ON |
| THE STUCCO TAPE TO BE USED ON STC-1 WALLS? ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 24) BUILDING PROVISO:A6.4 DETAIL # 2 & S5.0 FOR A |
| BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP |
| DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE |
| DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE |
| 140 MPH PROVISIONS OF 1609.6.2.1(2) & 1609.2.1(4) THIS |
| CAN BE SUBMITTED FOR REVIEW TO CAPRIFOR REVIEW THEN |
| TO WPB CONSTRUCTION SEERVICES DEPARTMENT. |
| |
| 25)COMPLIED. |
| |
| 26-27) COMPLIED. |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |