2008-03-08 10:48:55 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| MUNICIPAL CODES WPB |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| ******FROM PREVIOUS REVIEWS: (3RD REVIEW) |
| |
| 1. OK |
| 2. OK |
| |
| 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED |
| INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED |
| NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN |
| SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL |
| SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED, |
| SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE |
| LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC |
| 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219, |
| 481.2055. |
| ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED |
| LETTER HAS NOT BEEN SUBMITTED AS REQUESTED. |
| ******RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED |
| LETTER HAS NOT BEEN SUBMITTED AS REQUESTED. |
| |
| |
| 4. OK |
| 5. OK |
| 6. OK |
| |
| 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE |
| REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION |
| 611.1. |
| ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR |
| THE WATER FILTER HAVE NOT BEEN FOUND. ******RESPONSE |
| NOTED, BUT THE MANUF. SPECIFICATIONS FOR THE WATER |
| FILTER DO NOT SHOW COMPLIANCE/CERTIFICATION FOR NSF-42. |
| THE REQUIREMENTS FOR NSF-42 ARE A REQUIREMENT FOR |
| REDUCTION OF CHLORINE, TASTE & ODOR, CHLORAMINE, ZINC |
| ETC AS WELL AS BACTERIOSTATIC EFFECTS. NSF-53 IS NOT |
| SHOWN TO COMPLY WITH THE REQUIREMENTS OF NSF-42. A |
| SEPARATE FILTER CAN BE ADDED TO THE SYSTEM TO COMPLY |
| WITH THE REQUIREMENTS OF SECTION 611.1 |
| |
| 8. OK |
| 9. OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| 14. OK |
| 15. OK |
| 16. OK |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| 21. OK |
| |
| 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED: |
| |
| A. OK |
| B. OK |
| C. OK |
| D. OK |
| E. OK |
| F. OK |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS |
| FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE |
| RH UNITS. |
| ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT |
| SUBMITTED. |
| ******RESPONSE NOTED, BUT THE RICE COOKER IS NOT LISTED |
| AS BEING TESTED FOR THE GAS COMPONETS. THE ONLY LISTING |
| SHOWN IS FOR NSF. PER SECTION 301.3. PLEASE SHOW |
| LISTING. |
| |
| H. OK |
| 23. OK |
| |
| 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE |
| DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED |
| ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE |
| NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE |
| FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY |
| HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS |
| NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE |
| CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE |
| RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4. |
| ******RESPONSE NOTED, BUT THE VENT FOR THE FLOOR SINK |
| INDICATED IN COMMENT ABOVE DOES NOT COMPLY WITH CODE |
| SECTION 905.4. FLOOR SINK CAN BE CONNECTED ON THE RISE |
| OF THE VENT TO WASH THE BASE OF THE VENT. |
| |
| 25. OK |
| 26. OK |
| 27. OK |
| 28. OK |
| |
| **********NEW COMMENTS********** |
| |
| 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE |
| OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS |
| 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND |
| APPLICATION FOR PERMIT. |
| ******RESPONSE NOTED, BUT THE LETTER HAS NOT BEEN |
| SUBMITTED. |
| |
| 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| NOTICE ONLY AT THIS TIME. |
| |
| **********NEW COMMENTS********** |
| |
| 1C. THE GAS SYSTEM IS NOW INDICATED AS A 2PSI SYSTEM. |
| REGULATORS ARE REQUIRED IN THE SYSTEM TO REDUCE THE |
| PRESSURE FROM 2PSI TO .5 PSI PRIOR TO EACH APPLIANCE OR |
| GROUP OF APPLIANCES. A SHUT OFF VALVE IS REQUIRED |
| UPSTREAM OF EACH REGULATOR WITH A UNION DOWNSTREAM OF |
| THE SHUT OFF VALVE. SECTION 409.4. (SHUT OFF VALVES, |
| REGULATORS & UNIONS CAN NOT BE LOCATION IN THE |
| CEILING). |
| |
| 2C. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS |
| REGULATORS. IF THERE ARE VENT LINES ON THE REGULATORS, |
| INDICATE MATERIAL FOR VENTS. (NO COMBUSTABLE MATERIALS |
| FOR THE VENTS). SHOW ROUTING AND TERMINATION OF VENTS |
| IF INSTALLED/REQUIRED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE |
| VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON. |
| |
| REVIEW BY KEN STEVENS |