Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop P
Sequence Number 3
Notes
Date Text
2008-03-08 10:48:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: (3RD REVIEW)
  
 1. OK
 2. OK
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
 ******RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
  
  
 4. OK
 5. OK
 6. OK
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE WATER FILTER HAVE NOT BEEN FOUND. ******RESPONSE
 NOTED, BUT THE MANUF. SPECIFICATIONS FOR THE WATER
 FILTER DO NOT SHOW COMPLIANCE/CERTIFICATION FOR NSF-42.
 THE REQUIREMENTS FOR NSF-42 ARE A REQUIREMENT FOR
 REDUCTION OF CHLORINE, TASTE & ODOR, CHLORAMINE, ZINC
 ETC AS WELL AS BACTERIOSTATIC EFFECTS. NSF-53 IS NOT
 SHOWN TO COMPLY WITH THE REQUIREMENTS OF NSF-42. A
 SEPARATE FILTER CAN BE ADDED TO THE SYSTEM TO COMPLY
 WITH THE REQUIREMENTS OF SECTION 611.1
  
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS
 FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE
 RH UNITS.
 ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT
 SUBMITTED.
 ******RESPONSE NOTED, BUT THE RICE COOKER IS NOT LISTED
 AS BEING TESTED FOR THE GAS COMPONETS. THE ONLY LISTING
 SHOWN IS FOR NSF. PER SECTION 301.3. PLEASE SHOW
 LISTING.
  
 H. OK
 23. OK
  
 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE
 DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED
 ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE
 NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY
 HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS
 NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE
 CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4.
 ******RESPONSE NOTED, BUT THE VENT FOR THE FLOOR SINK
 INDICATED IN COMMENT ABOVE DOES NOT COMPLY WITH CODE
 SECTION 905.4. FLOOR SINK CAN BE CONNECTED ON THE RISE
 OF THE VENT TO WASH THE BASE OF THE VENT.
  
 25. OK
 26. OK
 27. OK
 28. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE
 OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS
 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND
 APPLICATION FOR PERMIT.
 ******RESPONSE NOTED, BUT THE LETTER HAS NOT BEEN
 SUBMITTED.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 **********NEW COMMENTS**********
  
 1C. THE GAS SYSTEM IS NOW INDICATED AS A 2PSI SYSTEM.
 REGULATORS ARE REQUIRED IN THE SYSTEM TO REDUCE THE
 PRESSURE FROM 2PSI TO .5 PSI PRIOR TO EACH APPLIANCE OR
 GROUP OF APPLIANCES. A SHUT OFF VALVE IS REQUIRED
 UPSTREAM OF EACH REGULATOR WITH A UNION DOWNSTREAM OF
 THE SHUT OFF VALVE. SECTION 409.4. (SHUT OFF VALVES,
 REGULATORS & UNIONS CAN NOT BE LOCATION IN THE
 CEILING).
  
 2C. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS
 REGULATORS. IF THERE ARE VENT LINES ON THE REGULATORS,
 INDICATE MATERIAL FOR VENTS. (NO COMBUSTABLE MATERIALS
 FOR THE VENTS). SHOW ROUTING AND TERMINATION OF VENTS
 IF INSTALLED/REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE
 VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]