Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2008-03-19 17:05:58*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 06.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE ENTRY
 CANOPY.
  
 07.A DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL
 BE SELF-CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH
 7.2.1.8.2 OF NFPA 101.
  
 09.SPECIFY INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH
 MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL
 ASSEMBLY AREA HAVING AN OCCUPANT LOADS OF MORE THAN
 300.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE APPROPIATE PLAN SHEET
 OR IN THE SPECIFICATIONS) EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW