Date |
Text |
2008-03-12 18:06:53 | ** DENIED 3RD REVIEW ** |
| |
| ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE |
| STILL IN NEED OF ADDRESSING.EXAMPLES WERE GIVEN ON |
| PREVIOUS REVIEW HOWEVER NOT ALL ITEMS AS MENTIONED. |
| PLEASE SEE SOME EXAMPLES ARE GIVEN ONCE AGAIN. |
| |
| ** PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON |
| DOCUMENTS SUBMITTED AND/OR CHANGES MADE TO PLANS OR |
| DOCUMENTS SUBMITTED. REVIEW COMMENTS CAN ONLY BE MADE |
| ON PLANS AND DOCUMENTS REVIEWED. |
| IN EITHER CASE THE COMMENTS NEED TO BE ADDRESSED. |
| |
| 1) NOTE: PLEASE SEE THE PLANS STILL SHOW A PERMANENT |
| STRUCTURE FOR OUTSIDE EATING ON THE WEST SIDE WHICH BY |
| GOING OVER WITH ERIC SCHNEIDER FROM ZONING, THIS |
| STRUCTURE MAY NOT BE BUILT AS SHOWN. THIS WILL AFFECT |
| ALMOST ALL DOCUMENTS AND PLANS INCLUDING ARCHITECTURAL, |
| ELECTRICAL, AND PERFORMANCE CALCULATIONS. |
| |
| 2) NOTE: PLEASE SEE SUBMITTED PLANS AND ALL DOCUMENTS |
| WERE GONE THROUGH AND AS NOTED ON PREVIOUS REVIEW |
| COMMENT #1, THE OWNER AFFIDAVIT WAS NOT SUBMITTED IN |
| PACKAGE. |
| PLEASE SEE FS 553.791(4)( C) |
| |
| 3) NOTE: PLEASE SEE ONE SHEET OF THE PRIVATE PROVIDER |
| BUILDING COMPLIANCE FOR MECHANICAL CONTAINS A NOTARY |
| STAMP AND SIGNATURE OF THIS SHEET HOWEVER THE SHEET |
| WHICH IS REQUIRED TO BE SIGNED BY THE REVIEWER IS NOT |
| SIGNED AND IS BLANK? |
| PLEASE SEE FS 553.791 AS THIS IS REQUIRED TO BE SIGNED |
| BY THE PLANS EXAMINER AND A NOTARY UNDER FS 117.05 MAY |
| NOT NOTARIZE A BLANK PAGE WHERE A SIGNATURE IS |
| REQUIRED. |
| |
| 4) NOTE: PLEASE SEE RESPONSE FROM THE DESIGNER FOR |
| SIGNATURE MENTIONS THE TOP SIGNATURE IS THE ONE TO USE |
| HOWEVER LETTER IS SIGNED WITH ANOTHER SIGNATURE ALL |
| TOGETHER.THE LETTER MAY NOT LIST MULTIPLE SIGNATURES |
| AND NEEDS TO STATE THIS IS THE LEGAL SIGNATURE. THE |
| LETTER WILL BE PLACED IN SIGNATURE FILE. |
| FS 471.025 |
| |
| 5) NOTE: PLEASE SEE COMMENTS BELOW WITH RESPECT TO |
| ARCHITECTURAL PLANS FOR LIGHTING AND ELECTRICAL PLANS |
| FOR LIGHTING WHICH DO NOT CORRELATE. PLEASE SEE SHEET |
| A2.2 SPECIFICALLY WHICH DOES NOT SHOW THE REVISED |
| LIGHTING FOR EMERGENCY LIGHTS, EXIT LIGHTS WHICH MANY |
| WERE ADDED AND SOME WERE REMOVED OR RELOCATED. ONE |
| EXAMPLE GIVEN: SEE THE AREA IN KITCHEN JUST TO THE LEFT |
| OF THE LIQUOR STORAGE ROOM #121 WHICH ON ELECTRICAL |
| PLANS THE EXIT LIGHT WAS REMOVED. |
| PLEASE SEE THE NEW UPDATED ARCHITECTURAL SHEETS NOW |
| CONTAIN COMPLETELY DIFFERENT SIGNATURES THAN THE |
| PREVIOUSLY SUBMITTED PLANS? |
| PLEASE SEE THE PRINTED LICENSE NUMBER OF THE ARCHITECT |
| WHICH MAY SIMPLY BE ADDED TO TITLE BLOCKS ON ANY SHEETS |
| WHICH DO NOT NEED TO BE RE-PRINTED. THIS IS GIVEN AS A |
| NEW COMMENT DUE TO THE A-SHEETS NOT CORRELATING WITH |
| ELECTRICAL. THIS WAS A COMMENT FROM OTHER TRADES ON |
| PREVIOUS REVIEW(S) AND IS GIVEN FOR INFORMATION AND IS |
| REQUIRED EVEN IF COMMENT IS NOT MADE BY OTHER |
| TRADE(S). |
| |
| 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| EGRESS LIGHTING REQUIRED TO MEET MINIMUM LEVELS PER THE |
| LIFE SAFETY CODE. 7.8 AND 7.9. THE RESPONSE MENTIONS |
| THIS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR AND |
| WILL NEED TO PERFORM READINGS OF LIGHTING LEVELS AT THE |
| END OF THE PROJECT. THIS IS NOT ACCEPTABLE AS THIS IS |
| NOT THE RESPONSIBILITY OF THE CONTRACTOR AND IS THE |
| RESPONSIBILITY OF THE DESIGN PROFESSIONAL. PLEASE SEE |
| FLORIDA ADMINISTRATIVE CODE 61G15-33.004 WITH RESPECT |
| TO MINIMUM RESPONSIBILITIES OF THE ENGINEER. |
| IF THE LIGHTING IN AREAS OF CONCERNS WERE NOT ON |
| DIMMING PANELS AND ALL A PART OF NORMAL LIGHTING AS |
| SHOWN ON PLANS THIS WOULD NOT BE OF CONCERN. THEFACT |
| THAT THE PLANS CONTAINS LIGHTING ON DIMMING PANELS AND |
| THERE IS NO INFORMATION ON A STARTING LIGHTING LEVEL |
| POINT AND NO INFORMATION ON THE MINIMUM LEVEL IN WHICH |
| EGRESS LIGHTING IN ALL PATHS WILL BE DIMMED TO, THIS |
| SHALL BE ADDRESSED AT THIS TIME. |
| PLEASE PROVIDE INFORMATION ON LEVELS, DIMMING ETC. |
| PLEASE SEE7.8.1.3, 7.8.1.4 WHICH REQUIRES 1FT CANDLE |
| MINIMUM NO DESIGNATED AREA TO FALL BELOW 2.2 LUX OR .02 |
| FT CANDLES WITH THE FAILURE OF ANY ONE UNIT. PLEASE SEE |
| SOUTHEAST CORNER OF DINING AREA FOR ONE EXAMPLE AS THE |
| LEVELS SHOWN ON PHOTO-METRIC PLANS FOR THAT AREA ARE |
| ALREADY LOW AND APPEARS IT WILL FALL BELOW MINIMUM AS |
| ONLY ONE UNIT IS SHOWN ON PLANS FOR THAT AREA. |
| |
| 7) NOTE: PLEASE SEE RESPONSE TO PREVIOUS REVIEW NOTE |
| WHICH MENTIONED VERSION 3.0 OF FLA-COMM COULD NOT BE |
| USED WAS AS FOLLOWS AND IS QUOTED FROM DESIGNER'S |
| RESPONSE: |
| * |
| BUILDING OFFICIALS: ENERGY GAUGE SUMMIT VERSION 3.0 AND |
| 3.1 SATISFIES THE REQUIREMENTS IN 13-400.3.A AND |
| 13-400.3.B (GENERATED BY FLA/COM-2004 COMPUTER PROGRAM, |
| VERSION 2.5).* |
| * |
| PLEASE SEE THIS IS EXACTLY THE WORDING ON THE STATE |
| WEBSITE. PLEASE READ WHAT THE STATEMENT SAYS, THE |
| VERSION 3.0 AND 3.1 *ENERGY GAUGE SUMMIT* GENERATED BY |
| THE FLA/COM 2004 COMPUTER PROGRAM, * VERSION 2.5*. |
| THESE MEANS IT IS STILL THE VERSION 2.5 AS TITLED IN |
| PROGRAM AND YOU WILL SEE THE ENERGY GAUGE SUMMIT 3.0 OR |
| 3.1 ON THE LAST LINE OF SHEET. |
| NOW THE SUBMITTED CALCULATIONS DO SHOW THE 2.5 HOWEVER |
| SAYS ENERGY GAUGE SUMMIT 3.14. |
| THE MECHANICAL REVIEW STATED IN THE PREVIOUS REVIEW |
| THAT METHOD *B* WAS NOT AN OPTION FOR MECHANICAL REVIEW |
| AND TO ADDRESS NOTE #17. |
| PLEASE SEE THE PREVIOUS ELECTRICAL REVIEWS GAVE |
| SECTIONS 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR |
| PRESCRIPTIVE REQUIREMENTS. |
| PLEASE SEE THAT NOT ALL LIGHTING ON PLANS COORDINATE |
| WITH THE LIGHTING ON FIXTURE SCHEDULE ALONG WITH |
| LIGHTING IN THE INPUT DATA REPORT. |
| EXAMPLE: WOMEN AND MEN BATH ROOMS, DIMMING PANELS |
| CLEARLY SHOW VANITY LIGHTING IN THESE AREAS YET NOT IN |
| THE IDR. |
| EXAMPLE: MECHANICAL ROOM WHICH IS NOTED AS ROOM 129 ON |
| PLANS WHICH IS BEING ASSUMED AS THE ROOM WHICH IS |
| LABELED AS STORAGE ON IDR. |
| EXAMPLE: FIXTURE U, WHICH FIXTURE LEGEND STATES 75W |
| TRANSFORMER MONO-POINT USE. |
| EXAMPLE: UMBRELLA LIGHTS ON DIMMING PANEL CIRCUIT 24. |
| WHAT ARE THESE FIXTURES, WHERE ARE THEY IN THE IDR, HOW |
| ARE THEY FIGURED? |
| THESE CALCULATIONS MAY ONLY BE FOR ELECTRICAL LIGHTING |
| AND MAY NOT TRADE OFF ANY OTHER ITEMS SUCH AS BUILDING |
| SYSTEMS ETC. |
| THIS SECTION13-101.1.3 APPLIES TO RENOVATIONS WHICH |
| THIS DOES NOT FALL UNDER AND ONLY 13-415.2 APPLIES AND |
| ITS ADOPTED SECTIONS THERETO. |
| PLEASE EXPLAIN HOW THE EFFECTIVE WATTAGE IS LESS THAN |
| DESIGN AND DESIGN IS HIGHER THAN THE ALLOWANCE. PLEASE |
| EXPLAIN HOW THE DESIGN WATTAGE ON COMPLIANCE SUMMARY |
| SHEET IS NOT THE SAME AS DESIGN WATTAGE ON LIGHTING |
| COMPLIANCE SHEET. |
| PLEASE SEE SECTION ABOVE AS THIS IS NOT A TRADE OFF FOR |
| OTHER COMPONENTS. |
| ** AS NOTED ON PREVIOUS REVIEW, PLEASE GO OVER ALL |
| LIGHTING ON PLANS, PLEASE BE SURE THE SPECIFIC |
| REQUIREMENTS OF 13-415.2.ABC.1.1, .1.2 AND .1.3 ARE |
| MET. |
| ** PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW |
| PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE |
| CERTIFICATION SHEETS. THIS DOES NOT MEAN THE NAME SHALL |
| BE TYPE WRITTEN ON SHEETS, THIS REQUIRES A SIGNATURE. |
| PLEASE BE SURE AS MENTIONED ON PREVIOUS REVIEW THE |
| CERTIFICATION SHEET CONTAINS THE SIGNATURE AND SEAL |
| FROM THE DESIGN PROFESSIONAL.13-103.1., FBC 106.1.2 |
| ADMIN SECTION. |
| |
| 8) NOTE: PLEASE SEE COMPLIANCE FOR 13-415.1.ABC.1.1, |
| .1.2 AND .1.3 HAVE NOT BEEN ACHIEVED FOR ALL LIGHTING |
| AS REQUIRED. |
| THERE ARE LOCATIONS ON PLANS WHICH STILL ONLY SHOW A |
| STANDARD METHOD OF CONTROL WHEN THE CODE REQUIRES |
| AUTOMATED SHUT OFF. SOME AREAS WERE GIVEN AS EXAMPLES |
| ON PREVIOUS REVIEW AND NOTED AS ALSO SEE OTHER AREAS. |
| PLEASE SEE PREVIOUS NOTE WITH RESPECT TO SOME OF THE |
| FIXTURES NOTED WHICH WERE NOT INCLUDED IN THE IDR. ONE |
| FOR EXAMPLE WAS FIXTURE *P* WHICH WAS GIVEN. PLEASE SEE |
| HOST AREA WHICH SHOWS FIXTURE *P* ABOVE ARE WHICH |
| CONTAINS A STANDARD DIMMING SWITCH AND DOES NOT GO TO |
| ANY CIRCUITING, CONTROLS, DIMMING PANEL ETC? THE PLANS |
| DO CONTAIN NOTES #9 AND #10 HOWEVER THEY MENTION TO SEE |
| E2.1 FOR CONTINUATION HOWEVER 2.1 DOES NOT PROVIDE ANY |
| CONTROL OR CIRCUITING INFORMATION. PLEASE EXPLAIN AND |
| SHOW HOW THE OCCUPANT CAN SEE ALL LIGHTING WHICH IS |
| BEING CONTROLLED AS THIS PROPOSED CONTROL IS AT ONE |
| LOCATION. HOW WILL SYSTEM MEET IDENTIFICATION AND PILOT |
| LIGHTS REQUIRED? |
| PLEASE SEE BAR RELAY PANEL MENTIONS THIS BEING A RELAY |
| PANEL HOWEVER THE CIRCUITS IN THIS PANEL ARE SHOWN FROM |
| PANEL L1 AND NO OVER RIDES OR TIMES COULD BE FOUND. |
| EXAMPLE: PLEASE SEE PLANS STILL INDICATE LIGHTING IN |
| MEN'S AND WOMEN'S BATHROOM WITH NO SEPARATE SPACE OVER |
| RIDE CONTROLS. SOME LIGHTING WAS NOW PLACED ON |
| OCCUPANCY SENSORS HOWEVER SEE DIMMING PANEL WHICH STILL |
| LIST LIGHTS IN BOTH OF THESE LOCATIONS. |
| ** PLEASE VERIFY LISTING OF MARLIN PANELS AND MATRIX |
| CONTROLLERS. AS THE SYSTEM ON PLANS WAS NOT COMPLETE |
| SOME RESEARCH OF SYSTEM COMPONENTS WAS DONE AND EVEN AS |
| EACH MAY BE LISTED, COULD NOT LOCATE THESE AS A LISTED |
| ASSEMBLY OR SYSTEM. PLEASE PROVIDE TECHNICAL SPECS/CUT |
| SHEETS FOR THIS PER 110.3, 90.7. THESE ARE NOW BEING |
| REQUESTED AS THE INFORMATION FOR LABELING, PILOT LIGHTS |
| ETC HAS NOT BEEN CLEAR ALONG WITH CONTROLS. |
| |
| 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT |
| TO TRACK LIGHTING LOADS AND HOW THEY WERE FIGURED INTO |
| SERVICE PER 220.43B. THE DIMMING PANELS NOW SHOW THE VA |
| PER TWO FT HOWEVER THE LOADS ARE STILL SHOWN AT 1.0 |
| FACTOR. ARE THESE NOT CONTINUOUS LOADS? |
| 125%, 215.3, 230.42 ETC PLEASE ADJUST. |
| |
| 10) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO |
| FLORIDA STATUES 553.80(2)(B) WITH RESPECT TO REPEAT |
| COMMENTS FOR CODE COMPLIANCE. AT THIS TIME AS REQUIRED |
| UNDER FLORIDA STATUTES, THIS OFFICE HAS ASSESSED THE |
| FEE AS REQUIRED WHICH IS REQUIRED TO BE PAID BEFORE THE |
| PLANS MAY BE RESUBMITTED. PLEASE BE SURE TO GO OVER |
| COMMENTS, IF THERE ARE ANY QUESTIONS PLEASE CONTACT |
| THIS OFFICE/REVIEWER TO GO OVER COMMENTS. |
| PLEASE SEE THE FEE OF $18, 600 WILL BE DUE UPON |
| RESUBMITTING OF PLANS. |
| ** ONE SET OF ELECTRICAL PLANS ALONG WITH ONE COPY OF |
| THE ENERGY CALCULATIONS SUBMITTED ARE BEING RETAINED BY |
| THIS OFFICE. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2008-03-11 19:37:58 | |
| |
| ** REVIEW WILL GO INTO A FAILED STATUS. NOTES TO FOLLOW |
| ONCE COMPLETED. |