Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop E
Sequence Number 3
Notes
Date Text
2008-03-12 18:06:53** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.EXAMPLES WERE GIVEN ON
 PREVIOUS REVIEW HOWEVER NOT ALL ITEMS AS MENTIONED.
 PLEASE SEE SOME EXAMPLES ARE GIVEN ONCE AGAIN.
  
 ** PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS BASED ON
 DOCUMENTS SUBMITTED AND/OR CHANGES MADE TO PLANS OR
 DOCUMENTS SUBMITTED. REVIEW COMMENTS CAN ONLY BE MADE
 ON PLANS AND DOCUMENTS REVIEWED.
 IN EITHER CASE THE COMMENTS NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE THE PLANS STILL SHOW A PERMANENT
 STRUCTURE FOR OUTSIDE EATING ON THE WEST SIDE WHICH BY
 GOING OVER WITH ERIC SCHNEIDER FROM ZONING, THIS
 STRUCTURE MAY NOT BE BUILT AS SHOWN. THIS WILL AFFECT
 ALMOST ALL DOCUMENTS AND PLANS INCLUDING ARCHITECTURAL,
 ELECTRICAL, AND PERFORMANCE CALCULATIONS.
  
 2) NOTE: PLEASE SEE SUBMITTED PLANS AND ALL DOCUMENTS
 WERE GONE THROUGH AND AS NOTED ON PREVIOUS REVIEW
 COMMENT #1, THE OWNER AFFIDAVIT WAS NOT SUBMITTED IN
 PACKAGE.
 PLEASE SEE FS 553.791(4)( C)
  
 3) NOTE: PLEASE SEE ONE SHEET OF THE PRIVATE PROVIDER
 BUILDING COMPLIANCE FOR MECHANICAL CONTAINS A NOTARY
 STAMP AND SIGNATURE OF THIS SHEET HOWEVER THE SHEET
 WHICH IS REQUIRED TO BE SIGNED BY THE REVIEWER IS NOT
 SIGNED AND IS BLANK?
 PLEASE SEE FS 553.791 AS THIS IS REQUIRED TO BE SIGNED
 BY THE PLANS EXAMINER AND A NOTARY UNDER FS 117.05 MAY
 NOT NOTARIZE A BLANK PAGE WHERE A SIGNATURE IS
 REQUIRED.
  
 4) NOTE: PLEASE SEE RESPONSE FROM THE DESIGNER FOR
 SIGNATURE MENTIONS THE TOP SIGNATURE IS THE ONE TO USE
 HOWEVER LETTER IS SIGNED WITH ANOTHER SIGNATURE ALL
 TOGETHER.THE LETTER MAY NOT LIST MULTIPLE SIGNATURES
 AND NEEDS TO STATE THIS IS THE LEGAL SIGNATURE. THE
 LETTER WILL BE PLACED IN SIGNATURE FILE.
 FS 471.025
  
 5) NOTE: PLEASE SEE COMMENTS BELOW WITH RESPECT TO
 ARCHITECTURAL PLANS FOR LIGHTING AND ELECTRICAL PLANS
 FOR LIGHTING WHICH DO NOT CORRELATE. PLEASE SEE SHEET
 A2.2 SPECIFICALLY WHICH DOES NOT SHOW THE REVISED
 LIGHTING FOR EMERGENCY LIGHTS, EXIT LIGHTS WHICH MANY
 WERE ADDED AND SOME WERE REMOVED OR RELOCATED. ONE
 EXAMPLE GIVEN: SEE THE AREA IN KITCHEN JUST TO THE LEFT
 OF THE LIQUOR STORAGE ROOM #121 WHICH ON ELECTRICAL
 PLANS THE EXIT LIGHT WAS REMOVED.
 PLEASE SEE THE NEW UPDATED ARCHITECTURAL SHEETS NOW
 CONTAIN COMPLETELY DIFFERENT SIGNATURES THAN THE
 PREVIOUSLY SUBMITTED PLANS?
 PLEASE SEE THE PRINTED LICENSE NUMBER OF THE ARCHITECT
 WHICH MAY SIMPLY BE ADDED TO TITLE BLOCKS ON ANY SHEETS
 WHICH DO NOT NEED TO BE RE-PRINTED. THIS IS GIVEN AS A
 NEW COMMENT DUE TO THE A-SHEETS NOT CORRELATING WITH
 ELECTRICAL. THIS WAS A COMMENT FROM OTHER TRADES ON
 PREVIOUS REVIEW(S) AND IS GIVEN FOR INFORMATION AND IS
 REQUIRED EVEN IF COMMENT IS NOT MADE BY OTHER
 TRADE(S).
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 EGRESS LIGHTING REQUIRED TO MEET MINIMUM LEVELS PER THE
 LIFE SAFETY CODE. 7.8 AND 7.9. THE RESPONSE MENTIONS
 THIS WILL BE THE RESPONSIBILITY OF THE CONTRACTOR AND
 WILL NEED TO PERFORM READINGS OF LIGHTING LEVELS AT THE
 END OF THE PROJECT. THIS IS NOT ACCEPTABLE AS THIS IS
 NOT THE RESPONSIBILITY OF THE CONTRACTOR AND IS THE
 RESPONSIBILITY OF THE DESIGN PROFESSIONAL. PLEASE SEE
 FLORIDA ADMINISTRATIVE CODE 61G15-33.004 WITH RESPECT
 TO MINIMUM RESPONSIBILITIES OF THE ENGINEER.
 IF THE LIGHTING IN AREAS OF CONCERNS WERE NOT ON
 DIMMING PANELS AND ALL A PART OF NORMAL LIGHTING AS
 SHOWN ON PLANS THIS WOULD NOT BE OF CONCERN. THEFACT
 THAT THE PLANS CONTAINS LIGHTING ON DIMMING PANELS AND
 THERE IS NO INFORMATION ON A STARTING LIGHTING LEVEL
 POINT AND NO INFORMATION ON THE MINIMUM LEVEL IN WHICH
 EGRESS LIGHTING IN ALL PATHS WILL BE DIMMED TO, THIS
 SHALL BE ADDRESSED AT THIS TIME.
 PLEASE PROVIDE INFORMATION ON LEVELS, DIMMING ETC.
 PLEASE SEE7.8.1.3, 7.8.1.4 WHICH REQUIRES 1FT CANDLE
 MINIMUM NO DESIGNATED AREA TO FALL BELOW 2.2 LUX OR .02
 FT CANDLES WITH THE FAILURE OF ANY ONE UNIT. PLEASE SEE
 SOUTHEAST CORNER OF DINING AREA FOR ONE EXAMPLE AS THE
 LEVELS SHOWN ON PHOTO-METRIC PLANS FOR THAT AREA ARE
 ALREADY LOW AND APPEARS IT WILL FALL BELOW MINIMUM AS
 ONLY ONE UNIT IS SHOWN ON PLANS FOR THAT AREA.
  
 7) NOTE: PLEASE SEE RESPONSE TO PREVIOUS REVIEW NOTE
 WHICH MENTIONED VERSION 3.0 OF FLA-COMM COULD NOT BE
 USED WAS AS FOLLOWS AND IS QUOTED FROM DESIGNER'S
 RESPONSE:
 *
 BUILDING OFFICIALS: ENERGY GAUGE SUMMIT VERSION 3.0 AND
 3.1 SATISFIES THE REQUIREMENTS IN 13-400.3.A AND
 13-400.3.B (GENERATED BY FLA/COM-2004 COMPUTER PROGRAM,
 VERSION 2.5).*
 *
 PLEASE SEE THIS IS EXACTLY THE WORDING ON THE STATE
 WEBSITE. PLEASE READ WHAT THE STATEMENT SAYS, THE
 VERSION 3.0 AND 3.1 *ENERGY GAUGE SUMMIT* GENERATED BY
 THE FLA/COM 2004 COMPUTER PROGRAM, * VERSION 2.5*.
 THESE MEANS IT IS STILL THE VERSION 2.5 AS TITLED IN
 PROGRAM AND YOU WILL SEE THE ENERGY GAUGE SUMMIT 3.0 OR
 3.1 ON THE LAST LINE OF SHEET.
 NOW THE SUBMITTED CALCULATIONS DO SHOW THE 2.5 HOWEVER
 SAYS ENERGY GAUGE SUMMIT 3.14.
 THE MECHANICAL REVIEW STATED IN THE PREVIOUS REVIEW
 THAT METHOD *B* WAS NOT AN OPTION FOR MECHANICAL REVIEW
 AND TO ADDRESS NOTE #17.
 PLEASE SEE THE PREVIOUS ELECTRICAL REVIEWS GAVE
 SECTIONS 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR
 PRESCRIPTIVE REQUIREMENTS.
 PLEASE SEE THAT NOT ALL LIGHTING ON PLANS COORDINATE
 WITH THE LIGHTING ON FIXTURE SCHEDULE ALONG WITH
 LIGHTING IN THE INPUT DATA REPORT.
 EXAMPLE: WOMEN AND MEN BATH ROOMS, DIMMING PANELS
 CLEARLY SHOW VANITY LIGHTING IN THESE AREAS YET NOT IN
 THE IDR.
 EXAMPLE: MECHANICAL ROOM WHICH IS NOTED AS ROOM 129 ON
 PLANS WHICH IS BEING ASSUMED AS THE ROOM WHICH IS
 LABELED AS STORAGE ON IDR.
 EXAMPLE: FIXTURE U, WHICH FIXTURE LEGEND STATES 75W
 TRANSFORMER MONO-POINT USE.
 EXAMPLE: UMBRELLA LIGHTS ON DIMMING PANEL CIRCUIT 24.
 WHAT ARE THESE FIXTURES, WHERE ARE THEY IN THE IDR, HOW
 ARE THEY FIGURED?
 THESE CALCULATIONS MAY ONLY BE FOR ELECTRICAL LIGHTING
 AND MAY NOT TRADE OFF ANY OTHER ITEMS SUCH AS BUILDING
 SYSTEMS ETC.
 THIS SECTION13-101.1.3 APPLIES TO RENOVATIONS WHICH
 THIS DOES NOT FALL UNDER AND ONLY 13-415.2 APPLIES AND
 ITS ADOPTED SECTIONS THERETO.
 PLEASE EXPLAIN HOW THE EFFECTIVE WATTAGE IS LESS THAN
 DESIGN AND DESIGN IS HIGHER THAN THE ALLOWANCE. PLEASE
 EXPLAIN HOW THE DESIGN WATTAGE ON COMPLIANCE SUMMARY
 SHEET IS NOT THE SAME AS DESIGN WATTAGE ON LIGHTING
 COMPLIANCE SHEET.
 PLEASE SEE SECTION ABOVE AS THIS IS NOT A TRADE OFF FOR
 OTHER COMPONENTS.
 ** AS NOTED ON PREVIOUS REVIEW, PLEASE GO OVER ALL
 LIGHTING ON PLANS, PLEASE BE SURE THE SPECIFIC
 REQUIREMENTS OF 13-415.2.ABC.1.1, .1.2 AND .1.3 ARE
 MET.
 ** PLEASE SEE AS MENTIONED ON THE PREVIOUS REVIEW
 PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE
 CERTIFICATION SHEETS. THIS DOES NOT MEAN THE NAME SHALL
 BE TYPE WRITTEN ON SHEETS, THIS REQUIRES A SIGNATURE.
 PLEASE BE SURE AS MENTIONED ON PREVIOUS REVIEW THE
 CERTIFICATION SHEET CONTAINS THE SIGNATURE AND SEAL
 FROM THE DESIGN PROFESSIONAL.13-103.1., FBC 106.1.2
 ADMIN SECTION.
  
 8) NOTE: PLEASE SEE COMPLIANCE FOR 13-415.1.ABC.1.1,
 .1.2 AND .1.3 HAVE NOT BEEN ACHIEVED FOR ALL LIGHTING
 AS REQUIRED.
 THERE ARE LOCATIONS ON PLANS WHICH STILL ONLY SHOW A
 STANDARD METHOD OF CONTROL WHEN THE CODE REQUIRES
 AUTOMATED SHUT OFF. SOME AREAS WERE GIVEN AS EXAMPLES
 ON PREVIOUS REVIEW AND NOTED AS ALSO SEE OTHER AREAS.
 PLEASE SEE PREVIOUS NOTE WITH RESPECT TO SOME OF THE
 FIXTURES NOTED WHICH WERE NOT INCLUDED IN THE IDR. ONE
 FOR EXAMPLE WAS FIXTURE *P* WHICH WAS GIVEN. PLEASE SEE
 HOST AREA WHICH SHOWS FIXTURE *P* ABOVE ARE WHICH
 CONTAINS A STANDARD DIMMING SWITCH AND DOES NOT GO TO
 ANY CIRCUITING, CONTROLS, DIMMING PANEL ETC? THE PLANS
 DO CONTAIN NOTES #9 AND #10 HOWEVER THEY MENTION TO SEE
 E2.1 FOR CONTINUATION HOWEVER 2.1 DOES NOT PROVIDE ANY
 CONTROL OR CIRCUITING INFORMATION. PLEASE EXPLAIN AND
 SHOW HOW THE OCCUPANT CAN SEE ALL LIGHTING WHICH IS
 BEING CONTROLLED AS THIS PROPOSED CONTROL IS AT ONE
 LOCATION. HOW WILL SYSTEM MEET IDENTIFICATION AND PILOT
 LIGHTS REQUIRED?
 PLEASE SEE BAR RELAY PANEL MENTIONS THIS BEING A RELAY
 PANEL HOWEVER THE CIRCUITS IN THIS PANEL ARE SHOWN FROM
 PANEL L1 AND NO OVER RIDES OR TIMES COULD BE FOUND.
 EXAMPLE: PLEASE SEE PLANS STILL INDICATE LIGHTING IN
 MEN'S AND WOMEN'S BATHROOM WITH NO SEPARATE SPACE OVER
 RIDE CONTROLS. SOME LIGHTING WAS NOW PLACED ON
 OCCUPANCY SENSORS HOWEVER SEE DIMMING PANEL WHICH STILL
 LIST LIGHTS IN BOTH OF THESE LOCATIONS.
 ** PLEASE VERIFY LISTING OF MARLIN PANELS AND MATRIX
 CONTROLLERS. AS THE SYSTEM ON PLANS WAS NOT COMPLETE
 SOME RESEARCH OF SYSTEM COMPONENTS WAS DONE AND EVEN AS
 EACH MAY BE LISTED, COULD NOT LOCATE THESE AS A LISTED
 ASSEMBLY OR SYSTEM. PLEASE PROVIDE TECHNICAL SPECS/CUT
 SHEETS FOR THIS PER 110.3, 90.7. THESE ARE NOW BEING
 REQUESTED AS THE INFORMATION FOR LABELING, PILOT LIGHTS
 ETC HAS NOT BEEN CLEAR ALONG WITH CONTROLS.
  
 9) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT
 TO TRACK LIGHTING LOADS AND HOW THEY WERE FIGURED INTO
 SERVICE PER 220.43B. THE DIMMING PANELS NOW SHOW THE VA
 PER TWO FT HOWEVER THE LOADS ARE STILL SHOWN AT 1.0
 FACTOR. ARE THESE NOT CONTINUOUS LOADS?
 125%, 215.3, 230.42 ETC PLEASE ADJUST.
  
 10) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO
 FLORIDA STATUES 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. AT THIS TIME AS REQUIRED
 UNDER FLORIDA STATUTES, THIS OFFICE HAS ASSESSED THE
 FEE AS REQUIRED WHICH IS REQUIRED TO BE PAID BEFORE THE
 PLANS MAY BE RESUBMITTED. PLEASE BE SURE TO GO OVER
 COMMENTS, IF THERE ARE ANY QUESTIONS PLEASE CONTACT
 THIS OFFICE/REVIEWER TO GO OVER COMMENTS.
 PLEASE SEE THE FEE OF $18, 600 WILL BE DUE UPON
 RESUBMITTING OF PLANS.
 ** ONE SET OF ELECTRICAL PLANS ALONG WITH ONE COPY OF
 THE ENERGY CALCULATIONS SUBMITTED ARE BEING RETAINED BY
 THIS OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-11 19:37:58 
  
 ** REVIEW WILL GO INTO A FAILED STATUS. NOTES TO FOLLOW
 ONCE COMPLETED.