2008-03-18 11:04:38BUILDING PLAN REVIEW
 PERMIT: 07090648
 ADD: 700 S ROSEMARY AVE# 100
 CONT: IN MOTION BUILDERS, INC.
 TEL: (954)698-0900
 MARCH 18/2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1A) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. 2)SHEET
 T1.1,CODE ANALYSIS PLEASE UPDATE THE 2004 TO THE 2007
 FBC, BUILDING WITH 2007 REVISIONS.
  
 1E) NEW COMMENT, PLANS INDICATE A NEW COVERED PATIO
 AREA BUT THE PERMIT APPLICATION
 (DUPLICATE) INDICATES ?ONLY INTERIOR WORK? WHICH IS
 CORRECT? THIS GREATLY AFFECTS THE SCOPE OF WHAT WORK
 WILL BE ACCOMPLISHED UNDER THIS PERMIT AND REVIEW.
 SINCE THE FIRST 2 REVIEWS WERE REVIEWED WITH THE
 COVERED PATIO ADDITION AS PART OF THE PERMIT SCOPE THIS
 REVIEW WILL ALSO INCLUDE THIS SAME SCOPE OF WORK. IF
 THE EXTERIOR COVERED PATIO IS NOT PART OF THIS PERMIT
 IT SHOULD NOT SHOW UP ON THE PLANS.
  
 2-9) COMPLIED.
  
 10) STRUCTURAL CALCULATIONS WERE RESUBMITTED,
 STRUCTURAL DESIGN CALCULATIONS ARE MISSING A SIGNED AND
 SEALED INDEX SHEET INDICATING WHAT WORK IS COVERED IN
 THIS REPORT.. FL S S 471.025.
  
 11A) COMPLIED.
  
 11B) 3RD REQUEST FROM PREVIOUS AUDITS,*** WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 11C) 3RD REQUEST FROM PREVIOUS AUDITS,*** W.P.B.
 AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 12) 3RD REQUEST FROM PREVIOUS AUDITS,*** THE STRUCTURAL
 SHEET S0.0 FOUNDATION DESIGN INDICATES THERE TO BE A
 GEOTECHNICAL SOILS ENGINEER SHALL VERIFY THAT THE SOILS
 OF THE DESIGN BEARING CAPACITY HAVE BEEN ENCOUNTERED.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 13-16) COMPLIED.
  
 17) 3RDD REQUEST FROM PREVIOUS AUDITS,*** FL BLD CODE
 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 COPIES (FOR
 THRESHOLD BUILDINGS (3 COPIES) OF PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
  
 17A) FIXED WINDOWS, STOREFRONT, FL COVERSHEET ONLY
 SUBMITTED
 PLANS CALL FOR LARGE MISSILE IMPACT RATED GLAZING, THE
 FL# 6001.1
 IS FOR NON-RATED SYSTEM REQUIRING STORM SHUTTERS OR
 ROLL DOWN SYSTEM
  
 17B) GLAZED EXTERIOR SWING DOOR, SINGLE AND PAIRS FL
 COVERSHEET SUBMITTED, NON-IMPACT
  
 17C) DOORS W/ SIDELIGHTS, FL COVERSHEET
 ONLY SUBMITTED, PLANS CALL FOR LARGE MISSILE IMPACT
 RATED GLAZING, THE FL# 7237.1 & 7237.2 IS FOR NON-RATED
 IMPACT SYSTEM REQUIRING STORM SHUTTERS OR ROLL DOWN
 SYSTEM ,
 THE ROLL-DOWN SYSTEM IS NOT FOUND IN THE SECTION
 DETAILS, THERE ARE HEATERS FOUND IN SOME OF THESE
 AREAS.
  
 17D) FOLDING DOOR SYSTEM FL COVERSHEET ONLY SUBMITTED.
 FL 6859.1 IMPACT RATED, A +/-
 75 PSF BUT IN NON WIND BORNE DEBRIS REGION.
  
 17D) FOLDING WALL SYSTEM FL 2947.2FL COVERSHEET
 SUBMITTED. .NANA WALL SYSTEM- FBC 2001 FBC NOT 2004FBC,
 SEE RESTRICTIONS PLANS INDICATE 13?-0? OPENINGS WITH 4
 EQUAL PANELS, RESTRICTION SIZE IS LIMITED TO 3?-0?. SEE
 REPORT NOT SUBMITTED!!!
  
 17E) HURRICANE SHUTTER, HORIZONTAL ROLLER, FL
 COVERSHEET ONLY SUBMITTED, PLANS INDICATE LARGE MISSILE
 ON THE EGRESS DOOR BUT THE FL NUMBERS SUBMITTED ARE FOR
 NON-RATED GLAZING BLOCKING REQUIRED EXITS WITH STORM
 SHUTTER OR ROLL DOWN SHUTTER SYSTEMS.
  
 17F) TRUSS ANCHOR TYPE HARDWARE, FL COVERSHEET
 SUBMITTED, OK WILL USE VALUES FROM CATALOG
 NO 1/3RD STEEL INCREASES TAKEN COLUMN.
  
 17G) LOUVER, FL COVERSHEET SUBMITTED THE REPORT NOT
 SUBMITTED WILL SHOW THIS TO BE A NON-
 RATED WALL LOUVER, SEE 1609.1.4(5).
  
 17H) ROOFING ASSEMBLIES W / INSULATION, FL COVERSHEET
 SUBMITTED ONLY, THE REPORT NOT SUBMITTED WILL INDICATE
 THAT THIS SYSTEM IS TO BE USED FOR APPLICATION TO A
 PLYWOOD DECK.
 BOTH THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE
 THE USE OF A METAL DECK, PLEASE SEE
 PLANS FOR DETAILS.
  
 18) 3RD REQUEST FROM PREVIOUS AUDITS,*** PRODUCT
 APPROVALS SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72.
  
 19) 3RD REQUEST FROM PREVIOUS AUDITS,*** WPB ADMIN CODE
 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2)*** THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 20)3RD REQUEST FROM PREVIOUS AUDITS,*** SHEET EX1.1
 INDICATES POINTS WHERE THE EXIT IS 3?-8? BUT THE WIDTH
 OF THE EGRESS PATH MAY BE AS LITTLE AS 30? IN SOME
 AREAS, PLEASE PROVIDE THE EGRESS PATH SHOWING THE FULL
 44? WHERE IT SERVES AN OCCUPANT LOAD GREATER THAN 50
 AND 36? WHERE REQUIRED FOR LESS THAN 50. 1024.9.1.1 THE
 MINIMUM WIDTH OF AISLES SERVING SEATING AT TABLES SHALL
 BE 44 INCHES (1118 MM). EXCEPTION: THIRTY-SIX INCHES
 (914 MM) WHERE SERVING AN OCCUPANT LOAD OF NOT MORE
 THAN 50.
  
 THERE ARE STILL AREAS ON THE EGRESS PLAN THAT WILL NOT
 MEET THE MINIMUM CLEARANCES PENCILED IN AREAS OF
 CONCERN.
  
 21-23) COMPLIED.
  
 24) BUILDING PROVISO: A6.4 DETAIL # 2 & S5.0 FOR A
 BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP
 DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE
 DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE
 140 MPH PROVISIONS OF 1609.6.
  
 25) COMPLIED.
  
 NEW COMMENTS, 3RD REVIEW:
  
 26) THE NEW SHEET A8.1 DOES NOT HAVE THE STAMP FROM
 CAPRI INDICATING CODE COMPLIANCE.
  
 27) THE NEW SHEET A8.1 THE DESIGN PROFESSIONAL JAMES R
 LENCIONI, ARCHITECT PUT THE EXPIRATION DATE OF HIS
 LICENSE ON THIS SHEET NOT THE DATE IT WAS DRAWN OR
 CHANGES MADE.
  
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 XX - STATE DATE PREPARED
 XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL -
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 NOTE:
 *** CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE OR
 MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE
 VIOLATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved