2008-03-18 11:04:38 | BUILDING PLAN REVIEW |
| PERMIT: 07090648 |
| ADD: 700 S ROSEMARY AVE# 100 |
| CONT: IN MOTION BUILDERS, INC. |
| TEL: (954)698-0900 |
| MARCH 18/2008 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3RD REVIEW |
| ACTION: DENIED |
| |
| 1A) --- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM |
| BEACH ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. 2)SHEET |
| T1.1,CODE ANALYSIS PLEASE UPDATE THE 2004 TO THE 2007 |
| FBC, BUILDING WITH 2007 REVISIONS. |
| |
| 1E) NEW COMMENT, PLANS INDICATE A NEW COVERED PATIO |
| AREA BUT THE PERMIT APPLICATION |
| (DUPLICATE) INDICATES ?ONLY INTERIOR WORK? WHICH IS |
| CORRECT? THIS GREATLY AFFECTS THE SCOPE OF WHAT WORK |
| WILL BE ACCOMPLISHED UNDER THIS PERMIT AND REVIEW. |
| SINCE THE FIRST 2 REVIEWS WERE REVIEWED WITH THE |
| COVERED PATIO ADDITION AS PART OF THE PERMIT SCOPE THIS |
| REVIEW WILL ALSO INCLUDE THIS SAME SCOPE OF WORK. IF |
| THE EXTERIOR COVERED PATIO IS NOT PART OF THIS PERMIT |
| IT SHOULD NOT SHOW UP ON THE PLANS. |
| |
| 2-9) COMPLIED. |
| |
| 10) STRUCTURAL CALCULATIONS WERE RESUBMITTED, |
| STRUCTURAL DESIGN CALCULATIONS ARE MISSING A SIGNED AND |
| SEALED INDEX SHEET INDICATING WHAT WORK IS COVERED IN |
| THIS REPORT.. FL S S 471.025. |
| |
| 11A) COMPLIED. |
| |
| 11B) 3RD REQUEST FROM PREVIOUS AUDITS,*** WPB AMENDMENT |
| 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT |
| HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM |
| AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE |
| PERMIT MAY BE ISSUED. |
| |
| 11C) 3RD REQUEST FROM PREVIOUS AUDITS,*** W.P.B. |
| AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 12) 3RD REQUEST FROM PREVIOUS AUDITS,*** THE STRUCTURAL |
| SHEET S0.0 FOUNDATION DESIGN INDICATES THERE TO BE A |
| GEOTECHNICAL SOILS ENGINEER SHALL VERIFY THAT THE SOILS |
| OF THE DESIGN BEARING CAPACITY HAVE BEEN ENCOUNTERED. |
| 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING |
| POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING |
| VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS |
| CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE |
| NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION |
| SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4 |
| THROUGH 1802.6 . |
| |
| 13-16) COMPLIED. |
| |
| 17) 3RDD REQUEST FROM PREVIOUS AUDITS,*** FL BLD CODE |
| 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 COPIES (FOR |
| THRESHOLD BUILDINGS (3 COPIES) OF PRODUCT TESTING |
| REPORTS ,MISSING REPORTS ARE AS FOLLOWS: |
| |
| 17A) FIXED WINDOWS, STOREFRONT, FL COVERSHEET ONLY |
| SUBMITTED |
| PLANS CALL FOR LARGE MISSILE IMPACT RATED GLAZING, THE |
| FL# 6001.1 |
| IS FOR NON-RATED SYSTEM REQUIRING STORM SHUTTERS OR |
| ROLL DOWN SYSTEM |
| |
| 17B) GLAZED EXTERIOR SWING DOOR, SINGLE AND PAIRS FL |
| COVERSHEET SUBMITTED, NON-IMPACT |
| |
| 17C) DOORS W/ SIDELIGHTS, FL COVERSHEET |
| ONLY SUBMITTED, PLANS CALL FOR LARGE MISSILE IMPACT |
| RATED GLAZING, THE FL# 7237.1 & 7237.2 IS FOR NON-RATED |
| IMPACT SYSTEM REQUIRING STORM SHUTTERS OR ROLL DOWN |
| SYSTEM , |
| THE ROLL-DOWN SYSTEM IS NOT FOUND IN THE SECTION |
| DETAILS, THERE ARE HEATERS FOUND IN SOME OF THESE |
| AREAS. |
| |
| 17D) FOLDING DOOR SYSTEM FL COVERSHEET ONLY SUBMITTED. |
| FL 6859.1 IMPACT RATED, A +/- |
| 75 PSF BUT IN NON WIND BORNE DEBRIS REGION. |
| |
| 17D) FOLDING WALL SYSTEM FL 2947.2FL COVERSHEET |
| SUBMITTED. .NANA WALL SYSTEM- FBC 2001 FBC NOT 2004FBC, |
| SEE RESTRICTIONS PLANS INDICATE 13?-0? OPENINGS WITH 4 |
| EQUAL PANELS, RESTRICTION SIZE IS LIMITED TO 3?-0?. SEE |
| REPORT NOT SUBMITTED!!! |
| |
| 17E) HURRICANE SHUTTER, HORIZONTAL ROLLER, FL |
| COVERSHEET ONLY SUBMITTED, PLANS INDICATE LARGE MISSILE |
| ON THE EGRESS DOOR BUT THE FL NUMBERS SUBMITTED ARE FOR |
| NON-RATED GLAZING BLOCKING REQUIRED EXITS WITH STORM |
| SHUTTER OR ROLL DOWN SHUTTER SYSTEMS. |
| |
| 17F) TRUSS ANCHOR TYPE HARDWARE, FL COVERSHEET |
| SUBMITTED, OK WILL USE VALUES FROM CATALOG |
| NO 1/3RD STEEL INCREASES TAKEN COLUMN. |
| |
| 17G) LOUVER, FL COVERSHEET SUBMITTED THE REPORT NOT |
| SUBMITTED WILL SHOW THIS TO BE A NON- |
| RATED WALL LOUVER, SEE 1609.1.4(5). |
| |
| 17H) ROOFING ASSEMBLIES W / INSULATION, FL COVERSHEET |
| SUBMITTED ONLY, THE REPORT NOT SUBMITTED WILL INDICATE |
| THAT THIS SYSTEM IS TO BE USED FOR APPLICATION TO A |
| PLYWOOD DECK. |
| BOTH THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE |
| THE USE OF A METAL DECK, PLEASE SEE |
| PLANS FOR DETAILS. |
| |
| 18) 3RD REQUEST FROM PREVIOUS AUDITS,*** PRODUCT |
| APPROVALS SUBMITTED WITH PERMIT APPLICATION AFTER |
| OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE |
| STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A |
| COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE |
| APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT |
| APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. |
| |
| 19) 3RD REQUEST FROM PREVIOUS AUDITS,*** WPB ADMIN CODE |
| 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2)*** THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC... |
| WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT |
| WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 20)3RD REQUEST FROM PREVIOUS AUDITS,*** SHEET EX1.1 |
| INDICATES POINTS WHERE THE EXIT IS 3?-8? BUT THE WIDTH |
| OF THE EGRESS PATH MAY BE AS LITTLE AS 30? IN SOME |
| AREAS, PLEASE PROVIDE THE EGRESS PATH SHOWING THE FULL |
| 44? WHERE IT SERVES AN OCCUPANT LOAD GREATER THAN 50 |
| AND 36? WHERE REQUIRED FOR LESS THAN 50. 1024.9.1.1 THE |
| MINIMUM WIDTH OF AISLES SERVING SEATING AT TABLES SHALL |
| BE 44 INCHES (1118 MM). EXCEPTION: THIRTY-SIX INCHES |
| (914 MM) WHERE SERVING AN OCCUPANT LOAD OF NOT MORE |
| THAN 50. |
| |
| THERE ARE STILL AREAS ON THE EGRESS PLAN THAT WILL NOT |
| MEET THE MINIMUM CLEARANCES PENCILED IN AREAS OF |
| CONCERN. |
| |
| 21-23) COMPLIED. |
| |
| 24) BUILDING PROVISO: A6.4 DETAIL # 2 & S5.0 FOR A |
| BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP |
| DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE |
| DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE |
| 140 MPH PROVISIONS OF 1609.6. |
| |
| 25) COMPLIED. |
| |
| NEW COMMENTS, 3RD REVIEW: |
| |
| 26) THE NEW SHEET A8.1 DOES NOT HAVE THE STAMP FROM |
| CAPRI INDICATING CODE COMPLIANCE. |
| |
| 27) THE NEW SHEET A8.1 THE DESIGN PROFESSIONAL JAMES R |
| LENCIONI, ARCHITECT PUT THE EXPIRATION DATE OF HIS |
| LICENSE ON THIS SHEET NOT THE DATE IT WAS DRAWN OR |
| CHANGES MADE. |
| |
| 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A |
| REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| MUST: |
| - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER |
| - STATE THE FIRM LICENSE NUMBER |
| - STATE PROJECT NAME OR IDENTIFICATION |
| XX - STATE DATE PREPARED |
| XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL - |
| INCLUDE THE PRINTED NAME OF THE |
| ARCHITECT SEALING THE PLANS |
| |
| |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| NOTE: |
| *** CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE OR |
| MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE |
| VIOLATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |