Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop P
Sequence Number 2
Notes
Date Text
2008-01-28 16:53:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED
 BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272, E-MAIL [email protected] OR CALVIN
 WILLIAMS (561) 822-2284, E-MAIL [email protected].
 THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN
 DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL
 BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR
 EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL
 CODE ARTICLE III SECTION 90-124(7).
 ****RESPONSE NOTED, BUT THE WRITTEN APPROVAL HAS NOT
 BEEN SUBMITTED.
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED
 LETTER HAS NOT BEEN SUBMITTED AS REQUESTED.
  
 4. OK
  
 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR
 THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV.
 SECTIONS 303, 303.1 303.2, & 303.4.
 ****RESPONSE NOTED, BUT THE LAV DRAIN PAN AND GRANITE
 LAV SHALL BE SUBMITTED AS ALTERNATIVE MATERIALS, DESIGN
 & METHODS OF CONSTRUCTION AND EQUIPMENT PER SECTION
 104.1.1 SUBMIT DETAILS AS TO THE FINISH AND POROSITY OF
 THE GRANITE AND INDICATE THE GUAGE OF THE STAINLESS
 STEEL LAV DRAIN PAN. INFORMATION SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL.
  
 6. OK
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
 ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE WATER FILTER HAVE NOT BEEN FOUND.
  
 8. OK
 9. OK
  
 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163
 DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES
 DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE KITCHEN SPEC BOOK HAS NOT
 BEEN FOUND.
  
 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN
 DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR
 RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED
 BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION
 106.1.
 ****RESPONSE NOTED, BUT THE KITCHEN CONSULTANT RESPONSE
 HAS NOT BEEN FOUND.
  
 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND
 THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE
 TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH
 INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL
 BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES. FAC 61G15-23.002(2) & FS 471.025. ****RESPONSE
 NOTED, BUT THE SIGNED, SEALED, NOTORIZED LETTER HAS NOT
 BEEN SUBMITTED.
  
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER
 SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO
 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE
 GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED.
 SECTION 402.
 ****RESPONSE NOTED, BUT THE INLET PRESSURE HAS BEEN
 INDICATED AS 2PSI AND .5 PSI. PLEASE CONTACT THE GAS
 PROVIDER AND INDICATE PRESSURE PROVIDED AT THE METER.
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT
 INDICATED.
 ****RESPONSE NOTED, BUT THE CUT SECTIONS FROM THE METER
 TO THE FIRST RISERS ON BOTH BRANCHES HAVE NO LENGTHS
 INDICATED AS WELL AS THE LENGTH FROM THE BRANCH LINES
 TO THE PATIO HEATERS.
  
 B. OK
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE
 REQUIREMENT "A" IS ADDRESSED.
 ****RESPONSE NOTED, BUT "A" HAS NOT BEEN COMPLETLY
 ADDRESS AND THE TOTAL DISTANCE FROM THE METER TO THE
 MOST REMOTE OUTLET DOES NOT APPEAR TO BE CORRECT.
 PLEASE RECHECK THE ADDITION.
  
 D. OK
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT
 #21.
 ****RESPONSE NOTED, BUT THE DELIVERY PRESSURE CAN BE
 2PSI OR .5 PSI, BUT NOT BOTH. INDICATE THE DELIVERY
 PRESSURE.
  
 F. OK
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS
 FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE
 RH UNITS.
 ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT
 SUBMITTED.
  
 H. OK
  
 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR
 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2"
 REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE
 RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE
 402.4(2) - (IF SCHEDULE 40 PIPE).
 ****RESPONSE NOTED, BUT 3/4" IS STILL SHOWN TO THE RICE
 COOKERS.
  
 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE
 DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED
 ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE
 NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY
 HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS
 NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE
 CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4.
  
 25. OK
 26. OK
 27. OK
 28. OK
  
 **********NEW COMMENTS**********
  
 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE
 OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS
 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND
 APPLICATION FOR PERMIT.
  
 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE
 VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]