Date |
Text |
2008-01-28 16:53:59 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| MUNICIPAL CODES WPB |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. OK |
| |
| 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED |
| BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT, |
| ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| (561) 822-2272, E-MAIL [email protected] OR CALVIN |
| WILLIAMS (561) 822-2284, E-MAIL [email protected]. |
| THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN |
| DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL |
| BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR |
| EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL |
| CODE ARTICLE III SECTION 90-124(7). |
| ****RESPONSE NOTED, BUT THE WRITTEN APPROVAL HAS NOT |
| BEEN SUBMITTED. |
| |
| 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED |
| INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED |
| NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN |
| SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL |
| SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED, |
| SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE |
| LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC |
| 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219, |
| 481.2055. |
| ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED |
| LETTER HAS NOT BEEN SUBMITTED AS REQUESTED. |
| |
| 4. OK |
| |
| 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR |
| THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV. |
| SECTIONS 303, 303.1 303.2, & 303.4. |
| ****RESPONSE NOTED, BUT THE LAV DRAIN PAN AND GRANITE |
| LAV SHALL BE SUBMITTED AS ALTERNATIVE MATERIALS, DESIGN |
| & METHODS OF CONSTRUCTION AND EQUIPMENT PER SECTION |
| 104.1.1 SUBMIT DETAILS AS TO THE FINISH AND POROSITY OF |
| THE GRANITE AND INDICATE THE GUAGE OF THE STAINLESS |
| STEEL LAV DRAIN PAN. INFORMATION SHALL BE SUBMITTED TO |
| THE BUILDING OFFICIAL. |
| |
| 6. OK |
| |
| 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE |
| REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION |
| 611.1. |
| ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR |
| THE WATER FILTER HAVE NOT BEEN FOUND. |
| |
| 8. OK |
| 9. OK |
| |
| 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163 |
| DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES |
| DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| ****RESPONSE NOTED, BUT THE KITCHEN SPEC BOOK HAS NOT |
| BEEN FOUND. |
| |
| 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN |
| DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR |
| RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED |
| BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION |
| 106.1. |
| ****RESPONSE NOTED, BUT THE KITCHEN CONSULTANT RESPONSE |
| HAS NOT BEEN FOUND. |
| |
| 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF |
| AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND |
| THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE |
| TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH |
| INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL |
| BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR |
| FILES. FAC 61G15-23.002(2) & FS 471.025. ****RESPONSE |
| NOTED, BUT THE SIGNED, SEALED, NOTORIZED LETTER HAS NOT |
| BEEN SUBMITTED. |
| |
| 13. OK |
| 14. OK |
| 15. OK |
| 16. OK |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| |
| 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER |
| SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO |
| 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE |
| GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED. |
| SECTION 402. |
| ****RESPONSE NOTED, BUT THE INLET PRESSURE HAS BEEN |
| INDICATED AS 2PSI AND .5 PSI. PLEASE CONTACT THE GAS |
| PROVIDER AND INDICATE PRESSURE PROVIDED AT THE METER. |
| |
| 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT |
| INDICATED. |
| ****RESPONSE NOTED, BUT THE CUT SECTIONS FROM THE METER |
| TO THE FIRST RISERS ON BOTH BRANCHES HAVE NO LENGTHS |
| INDICATED AS WELL AS THE LENGTH FROM THE BRANCH LINES |
| TO THE PATIO HEATERS. |
| |
| B. OK |
| |
| C. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE |
| REQUIREMENT "A" IS ADDRESSED. |
| ****RESPONSE NOTED, BUT "A" HAS NOT BEEN COMPLETLY |
| ADDRESS AND THE TOTAL DISTANCE FROM THE METER TO THE |
| MOST REMOTE OUTLET DOES NOT APPEAR TO BE CORRECT. |
| PLEASE RECHECK THE ADDITION. |
| |
| D. OK |
| |
| E. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT |
| #21. |
| ****RESPONSE NOTED, BUT THE DELIVERY PRESSURE CAN BE |
| 2PSI OR .5 PSI, BUT NOT BOTH. INDICATE THE DELIVERY |
| PRESSURE. |
| |
| F. OK |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS |
| FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE |
| RH UNITS. |
| ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT |
| SUBMITTED. |
| |
| H. OK |
| |
| 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR |
| 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2" |
| REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE |
| RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE |
| 402.4(2) - (IF SCHEDULE 40 PIPE). |
| ****RESPONSE NOTED, BUT 3/4" IS STILL SHOWN TO THE RICE |
| COOKERS. |
| |
| 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE |
| DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED |
| ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE |
| NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE |
| FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY |
| HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS |
| NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE |
| CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE |
| RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4. |
| |
| 25. OK |
| 26. OK |
| 27. OK |
| 28. OK |
| |
| **********NEW COMMENTS********** |
| |
| 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE |
| OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS |
| 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND |
| APPLICATION FOR PERMIT. |
| |
| 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| NOTICE ONLY AT THIS TIME. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE |
| VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |