Date Text
2008-01-31 15:27:03** NOTE ADDED **
 1/31
  
  
 1) NOTE: IT HAS BEEN CONFIRMED WITH FIRE MARSHAL THAT
 AN EXIT SIGN WILL BE REQUIRED AT DELIVERY DOOR FOR
 KITCHEN PERSONNEL.
 LS 101 7.8,7.9
2008-01-30 14:58:50** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SUBMIT THE REQUIRED FEE OWNER AFFIDAVIT
 WHICH IS REQUIRED PER FS 553.791(4)(C).
  
 2) NOTE: PLEASE SEE SIGNATURE LETTER SUBMITTED FOR THE
 ENGINEER CONTAINS TWO DIFFERENT SIGNATURES OF THE
 RESPONSIBLE ENGINEER OF RECORD.
 PLEASE SEE FS 471.025 WHICH SIGNATURE IS THE LEGAL
 ORIGINAL SIGNATURE FOR ENGINEER OF RECORD?
 PLEASE CALL TO GO OVER.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #17 WITH
 RESPECT TO LIGHTING ON BATH ROOMS BEING NOTED TO BE
 CONTROLLED BY DIMMING PANEL. THE RESPONSE WAS THE
 EMERGENCY LIGHT FIXTURE IS CIRCUITED TO THE HOT/LINE
 SIDE OF THE LOCAL CIRCUIT WHICH IS OK. PLEASE SEE THE
 PREVIOUS REVIEW COMMENT WAS NOT FOR THE EMERGENCY
 LIGHTING AND CIRCUITING, IT WAS FOR THE LEVELS OF
 LIGHTING UNDER NORMAL CONDITIONS. PLEASE SEE THE CODE
 SECTION WHICH WAS GIVEN ON PREVIOUS REVIEW WAS LS 101
 7.8 WHICH IS FOR MINIMUM LIGHTING LEVELS UNDER NORMAL
 CONDITIONS. THIS IS NOT FOR THE EMERGENCY (BATTERY BACK
 UP) LIGHT FIXTURE.
 PLEASE SEE THE LIGHTING LEVELS FOR EGRESS IN, AROUND
 AND EXITING BATHROOMS MAY NOT FALL BELOW 1FT CANDLE
 AVERAGE AT ALL EGRESS WALKING SURFACES.
 THIS COMMENT IS ALSO FOR OTHER EGRESS PATHS AS
 DESIGNATED AS GENERAL LIGHTING ON DIMMER PANEL MAY NOT
 FALL BELOW MINIMUM 1FT CANDLE LEVEL. PLEASE INDICATE
 HOW THIS IS BEING DONE.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 14 WITH
 RESPECT TO LIGHTING CONTROLS REQUIRED IN SEPARATE
 SPACES AND AN EXAMPLE WAS NOTED *SUCH AS BATHROOMS*.
 THE RESPONSE MENTIONS THE PARTITIONS INSIDE THE
 BATHROOMS AND CONTROLS ARE NOT REQUIRED AS THESE
 PARTITIONS DO NOT GO ALL THE WAY TO THE CEILING. PLEASE
 SEE 13-415.1.ABC.1.1 AND .1.2. THE PREVIOUS COMMENT WAS
 NOT FOR THE STALL AREAS IN THE BATHROOMS. THIS WAS FOR
 THE *BATHROOMS* AS THEY ARE CONSIDERED SEPARATE SPACES
 FROM OTHER OPEN AREAS WITH LIGHTING CONTROLS.
 PLEASE SEE THIS AND ANY OTHER AREAS.
 PLEASE SEE THIS PREVIOUS REVIEW NOTE ALSO CONTAIN A
 NOTICE ABOUT THE OCCUPANT BEING ABLE TO VISUALLY SEE
 ALL LIGHTING IN WHICH IS BEING OVER RIDDEN. PLEASE SEE
 THE RESPONSE LETTER ONLY RESPONDED TO PARTITIONS IN
 BATHROOMS. PLEASE CLARIFY HOW THE OCCUPANT FROM EACH
 OVER RIDE/ ENTRANCE LOCATION CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED OR MEETING THE
 EXCEPTION IN SAME SECTION AS PREVIOUSLY NOTED. THIS
 WOULD REQUIRE PILOT LIGHTS ETC CLEARLY LABELED.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 15 WITH
 RESPECT TO CHAPTER 13 AND ENERGY CALCULATIONS
 SUBMITTED.
 PLEASE KNOW THE PREVIOUS SUBMITTED METHOD WAS *A* WHICH
 IS NOW CHANGED TO METHOD *B* WHICH IS ACCEPTABLE
 HOWEVER PLEASE SEE FBC 13-400.3.B AS THE VERSION
 SUBMITTED IS NOT THE VERSION AS ADOPTED UNDER THE FBC.
 PLEASE SEE THE SECTION AS NOTED WHICH REFERENCES
 VERSION 2.5/400.B-04R.
 PLEASE SEE THE FOLLOWING SECTIONS TO THIS SAME NOTE:
 PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR
 ON THE FOLLOWING NOTES.
  
 A) ONCE AGAIN PLEASE CORRELATE ALL LIGHTING ON PLANS
 WITH THE IDR. PLEASE SEE SOME EXAMPLES WERE GIVEN ON
 PREVIOUS REVIEW HOWEVER THEY WERE NOT ALL.
 PLEASE SEE FOR EXAMPLE: THE EXTERIOR LIGHTING SHOWN ON
 PLANS DOES NOT COORDINATE WITH THE IDR FOR EXTERIOR
 LIGHTS. PLEASE SEE FIXTURES *H*, *BB*, *EM4*, ETC.
 PLEASE SEE FOR EXAMPLE: THE FIXTURES WHICH ARE NOTED AS
 INTERIOR LIGHTING WHEN THEY ARE LOCATED OUTSIDE. HOW IS
 THIS POSSIBLE?
 PLEASE SEE THE FIXTURES NOTED AS *EM4* ON PLANS ARE
 FIXTURES USED AS PART OF THE GENERAL LIGHTING WHICH ARE
 NOT EXEMPT.
 PLEASE ALSO SEE THE LIGHTING ON PLANS FOR INTERIOR
 FIXTURES DO NOT CORRELATE WITH THE IDR AND FIXTURE
 LEGEND. FOR EXAMPLE: SEE MISSING VA INPUTS FOR FIXTURES
 *P*, SEE MISSING VA REQUIRED FOR TRACK LIGHTING AS
 PREVIOUS NOTED, SEE ENTRY E1 FIXTURES AND COUNTS ON
 THESE IN HOST AREAS ETC
  
 THERE ARE SEVERAL INSTANCES ON PLANS AS NOTED WHICH
 NEED COORDINATION. PLEASE KNOW AS THE LOCATION
 DESIGNATIONS ON PLANS DO NOT CORRELATE WITH THE IDR AND
 BASED ON THE FACT NOT ALL LIGHTING IS FIGURED INTO THE
 IDR A COMPLETE REVIEW OF ALL ITEMS CAN NOT BE DONE AT
 THIS TIME.MECHANICAL ROOM, OTHER ROOM ON PLANS NEAR
 TOILET VESTIBULE NOT LABELED.
 PLEASE SEE 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3,
 13-415.2.ABC.1.2 (TRACK LIGHTING FOR LINE VOLTAGE AND
 LOW VOLTAGE) ETC.
  
 6) NOTE: PLEASE SEE THE CERTIFICATION SHEET CONTAINS A
 SIGNATURE FOR THE PERSON WHO *PREPARED* CALCULATIONS
 HOWEVER DOES NOT LIST ANY INFORMATION FOR THIS PERSON.
 PLEASE LIST INFORMATION AS LICENSED PE IN THE STATE OF
 FLORIDA. PLEASE SEE 13-103.1, FAC 61G15-23.002,
 FS471.025.
 THE COVER SHEET CONTAINS SIGNATURES AND SEALS FROM TOW
 OTHER DESIGNERS HOWEVER THIS INFORMATION SHOULD BE ON
 THE CERTIFICATION SHEET AS STATED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO
 LOADS FOR TRACK LIGHTING. PLEASE SEE RESPONSE MENTIONS
 LOAD WAS ADDED TO PANELS ON E4.1 HOWEVER COULD NOT
 LOCATE ON PLANS, PANELS OR ANY LOAD CALCULATIONS HOW
 THESE LOADS WERE DERIVED PER 220.43B.
  
 8) NOTE: PLEASE SEE FIXTURES EM4 ON SOUTH SIDE OF ENTRY
 VESTIBULE WILL BE REQUIRED TO BE CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT FEEDING OTHER *Q* FIXTURES IN THAT AREA
 PER 700.12F.
 PLEASE SEE THEY ARE CURRENTLY SHOWN COMING FROM SOUTH
 PATIO CIRCUIT.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS ALONG WITH ONE
 SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS
 OFFICE.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-01-29 20:16:33ON SET IN ELECTRICAL FOR REVIEW.