2008-01-31 15:27:03 | ** NOTE ADDED ** |
| 1/31 |
| |
| |
| 1) NOTE: IT HAS BEEN CONFIRMED WITH FIRE MARSHAL THAT |
| AN EXIT SIGN WILL BE REQUIRED AT DELIVERY DOOR FOR |
| KITCHEN PERSONNEL. |
| LS 101 7.8,7.9 |
2008-01-30 14:58:50 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM |
| PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING. |
| |
| 1) NOTE: PLEASE SUBMIT THE REQUIRED FEE OWNER AFFIDAVIT |
| WHICH IS REQUIRED PER FS 553.791(4)(C). |
| |
| 2) NOTE: PLEASE SEE SIGNATURE LETTER SUBMITTED FOR THE |
| ENGINEER CONTAINS TWO DIFFERENT SIGNATURES OF THE |
| RESPONSIBLE ENGINEER OF RECORD. |
| PLEASE SEE FS 471.025 WHICH SIGNATURE IS THE LEGAL |
| ORIGINAL SIGNATURE FOR ENGINEER OF RECORD? |
| PLEASE CALL TO GO OVER. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #17 WITH |
| RESPECT TO LIGHTING ON BATH ROOMS BEING NOTED TO BE |
| CONTROLLED BY DIMMING PANEL. THE RESPONSE WAS THE |
| EMERGENCY LIGHT FIXTURE IS CIRCUITED TO THE HOT/LINE |
| SIDE OF THE LOCAL CIRCUIT WHICH IS OK. PLEASE SEE THE |
| PREVIOUS REVIEW COMMENT WAS NOT FOR THE EMERGENCY |
| LIGHTING AND CIRCUITING, IT WAS FOR THE LEVELS OF |
| LIGHTING UNDER NORMAL CONDITIONS. PLEASE SEE THE CODE |
| SECTION WHICH WAS GIVEN ON PREVIOUS REVIEW WAS LS 101 |
| 7.8 WHICH IS FOR MINIMUM LIGHTING LEVELS UNDER NORMAL |
| CONDITIONS. THIS IS NOT FOR THE EMERGENCY (BATTERY BACK |
| UP) LIGHT FIXTURE. |
| PLEASE SEE THE LIGHTING LEVELS FOR EGRESS IN, AROUND |
| AND EXITING BATHROOMS MAY NOT FALL BELOW 1FT CANDLE |
| AVERAGE AT ALL EGRESS WALKING SURFACES. |
| THIS COMMENT IS ALSO FOR OTHER EGRESS PATHS AS |
| DESIGNATED AS GENERAL LIGHTING ON DIMMER PANEL MAY NOT |
| FALL BELOW MINIMUM 1FT CANDLE LEVEL. PLEASE INDICATE |
| HOW THIS IS BEING DONE. |
| |
| 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 14 WITH |
| RESPECT TO LIGHTING CONTROLS REQUIRED IN SEPARATE |
| SPACES AND AN EXAMPLE WAS NOTED *SUCH AS BATHROOMS*. |
| THE RESPONSE MENTIONS THE PARTITIONS INSIDE THE |
| BATHROOMS AND CONTROLS ARE NOT REQUIRED AS THESE |
| PARTITIONS DO NOT GO ALL THE WAY TO THE CEILING. PLEASE |
| SEE 13-415.1.ABC.1.1 AND .1.2. THE PREVIOUS COMMENT WAS |
| NOT FOR THE STALL AREAS IN THE BATHROOMS. THIS WAS FOR |
| THE *BATHROOMS* AS THEY ARE CONSIDERED SEPARATE SPACES |
| FROM OTHER OPEN AREAS WITH LIGHTING CONTROLS. |
| PLEASE SEE THIS AND ANY OTHER AREAS. |
| PLEASE SEE THIS PREVIOUS REVIEW NOTE ALSO CONTAIN A |
| NOTICE ABOUT THE OCCUPANT BEING ABLE TO VISUALLY SEE |
| ALL LIGHTING IN WHICH IS BEING OVER RIDDEN. PLEASE SEE |
| THE RESPONSE LETTER ONLY RESPONDED TO PARTITIONS IN |
| BATHROOMS. PLEASE CLARIFY HOW THE OCCUPANT FROM EACH |
| OVER RIDE/ ENTRANCE LOCATION CAN VISUALLY SEE THE |
| LIGHTING WHICH IS BEING CONTROLLED OR MEETING THE |
| EXCEPTION IN SAME SECTION AS PREVIOUSLY NOTED. THIS |
| WOULD REQUIRE PILOT LIGHTS ETC CLEARLY LABELED. |
| |
| 5) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 15 WITH |
| RESPECT TO CHAPTER 13 AND ENERGY CALCULATIONS |
| SUBMITTED. |
| PLEASE KNOW THE PREVIOUS SUBMITTED METHOD WAS *A* WHICH |
| IS NOW CHANGED TO METHOD *B* WHICH IS ACCEPTABLE |
| HOWEVER PLEASE SEE FBC 13-400.3.B AS THE VERSION |
| SUBMITTED IS NOT THE VERSION AS ADOPTED UNDER THE FBC. |
| PLEASE SEE THE SECTION AS NOTED WHICH REFERENCES |
| VERSION 2.5/400.B-04R. |
| PLEASE SEE THE FOLLOWING SECTIONS TO THIS SAME NOTE: |
| PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR |
| ON THE FOLLOWING NOTES. |
| |
| A) ONCE AGAIN PLEASE CORRELATE ALL LIGHTING ON PLANS |
| WITH THE IDR. PLEASE SEE SOME EXAMPLES WERE GIVEN ON |
| PREVIOUS REVIEW HOWEVER THEY WERE NOT ALL. |
| PLEASE SEE FOR EXAMPLE: THE EXTERIOR LIGHTING SHOWN ON |
| PLANS DOES NOT COORDINATE WITH THE IDR FOR EXTERIOR |
| LIGHTS. PLEASE SEE FIXTURES *H*, *BB*, *EM4*, ETC. |
| PLEASE SEE FOR EXAMPLE: THE FIXTURES WHICH ARE NOTED AS |
| INTERIOR LIGHTING WHEN THEY ARE LOCATED OUTSIDE. HOW IS |
| THIS POSSIBLE? |
| PLEASE SEE THE FIXTURES NOTED AS *EM4* ON PLANS ARE |
| FIXTURES USED AS PART OF THE GENERAL LIGHTING WHICH ARE |
| NOT EXEMPT. |
| PLEASE ALSO SEE THE LIGHTING ON PLANS FOR INTERIOR |
| FIXTURES DO NOT CORRELATE WITH THE IDR AND FIXTURE |
| LEGEND. FOR EXAMPLE: SEE MISSING VA INPUTS FOR FIXTURES |
| *P*, SEE MISSING VA REQUIRED FOR TRACK LIGHTING AS |
| PREVIOUS NOTED, SEE ENTRY E1 FIXTURES AND COUNTS ON |
| THESE IN HOST AREAS ETC |
| |
| THERE ARE SEVERAL INSTANCES ON PLANS AS NOTED WHICH |
| NEED COORDINATION. PLEASE KNOW AS THE LOCATION |
| DESIGNATIONS ON PLANS DO NOT CORRELATE WITH THE IDR AND |
| BASED ON THE FACT NOT ALL LIGHTING IS FIGURED INTO THE |
| IDR A COMPLETE REVIEW OF ALL ITEMS CAN NOT BE DONE AT |
| THIS TIME.MECHANICAL ROOM, OTHER ROOM ON PLANS NEAR |
| TOILET VESTIBULE NOT LABELED. |
| PLEASE SEE 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3, |
| 13-415.2.ABC.1.2 (TRACK LIGHTING FOR LINE VOLTAGE AND |
| LOW VOLTAGE) ETC. |
| |
| 6) NOTE: PLEASE SEE THE CERTIFICATION SHEET CONTAINS A |
| SIGNATURE FOR THE PERSON WHO *PREPARED* CALCULATIONS |
| HOWEVER DOES NOT LIST ANY INFORMATION FOR THIS PERSON. |
| PLEASE LIST INFORMATION AS LICENSED PE IN THE STATE OF |
| FLORIDA. PLEASE SEE 13-103.1, FAC 61G15-23.002, |
| FS471.025. |
| THE COVER SHEET CONTAINS SIGNATURES AND SEALS FROM TOW |
| OTHER DESIGNERS HOWEVER THIS INFORMATION SHOULD BE ON |
| THE CERTIFICATION SHEET AS STATED. |
| |
| 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO |
| LOADS FOR TRACK LIGHTING. PLEASE SEE RESPONSE MENTIONS |
| LOAD WAS ADDED TO PANELS ON E4.1 HOWEVER COULD NOT |
| LOCATE ON PLANS, PANELS OR ANY LOAD CALCULATIONS HOW |
| THESE LOADS WERE DERIVED PER 220.43B. |
| |
| 8) NOTE: PLEASE SEE FIXTURES EM4 ON SOUTH SIDE OF ENTRY |
| VESTIBULE WILL BE REQUIRED TO BE CIRCUITED TO THE LOCAL |
| BRANCH CIRCUIT FEEDING OTHER *Q* FIXTURES IN THAT AREA |
| PER 700.12F. |
| PLEASE SEE THEY ARE CURRENTLY SHOWN COMING FROM SOUTH |
| PATIO CIRCUIT. |
| |
| 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| NOTICE GIVEN AT THIS TIME. |
| PLEASE KNOW ONE SET OF ELECTRICAL PLANS ALONG WITH ONE |
| SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS |
| OFFICE. |
| |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2008-01-29 20:16:33 | ON SET IN ELECTRICAL FOR REVIEW. |