Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-01 09:52:11DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODES WPB
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL &
 RESTAURANT FOOD SERVICE LICENSE FOR REVIEW. REVIEWED
 SHEETS SHALL BE INSERTED INTO EACH SET OF PLANS AND THE
 TWO PAGE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED
 TO THE STAMPED PLANS REVIEWED BY DBPR. SECTION
 102.2.1.
  
 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED
 BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272, E-MAIL [email protected] OR CALVIN
 WILLIAMS (561) 822-2284, E-MAIL [email protected].
 THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN
 DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL
 BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR
 EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL
 CODE ARTICLE III SECTION 90-124(7).
  
 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED
 INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN
 THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN
 SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE
 LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC
 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219,
 481.2055.
  
 4. SHT A1.1 KEY NOTES WERE NOT FOUND. PLEASE CORRELATE
 KEY NOTES WITH FLOOR PLAN. SECTION 106.1.1.
  
 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR
 THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV.
 SECTIONS 303, 303.1 303.2, & 303.4.
  
 6. SHT A8.1 DETAIL 10 INDICATES A STORAGE CABINET WHERE
 THE LAV DRAIN PAN SHOULD BE PLEASE CLARIFY. SECTION
 106.1.1.
  
 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION
 611.1.
  
 8. SHTS FI-1 THRU FS-13 ARE SEALED BY THE ARCHITECT OF
 RECORD INDICATING "REVIEWED ONLY". IF THE PLANS ARE
 SIGNED AND SEALED THEN A TITLE BLOCK, PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT, DATED SEAL ETC IS
 REQUIRED. IF REVIEWING ONLY, INDICATE WITH A SHOP
 REVIEW APPROVAL STAMP ONLY SUCH AS USED IN SUBMITTALS.
 FAC 61G1-16.004 & FS 481.2055.
  
 9. SHT FS-1 EQUIPMENT SCHEDULE ITEM #62 NOT FOUND ON
 THE FLOOR PLAN, & ITEM 147 INDICATES QTY 1 BUT 2 ARE
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163
 DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES
 DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION
 106.1.1.
  
 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN
 DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR
 RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED
 BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION
 106.1.
  
 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND
 THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE
 TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH
 INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL
 BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES. FAC 61G15-23.002(2) & FS 471.025.
  
 13. ALL MEP SHEETS. THE CERTIFICATE OF AUTHORIZATION
 NUMBER, PRINTED NAME OF THE ENGINEER, AND THE LICENSE
 NUMBER OF THE ENGINEER ARE REQUIRED ON THE TITLE BLOCK.
 ALSO THE PLANS APPEAR TO BE SIGNED WITH INITIALS. IF
 THIS IS INDEED THE LEGAL SIGNATURE OF THE ENGINEER,
 THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL BE
 SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR FILES.
 FAC 61G15-23.002(2) & FS 471.025.
  
 14. SHT P1.1 THE CONDENSATE FROM THE AHU'S SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. THE CONDENSATE SHALL
 DRAIN SEPARATELY OUT OF THE BUILDING AND CONNECT TO
 STORM DRAINAGE, A CATCH BASIN, A DRYWELL OR INTO A
 PLANTED AREA SO AS NOT TO CREATE A HAZARD. IF THE
 CONDENSATE CONNECTS TO THE STORM LINES OUTSIDE THE
 BUILDING, THEN A RELIEF VENT, (GOOSENECK), SHALL BE
 PROVIDED AS THE CONDENSATE LINE EXITS THE BUILDING.
 MUNICIPAL CODE ARTICLE III SECTION 90-125(5).
  
 15. SHT P1.1 CONDENSATE FROM THE COOLER/FREEZER. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A
 FLOOR SINK OR HUB DRAIN IS REQUIRED. SECTIONS 802.3 &
 802.3.2.
  
 16. SHT P1.1 THE DISWASHER SHALL DRAIN TO THE SANITARY
 SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL CODE ARTICLE
 III SECTION 90-124(7)(B). PLEASE CHANGE THE FLOOR PLAN
 AND THE SANITARY RISER DIAGRAM.
  
 17. SHT P1.1 PLUMBING WASTE & VENT PLAN NOTES #6.
 CLEANOUTS TO BE PROVIDED AT THE BASE OF THE STACK PER
 SECTION 708.3.4. PLEASE INDICATE THE CORRECT LOCATION
 FOR THE CLEANOUTS.
  
 18. SHT P1.1 VBF'S DO NOT MEET THE REQUIREMENTS OF
 SECTION 913, ISLAND VENTS. (SEE ATTACHED SHEET FOR
 REQUIRED PIPING). PLEASE CORRECT VENTING TO COMPLY WITH
 SECTION 913.
  
 19. SHT P2.1 THE 3" GAS LINE IS INDICATED AS HAVING
 1,812 CFH & 1,482 CFH ON THE SAME LINE DOWNSTREAM OF
 THE METER. PLEASE ONLY SHOW THE CORRECT LOAD ON THE GAS
 LINE. SECTION 106.1.1.
  
 20. SHT P2.1 PLUMBING PLAN NOTES #3. THE RPZV BACKFLOWS
 SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE FLOOR FOR
 CERTIFICTION AND SERVICE. PLEASE INDICATE ON PLANS.
 SECTION 106.2.1.
  
 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER
 SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO
 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE
 GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED.
 SECTION 402.
  
 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT
 INDICATED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE
 REQUIREMENT "A" IS ADDRESSED.
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT
 #21.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS
 FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE
 RH UNITS.
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - UNION NOT SHOWN.
  
 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR
 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2"
 REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE
 RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE
 402.4(2) - (IF SCHEDULE 40 PIPE).
  
 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE
 DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED
 ON BOTH VENT LINES. (SEE ATTACHED SHEET).
  
 25. SHT P3.2 GREASE WASTE & VENT RISER VENT DOES NOT
 MEET CODE PER SECTION 905.4. VENTS ARE TURNING
 HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL OF
 THE FLOOR SINKS. (SEE GENERAL NOTE).
  
 26. SHT P3.2 GREASE WASTE & VENT RISER DOES NOT REFLECT
 THE FLOOR PLAN. FLOOR SINK (107) IS NOT SHOWN ON THE
 FLOOR PLAN.--IDENTIFY THE FIXTURE THAT THE ICE
 MACHINE IS DRAINING INTO. AN INDIRECT WASTE RECEPTOR IS
 REQUIRED. SECTIONS 106.1.1, 802.3 & 802.3.2.
  
 27. SHT P3.2 SANITARY WASTE & VENT RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR
 PLAN THAT ARE NOT ON THE RISER DIAGRAM.--PIPING TO
 FIXTURE 166 DOES NOT REFLECT THE FLOOR PLAN.-- PIPING
 UPSTREAM OF FIXTURE 162 DOES NOT RELFECT THE FLOOR
 PLAN. (AS SHOWN ON THE FLOOR PLAN IT IS A DRY
 HORIZONTAL VENT WHICH IS NOT APPROVED PER SECTION 905.3
 & SECTION 905.4.--THE ISLAND VENT FOR FIXTURE 166
 DOES NOT MEET CODE REQUIREMENT. (SEE ATTACHED SHEET).
  
 28. SHT P3.3 SHOW WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 ON THE RISER DIAGRAM. (QUICK CLOSING
 VALVES SUCH AS WASHING MACHINE, ICE MAKER ETC.). THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NO IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]