2007-10-01 09:52:11 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| MUNICIPAL CODES WPB |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF |
| BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL & |
| RESTAURANT FOOD SERVICE LICENSE FOR REVIEW. REVIEWED |
| SHEETS SHALL BE INSERTED INTO EACH SET OF PLANS AND THE |
| TWO PAGE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED |
| TO THE STAMPED PLANS REVIEWED BY DBPR. SECTION |
| 102.2.1. |
| |
| 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED |
| BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT, |
| ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| (561) 822-2272, E-MAIL [email protected] OR CALVIN |
| WILLIAMS (561) 822-2284, E-MAIL [email protected]. |
| THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN |
| DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL |
| BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR |
| EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL |
| CODE ARTICLE III SECTION 90-124(7). |
| |
| 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED |
| INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED |
| NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN |
| SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL |
| SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED, |
| SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE |
| LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC |
| 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219, |
| 481.2055. |
| |
| 4. SHT A1.1 KEY NOTES WERE NOT FOUND. PLEASE CORRELATE |
| KEY NOTES WITH FLOOR PLAN. SECTION 106.1.1. |
| |
| 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR |
| THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV. |
| SECTIONS 303, 303.1 303.2, & 303.4. |
| |
| 6. SHT A8.1 DETAIL 10 INDICATES A STORAGE CABINET WHERE |
| THE LAV DRAIN PAN SHOULD BE PLEASE CLARIFY. SECTION |
| 106.1.1. |
| |
| 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE |
| REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION |
| 611.1. |
| |
| 8. SHTS FI-1 THRU FS-13 ARE SEALED BY THE ARCHITECT OF |
| RECORD INDICATING "REVIEWED ONLY". IF THE PLANS ARE |
| SIGNED AND SEALED THEN A TITLE BLOCK, PRINTED NAME OF |
| THE PERSON SEALING THE DOCUMENT, DATED SEAL ETC IS |
| REQUIRED. IF REVIEWING ONLY, INDICATE WITH A SHOP |
| REVIEW APPROVAL STAMP ONLY SUCH AS USED IN SUBMITTALS. |
| FAC 61G1-16.004 & FS 481.2055. |
| |
| 9. SHT FS-1 EQUIPMENT SCHEDULE ITEM #62 NOT FOUND ON |
| THE FLOOR PLAN, & ITEM 147 INDICATES QTY 1 BUT 2 ARE |
| SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163 |
| DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES |
| DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| |
| 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN |
| DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR |
| RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED |
| BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION |
| 106.1. |
| |
| 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF |
| AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND |
| THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE |
| TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH |
| INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL |
| BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR |
| FILES. FAC 61G15-23.002(2) & FS 471.025. |
| |
| 13. ALL MEP SHEETS. THE CERTIFICATE OF AUTHORIZATION |
| NUMBER, PRINTED NAME OF THE ENGINEER, AND THE LICENSE |
| NUMBER OF THE ENGINEER ARE REQUIRED ON THE TITLE BLOCK. |
| ALSO THE PLANS APPEAR TO BE SIGNED WITH INITIALS. IF |
| THIS IS INDEED THE LEGAL SIGNATURE OF THE ENGINEER, |
| THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL BE |
| SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR FILES. |
| FAC 61G15-23.002(2) & FS 471.025. |
| |
| 14. SHT P1.1 THE CONDENSATE FROM THE AHU'S SHALL NOT |
| DRAIN INTO THE SANITARY SYSTEM. THE CONDENSATE SHALL |
| DRAIN SEPARATELY OUT OF THE BUILDING AND CONNECT TO |
| STORM DRAINAGE, A CATCH BASIN, A DRYWELL OR INTO A |
| PLANTED AREA SO AS NOT TO CREATE A HAZARD. IF THE |
| CONDENSATE CONNECTS TO THE STORM LINES OUTSIDE THE |
| BUILDING, THEN A RELIEF VENT, (GOOSENECK), SHALL BE |
| PROVIDED AS THE CONDENSATE LINE EXITS THE BUILDING. |
| MUNICIPAL CODE ARTICLE III SECTION 90-125(5). |
| |
| 15. SHT P1.1 CONDENSATE FROM THE COOLER/FREEZER. FLOOR |
| DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A |
| FLOOR SINK OR HUB DRAIN IS REQUIRED. SECTIONS 802.3 & |
| 802.3.2. |
| |
| 16. SHT P1.1 THE DISWASHER SHALL DRAIN TO THE SANITARY |
| SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL CODE ARTICLE |
| III SECTION 90-124(7)(B). PLEASE CHANGE THE FLOOR PLAN |
| AND THE SANITARY RISER DIAGRAM. |
| |
| 17. SHT P1.1 PLUMBING WASTE & VENT PLAN NOTES #6. |
| CLEANOUTS TO BE PROVIDED AT THE BASE OF THE STACK PER |
| SECTION 708.3.4. PLEASE INDICATE THE CORRECT LOCATION |
| FOR THE CLEANOUTS. |
| |
| 18. SHT P1.1 VBF'S DO NOT MEET THE REQUIREMENTS OF |
| SECTION 913, ISLAND VENTS. (SEE ATTACHED SHEET FOR |
| REQUIRED PIPING). PLEASE CORRECT VENTING TO COMPLY WITH |
| SECTION 913. |
| |
| 19. SHT P2.1 THE 3" GAS LINE IS INDICATED AS HAVING |
| 1,812 CFH & 1,482 CFH ON THE SAME LINE DOWNSTREAM OF |
| THE METER. PLEASE ONLY SHOW THE CORRECT LOAD ON THE GAS |
| LINE. SECTION 106.1.1. |
| |
| 20. SHT P2.1 PLUMBING PLAN NOTES #3. THE RPZV BACKFLOWS |
| SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE FLOOR FOR |
| CERTIFICTION AND SERVICE. PLEASE INDICATE ON PLANS. |
| SECTION 106.2.1. |
| |
| 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER |
| SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO |
| 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE |
| GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED. |
| SECTION 402. |
| |
| 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| FOLLOWING INFORMATION IS REQUIRED: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT |
| INDICATED. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE |
| REQUIREMENT "A" IS ADDRESSED. |
| |
| D. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| |
| E. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT |
| #21. |
| |
| F. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS |
| FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE |
| RH UNITS. |
| |
| H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. - UNION NOT SHOWN. |
| |
| 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR |
| 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2" |
| REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE |
| RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE |
| 402.4(2) - (IF SCHEDULE 40 PIPE). |
| |
| 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE |
| DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED |
| ON BOTH VENT LINES. (SEE ATTACHED SHEET). |
| |
| 25. SHT P3.2 GREASE WASTE & VENT RISER VENT DOES NOT |
| MEET CODE PER SECTION 905.4. VENTS ARE TURNING |
| HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL OF |
| THE FLOOR SINKS. (SEE GENERAL NOTE). |
| |
| 26. SHT P3.2 GREASE WASTE & VENT RISER DOES NOT REFLECT |
| THE FLOOR PLAN. FLOOR SINK (107) IS NOT SHOWN ON THE |
| FLOOR PLAN.--IDENTIFY THE FIXTURE THAT THE ICE |
| MACHINE IS DRAINING INTO. AN INDIRECT WASTE RECEPTOR IS |
| REQUIRED. SECTIONS 106.1.1, 802.3 & 802.3.2. |
| |
| 27. SHT P3.2 SANITARY WASTE & VENT RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| REQUIREMENTS. 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR |
| PLAN THAT ARE NOT ON THE RISER DIAGRAM.--PIPING TO |
| FIXTURE 166 DOES NOT REFLECT THE FLOOR PLAN.-- PIPING |
| UPSTREAM OF FIXTURE 162 DOES NOT RELFECT THE FLOOR |
| PLAN. (AS SHOWN ON THE FLOOR PLAN IT IS A DRY |
| HORIZONTAL VENT WHICH IS NOT APPROVED PER SECTION 905.3 |
| & SECTION 905.4.--THE ISLAND VENT FOR FIXTURE 166 |
| DOES NOT MEET CODE REQUIREMENT. (SEE ATTACHED SHEET). |
| |
| 28. SHT P3.3 SHOW WATER HAMMER ARRESTORS REQUIRED BY |
| SECTION 604.9 ON THE RISER DIAGRAM. (QUICK CLOSING |
| VALVES SUCH AS WASHING MACHINE, ICE MAKER ETC.). THE |
| WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| FIXTURES IN AN "EFFECTIVE RANGE" NO IN THE CEILING. |
| PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| |