Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop M
Sequence Number 1
Notes
Date Text
2007-09-28 18:15:07REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG A3.1: REGARDING EQUIPMENT SUPPORT DETAIL #2, IF
 ROOFING MATERIALS EXTEND UNDER EQUIPMENT, RAISED
 EQUIPMENT SUPPORTS SHALL PROVIDE MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH FBC TABLE 1509.7.
  
 2. PG A3.1: WHAT IS THE HEIGHT OF EXISTING PARAPET WALL
 ADJACENT TO NEW GREASE EXHAUST FAN? THE MINIMUM
 HORIZONTAL DISTANCE BETWEEN VERTICAL DISCHARGE FANS AND
 PARAPET-TYPE BUILDING STRUCTURES SHALL BE AT LEAST 10
 FEET UNLESS SUCH STRUCTURES ARE LOWER THAN THE TOP OF
 THE FAN DISCHARGE OPENING. IF THE FAN DISCHARGE OPENING
 IS HIGHER THAN SUCH STRUCTURE THE MINIMUM DISTANCE
 SHALL BE TWO FEET. PLEASE PROVIDE AN ELEVATION VIEW
 SHOWING THE HEIGHT OF THE FAN OUTLET AND PARAPET WALL
 AS WELL AS THE DISTANCE BETWEEN THEM TO DEMONSTRATE
 COMPLIANCE WITH FBC,M 506.5.5.
  
 3. PG A3.1: KEY NOTE #7, ANY EXISTING STANDS MAY BE
 USED AS-IS PROVIDED THE NEW EQUIPMENT IS ATTACHED TO
 MEET WIND LOADS IN ACCORDANCE WITH FBC,M 301.13 AND FBC
 CH.16. HOWEVER, ANY NEW EQUIPMENT INSTALLED ON NEW
 STANDS SHALL ALSO MEET THE CLEARANCE REQUIREMENTS OF
 FBC TABLE 1509.7.
  
 4. PG M1.1: MAU-1 IS SHOWN ABOVE THE WALK-IN COOLER.
 SERVICE ACCESS FOR MAU-1 WILL BE ABOVE THE COOLER. ARE
 THE COOLER CEILING PANELS STRUCTURALLY SOUND FOR THE
 PURPOSE OF BEING A WALKING SURFACE FOR SERVICE ACCESS?
 IF SO, PROVIDE DETAIL SHOWING SAME. ALSO, IF COOLER IS
 TO SERVE A SERVICE ACCESS, GUARDS ARE REQUIRED IN
 ACCORDANCE WITH FBC,M 304.10.
  
 5. PG FS-13: FREEZER/COOLER DETAIL INDICATES THIS IS
 FOR AN OUTDOOR INSTALLATION. PG M1.1 SHOWS THE
 FREEZER/COOLER INDOORS. PLEASE CLARIFY. FBC,M 304.1.
 ALSO, PG FS-13 CALLS FOR 3/4 INCH PLYWOOD IN
 FREEZER/COOLER CEILING PANELS. AS THIS BUILDING IS OF
 TYPE IB CONSTRUCTION, PLEASE SHOW COMPLIANCE WITH FBC
 603.1.
  
 6. PG M1.1: AHU-2 IS ABOVE A GYPSUM BOARD CEILING.
 ACCESS FOR SERVICE OR REPLACEMENT IS REQUIRED WITHOUR
 REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBC,M 306.1. PLEASE SHOW HOW ACCESS TO
 THIS EQUIPMENT IS TO BE PROVIDED.
  
 7. PG M1.1: AHU-3, MOTORIZED OUTDOOR AIR DAMPER IS
 LOCATED ABOVE A GYPSUM BOARD CEILING. PROVIDE ACCESS IN
 ACCORDANCE WITH FBC,M 306.1 AND SPECIFICATION 15A 1-18
 ON PG M4.1.
  
 8. SHOW LOCATION OF DUCT MOUNTED SMOKE DETECTORS ON ALL
 AHU'S TO DEMONSTRATE COMPLIANCE WITH FBC,M 606.3.
 DETECTORS ARE TO MONITOR THE ENTIRE AIRFLOW AND BE
 ACCESSIBLE FOR INSPECTION AND MAINTENANCE.
  
 9. PROVIDE OUTDOOR AIR CALCULATIONS SHOWING OCCUPANCY
 CLASSIFICATION, OCCUPANT LOADS AND CFM REQUIRED BASED
 ON FBC,M TABLE 403.3. THIS SHOULD BE INCLUDED AS PART
 OF SIGNED AND SEALED PLANS. FBC 106.1.2.
  
 10. PG M1.2: NOTE #20 CALLS FOR GREASE DUCT (SHOWN ON
 M1.1) TO BE PITCHED MIN. 1/4 INCH PER FOOT. WHEN
 HORIZONTAL DUCTS EXCEED 75 FEET IN LENGTH, AS THEY DO
 IN THIS APPLICATION, THE SLOPE SHALL BE NOT BE LESS
 THAN 1 INCH PER FOOT IN ACCORDANCE WITH FBC,M 506.3.7.
 GIVEN THE DISTANCE AS SHOWN BETWEEN KEH-1 OUTLET TO THE
 RISER LOCATION (PLAN NOTE #33 ON M1.1), A RISE OF OVER
 100 INCHES WOULD BE REQUIRED TO MAINTAIN THE MINIMUM
 SLOPE. PLEASE VERIFY THAT THIS IS POSSIBLE AND ADJUST
 THE DESIGN, IF NECESSARY, TO SHOW COMPLIANCE WITH THIS
 SECTION.
  
 11. PG M1.2: CHILLED WATER PIPE PENETRATIONS OF FIRE
 RESISTANCE RATED WALL ASSEMBLY ARE REQUIRED TO BE
 PROTECTED WITH A THROUGH-PENETRATION FIRESTOP SYSTEM IN
 ACCORDANCE WITH FBC SEC.712. PROVIDE DETAIL WHICH
 CORRESPONDS WITH THE LISTED ASSEMBLY TO BE USED.
  
 12. PG M3.1: PROVIDE DETAIL SHOWING HOW GREASE DUCTS
 ARE TO BE SUPPORTED, INCLUDING ATTACHMENTS TO
 STRUCTURE, IN ACCORDANCE WITH FBC,M 506.3.3 AND FBC
 106.1.2.
  
 13. TYPE I HOODS SHALL BE SECURED IN PLACE BY
 NONCOMBUSTIBLE SUPPORTS. ALL TYPE I AND TYPE II HOOD
 SUPPORTS SHALL BE ADEQUATE FOR THE APPLIED LOAD OF THE
 HOOD, THE UNSUPPORTED DUCTWORK, THE EFFLUENT LOADING,
 AND THE POSSIBLE WEIGHT OF PERSONNEL WORKING IN OR ON
 THE HOOD. PROVIDE DETAIL FOR SUPPORTS ON TYPE I AND
 TYPE II HOODS. FBC,M 507.6
  
 14. PG M3.1: DETAIL 5 INDICATES "PREFABRICATED
 EQUIPMENT SUPPORT RAILS." ANY PRE-ENGINEERED EQUIPMENT
 STANDS ARE CONSIDERED STRUCTURAL COMPONNTS UNDER FAC
 RULE 9B-72 AND AS SUCH ARE SUBJECT TO THE FLORIDA
 PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT APPROVAL FOR
 THE SPECIFIC STAND(S) TO BE USED IN ALL NEW
 APPLICATIONS, INCLUDING THOSE MENTIONED IN COMMENT #3.
 FOR MORE INFORMATION ON THE FLORIDA PRODUCT APPROVAL
 SYSTEM PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 15. PG. M3.1: WALL LOUVERS ARE CLASSIFIED AS PANEL
 WALLS UNDER FAC RULE 9B-72 AND AS SUCH ARE SUBJECT TO
 THE FLORIDA PRODUCT APPROVAL SYSTEM. PROVIDE PRODUCT
 APPROVAL FOR THE SPECIFIC LOUVER(S) TO BE USED IN ALL
 NEW APPLICATIONS. FOR MORE INFORMATION ON THE FLORIDA
 PRODUCT APPROVAL SYSTEM PLEASE VISIT:
 WWW.FLORIDABUILDING.ORG
  
 16. PG M3.1: DETAIL 5, CONNECTIONS TO SIDE-INLET
 UTILITY FANS SHALL BE FLANGED, GASKETED AND BOLTED TO
 THE INLET. PLEASE SHOW HOW DUCT IS TO BE CONNECTED TO
 EXHAUST FAN. FBC,M 506.3.2.2
  
 17. PG M2.1: AHU-4 AND AHU-5, THE HP RATING ON THESE
 FAN MOTORS EXCEEDS THE MAXIMUM ALLOWABLE MOTOR POWER IN
 ACCORDANCE WITH FBC TABLE 13-410.1.1.1. ALSO, AHU-1
 SHOWS A 3 HP MOTOR, BUT THE MODEL NUMBER SHOWN ON
 SCHEDULE INDICATES THIS SIZE UNIT WOULD HAVE A 5 HP
 MOTOR. PLEASE VERIFY MODEL NUMBERS AND SHOW ALL THREE
 UNITS TO BE IN COMPLIANCE WITH THIS SECTION.
  
 18. ENERGY CALCULATIONS: A METHOD A COMPLIANCE FORM HAS
 BEEN SUBMITTED FOR THIS PROJECT. HOWEVER, AS THIS IS
 NOT A WHOLE NEW BUILDING, COMPLIANCE WITH FBC CHAPTER
 13 SHALL BE DEMONSTRATED IN ACCORDANCE WITH FBC
 13-400.0.C.4. EXISTING BUILDINGS NOT MEETING THE
 DEFINITION OF A RENOVATION (SEE DEFINITION IN SEC.202)
 IN WHICH NEW HEATING, COOLING, WATER HEATING,
 ELECTRICAL OR LIGHTING SYSTEMS ARE INSTALLED SHALL MEET
 THE BASIC PRESCRIPTIVE MINIMUM EFFICIENCIES LISTED IN
 THIS CODE FOR THE SYSTEM(S) BEING CHANGED.
  
 19. IF A CODE COMPLIANCE FORM IS TO BE SUBMITTED FOR
 THIS PROJECT, THE PERSON PREPARING THE COMPLIANCE
 CALCULATION SHALL CERTIFY THAT THE CALCULATION, OR
 AMENDMENTS THERETO, IS TRUE AND ACCURATE AND
 DEMONSTRATES THAT THE BUILDING IS IN COMPLIANCE WITH
 THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE. ORIGINAL
 SIGNATURE AND SEAL IS REQUIRED ON THE CERTIFICATIONS
 PAGE OF EACH SET OF CALCULATIONS. FBC 13-400.3.ABC.2.
 ONE SET OF CALCULATIONS WHICH WERE SUBMITTED CONTAINS
 NO SEAL AND PHOTOCOPIED SIGNATURES. ALSO, THE PARTY
 RESPONSIBLE UNDER SUBSECTIONS 471.003 AND 481.228 AND
 CHAPTER 489, FLORIDA STATUTES, FOR THE DESIGN AND
 SPECIFICATION OF EACH BUILDING SYSTEM SHALL CERTIFY
 THAT THE PLANS AND SPECIFICATIONS FOR THAT SYSTEM
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE
 (SEE ALSO SECTION 13-103.2). THIS INFORMATION SHALL
 ALSO BE INCLUDED ON THE CERTIFICATIONS PAGE IN
 ACCORDANCE WITH THIS SECTION.
  
 20. M1.1: ROOM 126 (MECHANICAL ROOM) HAS TWO 196,000
 BTU/H GAS WATER HEATERS. DETAIL 9 ON PG P5.1 INDICATES
 EXHAUST AND INTAKE FOR WATER HEATERS ARE TO BE
 INSTALLED BY MECHANICAL. NO INFORMATION COULD BE FOUND
 IN MECHANICAL OR PLUMBING PLANS SHOWING ANY PROVISIONS
 FOR VENTING COMBUSTION OR DILLUTION AIR FOR THESE GAS
 APPLIANCES. SHOW MEANS OF VENTING AND COMBUSTION AIR IN
 ACCORDANCE WITH FBC,FG SEC. 304, PROVIDE CALCULATIONS
 IF COMBUSTION AIR IS REQUIRED UNDER THIS SECTION. IF A
 LISTED APPLIANCE IS BEING USED WITH INTEGRAL OR DIRECT
 VENTS, PROVIDE SUBMITTAL WITH INSTALLATION
 INSTRUCTIONS.
  
 21. EACH SHEET OF PLANS AND PRINTS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL BE
 SEALED, SIGNED AND DATED BY THE PROFESSIONAL ENGINEER
 IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) PLEASE CORRECT EACH SHEET SIGNED/SEALED
 BY AN ENGINEER WHICH IS MISSING THIS INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: