2007-10-04 14:29:10 | *****DENIED***** |
| |
| |
| 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE |
| PROJECT SITE ADDRESS LOCATED IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET. |
| |
| 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED.ADD TO CODE ANALYSIS UNDER APPLICABLE |
| CODES (SHEET T1.1). |
| |
| 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY |
| AS NECESSARY FOR SAFE OPERATION. |
| |
| 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| SOUTH ROSEMARY AVENUE, DISPLAY THE SUITE NUMBER.AS |
| PER WEST PALM BEACH CODE, TENANT SPACE NUMBERS SHALL BE |
| NO LESS THA 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| |
| 06.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE ENTRY |
| CANOPY. |
| |
| 07.A DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL |
| BE SELF-CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH |
| 7.2.1.8.2 OF NFPA 101. |
| |
| 08.COMMERCIAL COOKING EQUIPMENT SHALL BE IN |
| ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT |
| WILL BE REQUIRED FOR THE HOOD INSTALLATION AS WELL AS |
| THE HOOD SUPPRESSION SYSTEM. |
| |
| 09.SPECIFY INTERIOR FINISH CLASSIFICATION FOR THE |
| WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH |
| MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL |
| ASSEMBLY AREA HAVING AN OCCUPANT LOAD S OF MORE THAN |
| 300. |
| |
| 10.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF |
| CLASS I OR CLASSII. |
| |
| 11.THE 2002 EDITION NFPA 13 SHALL BE BE REFERENCED |
| FOR THE FIRE SPRINKLER INSTALLATION AND/RE-MODEL. |
| |
| 12.THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED |
| FOR THE INSTALLATION/RE-MODEL OF THE FIRE ALARM |
| SYSTEM. |
| |
| 13.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS |
| SHALL INITIATE A GENERAL FIRE ALARM.AMEND FIRE ALARM |
| GENERAL NOTE 6 ON SHEET F1.1 AND ALSO THE FIRE ALARM |
| SEQUENCE OF OPERATIONS ON SHEET F2.1 SECTION 16C 2-3. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE (ON THE PLAN OR IN THE |
| SPECIFICATIONS) EACH COMMENT WAS ADDRESSED |
| |