2007-10-04 14:29:10*****DENIED*****
  
  
 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE
 PROJECT SITE ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.ADD TO CODE ANALYSIS UNDER APPLICABLE
 CODES (SHEET T1.1).
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY
 AS NECESSARY FOR SAFE OPERATION.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, DISPLAY THE SUITE NUMBER.AS
 PER WEST PALM BEACH CODE, TENANT SPACE NUMBERS SHALL BE
 NO LESS THA 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 06.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE ENTRY
 CANOPY.
  
 07.A DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL
 BE SELF-CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH
 7.2.1.8.2 OF NFPA 101.
  
 08.COMMERCIAL COOKING EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AS WELL AS
 THE HOOD SUPPRESSION SYSTEM.
  
 09.SPECIFY INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH
 MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL
 ASSEMBLY AREA HAVING AN OCCUPANT LOAD S OF MORE THAN
 300.
  
 10.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASSII.
  
 11.THE 2002 EDITION NFPA 13 SHALL BE BE REFERENCED
 FOR THE FIRE SPRINKLER INSTALLATION AND/RE-MODEL.
  
 12.THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED
 FOR THE INSTALLATION/RE-MODEL OF THE FIRE ALARM
 SYSTEM.
  
 13.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.AMEND FIRE ALARM
 GENERAL NOTE 6 ON SHEET F1.1 AND ALSO THE FIRE ALARM
 SEQUENCE OF OPERATIONS ON SHEET F2.1 SECTION 16C 2-3.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLAN OR IN THE
 SPECIFICATIONS) EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722