Date |
Text |
2007-09-24 17:57:21 | 2007-09-24 17:57:21 |
| |
| |
| ** DENIED** |
| |
| KONA GRILL |
| |
| |
| 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON |
| PLANS. |
| PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE |
| SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| ** PLANS INDICATE THE 2004 FLORIDA ELECTRICAL CODE. |
| |
| 2) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON |
| TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE MISSING |
| PRINTED INFORMATION ALONG WITH MISSING LICENSE |
| INFORMATION. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004. |
| PLEASE ALSO SEE FLORIDA STATUES 481.219 FOR MISSING |
| CERTIFICATE OF AUTHORIZATION NUMBER ALSO KNOWN AS FIRM |
| LICENSE NUMBER. |
| PLEASE BE SURE THE PRINTED NAME IS ALSO STATED. |
| ** THIS IS REQUIRED FOR ALL SHEETS WHICH CONTAIN THE |
| TITLE BLOCKS FOR ARIA GROUP ARCHITECTS INC. INFORMATION |
| ON REQUIREMENTS MAY ALSO BE FOUND THROUGH THE STATE OF |
| FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| REGULATION OR FLORIDA BOARD OF ARCHITECT'S LEGAL |
| COUNSEL TO THE BOARD. |
| |
| 3) NOTE: PLEASE SEE ARCHITECTURAL AND OTHER SHEETS SUCH |
| AS *G* SHEETS WHICH WERE NOT DATED WHEN SIGNED AND |
| SEALED. |
| PLEASE SEE ONLY THE FIRST SHEET IN SET WAS SIGNED, |
| DATED AND SEALED AS REQUIRED PER FS 481.221 |
| |
| 4) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS ALSO AS |
| THE *S* SHEETS ARE MISSING THE REQUIRED TITLE BLOCK |
| INFORMATION FOR THE ENGINEERING FIRM. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND |
| FLORIDA STATUTES 471.023 FOR THE REQUIRED CERTIFICATE |
| OF AUTHORIZATION NUMBER. (ALSO KNOWN AS ENGINEERING |
| BUSINESS NUMBER) |
| THIS REQUIRES PRINTED NAME, PRINTED LICENSE NUMBER OF |
| THE DESIGNER AS WELL. |
| |
| 5) NOTE: PLEASE SEE ELECTRICAL SHEETS AS WELL AS ALL |
| MEP SHEETS WHICH ARE MISSING REQUIRED INFORMATION ON |
| TITLE BLOCKS PER THE FAC 61G15-23.002 AND FS 471.023. |
| THIS IS THE SAME INFORMATION AS STATED ABOVE IN NOTE |
| #4. |
| TITLE BLOCKS TO INCLUDE PRINTED NAME OF DESIGNER, |
| PRINTED LICENSE NUMBER AND CA/EB LICENSE NUMBER FOR |
| FIRM. |
| *** THIS IS REQUIRED FOR ALL MEP SHEETS WHETHER OR NOT |
| COMMENT IS MADE BY OTHER TRADE(S). IF THERE ARE ANY |
| QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS |
| OFFICE. INFORMATION ON REQUIREMENTS MAY ALSO BE FOUND |
| THROUGH THE STATE OF FLORIDA DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION OR FLORIDA BOARD OF |
| PROFESSIONAL ENGINEERS. |
| |
| 6) NOTE: PLEASE BE SURE TO PROVIDE THE UNIT/SUITE |
| NUMBER ON TITLE BLOCKS FOR PROJECT. THE BUILDING |
| ADDRESS IS ALREADY ON SHEETS, HOWEVER NEEDS TO CONTAIN |
| UNIT NUMBER. |
| FAC 61G1-16.004, 61G15-23.002, FBC ADMINISTRATIVE |
| SECTION 110.1.2, 106.1.2. |
| |
| 7) NOTE: PLEASE KNOW EVEN AS THE REQUIRED FIRE ALARM |
| SYSTEM WILL BE UNDER A SEPARATE PERMIT THE BASE BUILD |
| OUT PLANS ARE STILL REQUIRED TO SHOW THE MINIMUM |
| DEVICES AND DEVICE LEVELS FOR THE FLORIDA BUILDING CODE |
| CHAPTER 11 FOR ADA. |
| PLEASE SEE 11-4.28.1, .2 AND .3(4) AS THE MINIMUM |
| LEVELS ARE TO BE STATED ON PLANS. |
| THE SYMBOL LEGEND AND F SHEETS DO INDICATE LEVELS |
| HOWEVER MANY DEVICES DO NOT MEET THE MINIMUM LEVELS. |
| PLEASE KNOW IF MULTIPLE LOCATIONS ARE INDEED USING A |
| DEVICE WITH LESS THAN THE MINIMUM THEN PLEASE PROVIDE |
| POINT BY POINT CALCULATIONS ON THE MINIMUM LIGHTING |
| LEVELS FOR CANDELA LEVELS. |
| PLEASE ADJUST FOR THE MINIMUM LEVELS AS REQUIRED IN |
| SECTIONS ABOVE. |
| |
| 8) NOTE: PLEASE SEE THE COLOR CODING AS STATED ON SHEET |
| E5.1 FOR 277/480V NEEDS TO BE BROWN, PURPLE, AND |
| YELLOW. |
| PLEASE KNOW THE NEC ONLY PROVIDE THE IDENTIFICATION OF |
| *ORANGE* FOR HIGH-LEG SYSTEMS. AS THIS SYSTEM DOES NOT |
| CONTAIN A HIGH-LEG AND ALONG WITH THE FACT THE LOCAL |
| COLOR CODING USED IN THIS EXISTING BUILDING IS THE |
| COLOR CODING AS NOTED ABOVE ANY NEW CONDUCTORS WILL |
| REQUIRE THE SAME IDENTIFICATION. PLEASE ADJUST NOTE. |
| NEC 90.4. |
| |
| 9) NOTE: PLEASE SEE THE RISER CONTAINS AN |
| IDENTIFICATION AS EX FROM THE FPL TRANSFORMER TO THE |
| BUILDING SERVICE MAIN. THE EX ON THE RISER NOTES |
| MENTIONS THESE ARE *FEEDERS*. PLEASE CLARIFY THIS |
| IDENTIFICATION AS THE CONDUCTORS AHEAD OF ANY SERVICE |
| MAIN ARE IN FACT *SERVICE ENTRANCE CONDUCTORS* AND |
| WOULD CONTAIN IDENTIFICATION ACCORDINGLY. |
| NEC 100, 215, ETC |
| FBC 106.1.2 ADDITIONAL INFORMATION. |
| |
| 10) NOTE: PLEASE SEE THE CONDUCTORS FROM THE SECONDARY |
| SIDE OF THE TRANSFORMER TO THE LDP ARE NOT LARGE |
| ENOUGH. |
| PLEASE SEE 240.21C2, 240.4, 310.16 AND 110.14 |
| ** THE CODE DOES PERMIT OVER CURRENT PROTECTION TO THE |
| NEXT STANDARD AS LISTED IN 240.6 IN MANY INSTANCES |
| HOWEVER NOT ON THE SECONDARY SIDE OF THE TRANSFORMERS |
| AS THEY ARE REQUIRED TO TERMINATE IN OVER CURRENT |
| PROTECTION WHICH LIMITS THE LOAD ON THE CONDUCTORS. |
| |
| 11) NOTE: PLEASE SEE PANEL *CC* WHICH IS NOTED ON RISER |
| AS BEING FED BY 80AMP OVER CURRENT PROTECTION ON THE |
| CIRCUIT SCHEDULE, HOWEVER THE RISER INDICATES 125AMP |
| OVER CURRENT PROTECTION ON PANEL LDP WHICH DOES NOT |
| CORRELATE. |
| PLEASE COORDINATE AND ADJUST PLANS. |
| FBC 106.1.2, 106.1.3 ADMIN FOR COORDINATION. |
| |
| 12) NOTE: PLEASE CLARIFY WHERE AND HOW TRACK LIGHTING |
| LOADS FOR THE LOAD CALCULATIONS HAVE BEEN FIGURED PER |
| 220.43B. |
| |
| 13) NOTE: PLEASE SEE 210.8B2 AS PROTECTION OF ALL |
| RECEPTACLES IN KITCHENS ARE REQUIRED TO CONTAIN GFCI |
| PROTECTION. THIS IS FOR ALL 15 AND 20AMP RECEPTACLES |
| WHETHER OR NOT THEY ARE FEEDING THE COUNTER SPACES. THE |
| PLANS DO INDICATE A NOTE WHICH MENTIONS THIS HOWEVER |
| THERE ARE NUMEROUS CIRCUITS ON PANEL SCHEDULES WHICH DO |
| NOT INDICATE THE DESIGNATION FOR GF TYPE BREAKERS WHICH |
| IS NOTED ON LEGEND ON PANEL SCHEDULE. |
| PLEASE SEE SOME ARE NOTED AS GFEP FOR GROUND FAULT |
| EQUIPMENT PROTECTION HOWEVER PLEASE KNOW THAT THE CLASS |
| OF GROUND FAULT PROTECTION IS NOT THAT FOR EQUIPMENT |
| BUT FOR PERSONNEL. |
| PLEASE SEE FOR EXAMPLE A FEW CIRCUITS MISSING REQUIRED |
| PROTECTION: |
| KP1-16, KP1-31, KP2-22, KP2-15. THIS IS ONLY A FEW AS |
| NOTED FOR EXAMPLE. |
| |
| 14) NOTE: PLEASE SEE MISSING SOME INFORMATION FOR |
| COMPLIANCE TO FBC CHAPTER 13. |
| THERE IS NOT ENOUGH INFORMATION FOR LIGHTING CONTROLS |
| AT THIS TIME. |
| PLEASE SEE MISSING INFORMATION FOR LIGHTING CONTROLS OF |
| MAIN DINING AREAS AND OTHER SEPARATE SPACES PER |
| 13-415.1.ABC .1.1, .1.2 AND .1.3. |
| PLEASE SEE SOME OCCUPANCY DEVICES ARE SHOWN FOR SOME |
| AREAS AND TWO CONTACTORS ARE SHOWN FOR SOME EXTERIOR |
| LIGHTING AND KITCHEN PREP AREAS HOWEVER MISSING |
| INFORMATION AND CONTROLS FOR OTHER SPACES INCLUDING |
| SEPARATE SPACES WHICH CONTAIN FLOOR TO CEILING HEIGHT |
| PARTITIONS (BATHROOMS) AND ACCENT LIGHTING. |
| PLEASE PROVIDE LOCATIONS FOR ALL DEVICES OR SYSTEMS. |
| SECTION 13-415.1.ABC.1.1, .1.2 REQUIRES THE OCCUPANT TO |
| SEE THE LIGHTING IN WHICH IS BEING OVER RIDDEN OR |
| CONTROLLED. THERE IS AN EXCEPTION AND IF USING THE |
| EXCEPTION FOR PILOT LIGHTS ETC PLEASE INDICATE AND |
| PROVIDE DETAIL. |
| PLEASE PROVIDE SCHEDULING OF SYSTEM OR INFORMATION ON |
| OTHER DEVICES. |
| PLEASE BE SURE TO PROVIDE ALL MAXIMUM OVER RIDE TIMES |
| ON OTHER DEVICES INSTALLED. THIS WAS DONE FOR THE |
| DEVICES ALREADY ON PLANS. |
| |
| 15) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.B, |
| 13-415.1.C, 13-415.2. |
| A)PLEASE SEE MECHANICAL REVIEW COMMENTS ALSO WITH |
| RESPECT TO THE *METHOD* OF CALCULATIONS BEING |
| SUBMITTED. PLEASE CLARIFY HOW *A* IS BEING USED WHEN |
| THIS IS NOT A WHOLE BUILDING. |
| METHOD *A* CLEARLY STATES *WHOLE BUILDING METHOD*. |
| |
| B) PLEASE COORDINATE ALL LIGHTING ON THE ENERGY |
| CALCULATIONS SPECIFICALLY THE INPUT DATA REPORT WITH |
| THE PLANS. |
| PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED MINIMUM |
| LOADS/FIGURES TO BE USED FOR TRACK LIGHTING. PLEASE SEE |
| THE MINIMUM FOR LINE VOLTAGE TRACK IS BASED ON THE |
| NUMBER OF FIXTURES AT THE WATTAGE OF EACH OR THE TOTAL |
| LINEAR FT OF TRACK AT 30VA PER FT, WHICH EVER IS |
| GREATER. |
| PLEASE ALSO SEE THE ANY LOW VOLTAGE TRACK IS BASED ON |
| THE AVAILABLE VA OF THE TRANSFORMER. |
| PLEASE BE SURE TO COMPLETE PLANS WITH ALL INFORMATION |
| EACH OF THE TRANSFORMERS. |
| PLEASE SEE THE PLANS SEEM TO INDICATE A *T* IN A SQUARE |
| BOX FOR WHAT IS BEING ASSUMED AS THE LOW VOLTAGE |
| TRANSFORMERS. PLEASE CLARIFY THIS AS THE SYMBOL LEGEND |
| ON THE MEP1.0 SHEET DOES NOT CONTAIN THIS DESIGNATION. |
| C) PLEASE COORDINATE ALL OTHER LIGHTING FIXTURES, |
| WATTAGE AND METHOD OF CONTROLS ON THE INPUT DATA |
| REPORT. THE FIXTURE LEGEND ON PLANS INDICATES A CERTAIN |
| WATTAGE AND THE IDR INDICATES ANOTHER. |
| EXAMPLE, PLEASE SEE TYPE N-2 FIXTURE ON E1.1 WHICH IS |
| SHOWN LISTED FOR THE OFFICE, MECHANICAL ROOM AND LIQUOR |
| STORAGE. THIS SAME FIXTURE N-2 IS LISTED AS 96VA/WATTS |
| ON THE FIXTURE LEGEND ON SHEET E4.1, AND YET THE IDR |
| LIST THIS SAME FIXTURE AS 84VA AND 64VA? PLEASE SEE TWO |
| DIFFERENT VA LISTINGS FOR THE SAME FIXTURE. (MECHANICAL |
| ROOM/OFFICE) |
| PLEASE SEE THIS IS ONLY ONE LOCATION IN QUESTION. |
| PLEASE BE SURE TO SEE PART *B* OF THIS COMMENT ABOVE AS |
| THE TRACK LIGHTING LOADS ON THE CALCULATIONS WILL NEED |
| ADJUSTING. |
| |
| D) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE |
| REQUIRED TO FILL OUT WITH COMPLETED INFORMATION ON THE |
| CERTIFICATION SHEETS ALONG WITH BEING SIGNED, DATED AND |
| SEALED BY THE RESPECTIVE RESPONSIBLE DESIGNERS OF |
| RECORD. |
| PLEASE SEE NEITHER COPY SUBMITTED CONTAIN THIS REQUIRED |
| INFORMATION ON THE *CERTIFICATION SHEET* AS REQUIRED. |
| PLEASE SEE ONLY ONE COPY ACTUALLY CONTAINED ANY |
| SIGNATURES AND SEALS. IN FACT THE SECOND SET OF |
| CALCULATIONS WERE *PHOTO-COPIES* OF THE FIRST SET. |
| PLEASE SEE FLORIDA BUILDING CODE 13-101.1.1.1, FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES |
| 471.025. |
| PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON |
| SHEET. |
| |
| 16) NOTE: PLEASE PROVIDE THE MINIMUM DESIGNATED EGRESS |
| PATHS AND MINIMUM PHOTO-METRIC LEVELS FOR THESE SAME |
| EGRESS DESIGNATION PATHS AS REQUIRED PER NFPA-101 7.8 |
| AND 7.9. |
| PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004. |
| FBC ADMIN SECTION106.1.2, 106.3.5.1.2 |
| |
| 17) NOTE: PLEASE CLARIFY LIGHTING NOTE #2 WITH RESPECT |
| TO *DIMMING* LIGHTING IN BATHROOMS. |
| LS 101 7.8. |
| FBC 106.1.2 |
| |
| 18) NOTE: PLEASE CLARIFY HOW PANEL *CC* MEETS 110.26, |
| 110.11, 240.24D, 110.3, 90.7. |
| PLEASE PROVIDE MORE INFORMATION ON CLEARANCES FOR |
| EQUIPMENT AND IF THIS PANEL IS LOCATED NEAR FLOOR WHICH |
| IN A KITCHEN WOULD PLACE THIS PANEL NOT ONLY IN A WET |
| AREA BUT ALSO NEAR DETERIORATING FACTORS IF NOT LISTED |
| FOR THE LOCATION OR ENVIRONMENT INSTALLED. |
| FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| |
| 19) NOTE: PLEASE CLARIFY HOW THE LOAD IN THE PANEL |
| SCHEDULE ON SHEET E3.1 IS LOWER THAN THE LOAD ON THE |
| EQUIPMENT PLANS FOR THE SAME PANEL. |
| PLEASE COORDINATE. |
| 240, 408.4, 220, 215, ETC. |
| FBC 106.1.2 COORDINATION. |
| |
| 20) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE |
| ONLY. ALL LOW VOLTAGE SYSTEMS SUCH AS PHONE, CATV, AND |
| DATA ETC ARE REQUIRED TO BE UNDER SEPARATE PERMITS. THE |
| PLANS MAY CONTAIN THIS LOW VOLTAGE INFORMATION AND ANY |
| LV PERMIT APPLICATIONS MAY REFERENCE THE BASE PLANS |
| ONCE ISSUED FOR PERMIT. |
| ANY LOW VOLTAGE NOT INCLUDED ON BASE BUILD OUT PLANS |
| WILL REQUIRE SEPARATE PLANS. |
| IF THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS REVIEWER. |
| |
| 21) NOTE: PLEASE KNOW AS PLANS ARE *PROVIDE PROVIDER* |
| STAMPED AND REVIEWED PER FS553.791, PLANS MAY NOT BE |
| STAMPED WITH *REDLINES* OR *PROVISOS* FOR CONDITIONS OF |
| PERMIT ISSUANCE. |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |