Plan Review Notes
Plan Review Notes For Permit 07090648
Permit Number 07090648
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-24 17:57:212007-09-24 17:57:21
  
  
 ** DENIED**
  
 KONA GRILL
  
  
 1) NOTE: PLEASE STATE THE FOLLOWING RELEVANT CODES ON
 PLANS.
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLANS INDICATE THE 2004 FLORIDA ELECTRICAL CODE.
  
 2) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE MISSING
 PRINTED INFORMATION ALONG WITH MISSING LICENSE
 INFORMATION.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004.
 PLEASE ALSO SEE FLORIDA STATUES 481.219 FOR MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER ALSO KNOWN AS FIRM
 LICENSE NUMBER.
 PLEASE BE SURE THE PRINTED NAME IS ALSO STATED.
 ** THIS IS REQUIRED FOR ALL SHEETS WHICH CONTAIN THE
 TITLE BLOCKS FOR ARIA GROUP ARCHITECTS INC. INFORMATION
 ON REQUIREMENTS MAY ALSO BE FOUND THROUGH THE STATE OF
 FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION OR FLORIDA BOARD OF ARCHITECT'S LEGAL
 COUNSEL TO THE BOARD.
  
 3) NOTE: PLEASE SEE ARCHITECTURAL AND OTHER SHEETS SUCH
 AS *G* SHEETS WHICH WERE NOT DATED WHEN SIGNED AND
 SEALED.
 PLEASE SEE ONLY THE FIRST SHEET IN SET WAS SIGNED,
 DATED AND SEALED AS REQUIRED PER FS 481.221
  
 4) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS ALSO AS
 THE *S* SHEETS ARE MISSING THE REQUIRED TITLE BLOCK
 INFORMATION FOR THE ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023 FOR THE REQUIRED CERTIFICATE
 OF AUTHORIZATION NUMBER. (ALSO KNOWN AS ENGINEERING
 BUSINESS NUMBER)
 THIS REQUIRES PRINTED NAME, PRINTED LICENSE NUMBER OF
 THE DESIGNER AS WELL.
  
 5) NOTE: PLEASE SEE ELECTRICAL SHEETS AS WELL AS ALL
 MEP SHEETS WHICH ARE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS PER THE FAC 61G15-23.002 AND FS 471.023.
 THIS IS THE SAME INFORMATION AS STATED ABOVE IN NOTE
 #4.
 TITLE BLOCKS TO INCLUDE PRINTED NAME OF DESIGNER,
 PRINTED LICENSE NUMBER AND CA/EB LICENSE NUMBER FOR
 FIRM.
 *** THIS IS REQUIRED FOR ALL MEP SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S). IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE. INFORMATION ON REQUIREMENTS MAY ALSO BE FOUND
 THROUGH THE STATE OF FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION OR FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
  
 6) NOTE: PLEASE BE SURE TO PROVIDE THE UNIT/SUITE
 NUMBER ON TITLE BLOCKS FOR PROJECT. THE BUILDING
 ADDRESS IS ALREADY ON SHEETS, HOWEVER NEEDS TO CONTAIN
 UNIT NUMBER.
 FAC 61G1-16.004, 61G15-23.002, FBC ADMINISTRATIVE
 SECTION 110.1.2, 106.1.2.
  
 7) NOTE: PLEASE KNOW EVEN AS THE REQUIRED FIRE ALARM
 SYSTEM WILL BE UNDER A SEPARATE PERMIT THE BASE BUILD
 OUT PLANS ARE STILL REQUIRED TO SHOW THE MINIMUM
 DEVICES AND DEVICE LEVELS FOR THE FLORIDA BUILDING CODE
 CHAPTER 11 FOR ADA.
 PLEASE SEE 11-4.28.1, .2 AND .3(4) AS THE MINIMUM
 LEVELS ARE TO BE STATED ON PLANS.
 THE SYMBOL LEGEND AND F SHEETS DO INDICATE LEVELS
 HOWEVER MANY DEVICES DO NOT MEET THE MINIMUM LEVELS.
 PLEASE KNOW IF MULTIPLE LOCATIONS ARE INDEED USING A
 DEVICE WITH LESS THAN THE MINIMUM THEN PLEASE PROVIDE
 POINT BY POINT CALCULATIONS ON THE MINIMUM LIGHTING
 LEVELS FOR CANDELA LEVELS.
 PLEASE ADJUST FOR THE MINIMUM LEVELS AS REQUIRED IN
 SECTIONS ABOVE.
  
 8) NOTE: PLEASE SEE THE COLOR CODING AS STATED ON SHEET
 E5.1 FOR 277/480V NEEDS TO BE BROWN, PURPLE, AND
 YELLOW.
 PLEASE KNOW THE NEC ONLY PROVIDE THE IDENTIFICATION OF
 *ORANGE* FOR HIGH-LEG SYSTEMS. AS THIS SYSTEM DOES NOT
 CONTAIN A HIGH-LEG AND ALONG WITH THE FACT THE LOCAL
 COLOR CODING USED IN THIS EXISTING BUILDING IS THE
 COLOR CODING AS NOTED ABOVE ANY NEW CONDUCTORS WILL
 REQUIRE THE SAME IDENTIFICATION. PLEASE ADJUST NOTE.
 NEC 90.4.
  
 9) NOTE: PLEASE SEE THE RISER CONTAINS AN
 IDENTIFICATION AS EX FROM THE FPL TRANSFORMER TO THE
 BUILDING SERVICE MAIN. THE EX ON THE RISER NOTES
 MENTIONS THESE ARE *FEEDERS*. PLEASE CLARIFY THIS
 IDENTIFICATION AS THE CONDUCTORS AHEAD OF ANY SERVICE
 MAIN ARE IN FACT *SERVICE ENTRANCE CONDUCTORS* AND
 WOULD CONTAIN IDENTIFICATION ACCORDINGLY.
 NEC 100, 215, ETC
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 10) NOTE: PLEASE SEE THE CONDUCTORS FROM THE SECONDARY
 SIDE OF THE TRANSFORMER TO THE LDP ARE NOT LARGE
 ENOUGH.
 PLEASE SEE 240.21C2, 240.4, 310.16 AND 110.14
 ** THE CODE DOES PERMIT OVER CURRENT PROTECTION TO THE
 NEXT STANDARD AS LISTED IN 240.6 IN MANY INSTANCES
 HOWEVER NOT ON THE SECONDARY SIDE OF THE TRANSFORMERS
 AS THEY ARE REQUIRED TO TERMINATE IN OVER CURRENT
 PROTECTION WHICH LIMITS THE LOAD ON THE CONDUCTORS.
  
 11) NOTE: PLEASE SEE PANEL *CC* WHICH IS NOTED ON RISER
 AS BEING FED BY 80AMP OVER CURRENT PROTECTION ON THE
 CIRCUIT SCHEDULE, HOWEVER THE RISER INDICATES 125AMP
 OVER CURRENT PROTECTION ON PANEL LDP WHICH DOES NOT
 CORRELATE.
 PLEASE COORDINATE AND ADJUST PLANS.
 FBC 106.1.2, 106.1.3 ADMIN FOR COORDINATION.
  
 12) NOTE: PLEASE CLARIFY WHERE AND HOW TRACK LIGHTING
 LOADS FOR THE LOAD CALCULATIONS HAVE BEEN FIGURED PER
 220.43B.
  
 13) NOTE: PLEASE SEE 210.8B2 AS PROTECTION OF ALL
 RECEPTACLES IN KITCHENS ARE REQUIRED TO CONTAIN GFCI
 PROTECTION. THIS IS FOR ALL 15 AND 20AMP RECEPTACLES
 WHETHER OR NOT THEY ARE FEEDING THE COUNTER SPACES. THE
 PLANS DO INDICATE A NOTE WHICH MENTIONS THIS HOWEVER
 THERE ARE NUMEROUS CIRCUITS ON PANEL SCHEDULES WHICH DO
 NOT INDICATE THE DESIGNATION FOR GF TYPE BREAKERS WHICH
 IS NOTED ON LEGEND ON PANEL SCHEDULE.
 PLEASE SEE SOME ARE NOTED AS GFEP FOR GROUND FAULT
 EQUIPMENT PROTECTION HOWEVER PLEASE KNOW THAT THE CLASS
 OF GROUND FAULT PROTECTION IS NOT THAT FOR EQUIPMENT
 BUT FOR PERSONNEL.
 PLEASE SEE FOR EXAMPLE A FEW CIRCUITS MISSING REQUIRED
 PROTECTION:
 KP1-16, KP1-31, KP2-22, KP2-15. THIS IS ONLY A FEW AS
 NOTED FOR EXAMPLE.
  
 14) NOTE: PLEASE SEE MISSING SOME INFORMATION FOR
 COMPLIANCE TO FBC CHAPTER 13.
 THERE IS NOT ENOUGH INFORMATION FOR LIGHTING CONTROLS
 AT THIS TIME.
 PLEASE SEE MISSING INFORMATION FOR LIGHTING CONTROLS OF
 MAIN DINING AREAS AND OTHER SEPARATE SPACES PER
 13-415.1.ABC .1.1, .1.2 AND .1.3.
 PLEASE SEE SOME OCCUPANCY DEVICES ARE SHOWN FOR SOME
 AREAS AND TWO CONTACTORS ARE SHOWN FOR SOME EXTERIOR
 LIGHTING AND KITCHEN PREP AREAS HOWEVER MISSING
 INFORMATION AND CONTROLS FOR OTHER SPACES INCLUDING
 SEPARATE SPACES WHICH CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS (BATHROOMS) AND ACCENT LIGHTING.
 PLEASE PROVIDE LOCATIONS FOR ALL DEVICES OR SYSTEMS.
 SECTION 13-415.1.ABC.1.1, .1.2 REQUIRES THE OCCUPANT TO
 SEE THE LIGHTING IN WHICH IS BEING OVER RIDDEN OR
 CONTROLLED. THERE IS AN EXCEPTION AND IF USING THE
 EXCEPTION FOR PILOT LIGHTS ETC PLEASE INDICATE AND
 PROVIDE DETAIL.
 PLEASE PROVIDE SCHEDULING OF SYSTEM OR INFORMATION ON
 OTHER DEVICES.
 PLEASE BE SURE TO PROVIDE ALL MAXIMUM OVER RIDE TIMES
 ON OTHER DEVICES INSTALLED. THIS WAS DONE FOR THE
 DEVICES ALREADY ON PLANS.
  
 15) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.B,
 13-415.1.C, 13-415.2.
 A)PLEASE SEE MECHANICAL REVIEW COMMENTS ALSO WITH
 RESPECT TO THE *METHOD* OF CALCULATIONS BEING
 SUBMITTED. PLEASE CLARIFY HOW *A* IS BEING USED WHEN
 THIS IS NOT A WHOLE BUILDING.
 METHOD *A* CLEARLY STATES *WHOLE BUILDING METHOD*.
  
 B) PLEASE COORDINATE ALL LIGHTING ON THE ENERGY
 CALCULATIONS SPECIFICALLY THE INPUT DATA REPORT WITH
 THE PLANS.
 PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED MINIMUM
 LOADS/FIGURES TO BE USED FOR TRACK LIGHTING. PLEASE SEE
 THE MINIMUM FOR LINE VOLTAGE TRACK IS BASED ON THE
 NUMBER OF FIXTURES AT THE WATTAGE OF EACH OR THE TOTAL
 LINEAR FT OF TRACK AT 30VA PER FT, WHICH EVER IS
 GREATER.
 PLEASE ALSO SEE THE ANY LOW VOLTAGE TRACK IS BASED ON
 THE AVAILABLE VA OF THE TRANSFORMER.
 PLEASE BE SURE TO COMPLETE PLANS WITH ALL INFORMATION
 EACH OF THE TRANSFORMERS.
 PLEASE SEE THE PLANS SEEM TO INDICATE A *T* IN A SQUARE
 BOX FOR WHAT IS BEING ASSUMED AS THE LOW VOLTAGE
 TRANSFORMERS. PLEASE CLARIFY THIS AS THE SYMBOL LEGEND
 ON THE MEP1.0 SHEET DOES NOT CONTAIN THIS DESIGNATION.
 C) PLEASE COORDINATE ALL OTHER LIGHTING FIXTURES,
 WATTAGE AND METHOD OF CONTROLS ON THE INPUT DATA
 REPORT. THE FIXTURE LEGEND ON PLANS INDICATES A CERTAIN
 WATTAGE AND THE IDR INDICATES ANOTHER.
 EXAMPLE, PLEASE SEE TYPE N-2 FIXTURE ON E1.1 WHICH IS
 SHOWN LISTED FOR THE OFFICE, MECHANICAL ROOM AND LIQUOR
 STORAGE. THIS SAME FIXTURE N-2 IS LISTED AS 96VA/WATTS
 ON THE FIXTURE LEGEND ON SHEET E4.1, AND YET THE IDR
 LIST THIS SAME FIXTURE AS 84VA AND 64VA? PLEASE SEE TWO
 DIFFERENT VA LISTINGS FOR THE SAME FIXTURE. (MECHANICAL
 ROOM/OFFICE)
 PLEASE SEE THIS IS ONLY ONE LOCATION IN QUESTION.
 PLEASE BE SURE TO SEE PART *B* OF THIS COMMENT ABOVE AS
 THE TRACK LIGHTING LOADS ON THE CALCULATIONS WILL NEED
 ADJUSTING.
  
 D) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ARE
 REQUIRED TO FILL OUT WITH COMPLETED INFORMATION ON THE
 CERTIFICATION SHEETS ALONG WITH BEING SIGNED, DATED AND
 SEALED BY THE RESPECTIVE RESPONSIBLE DESIGNERS OF
 RECORD.
 PLEASE SEE NEITHER COPY SUBMITTED CONTAIN THIS REQUIRED
 INFORMATION ON THE *CERTIFICATION SHEET* AS REQUIRED.
 PLEASE SEE ONLY ONE COPY ACTUALLY CONTAINED ANY
 SIGNATURES AND SEALS. IN FACT THE SECOND SET OF
 CALCULATIONS WERE *PHOTO-COPIES* OF THE FIRST SET.
 PLEASE SEE FLORIDA BUILDING CODE 13-101.1.1.1, FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025.
 PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON
 SHEET.
  
 16) NOTE: PLEASE PROVIDE THE MINIMUM DESIGNATED EGRESS
 PATHS AND MINIMUM PHOTO-METRIC LEVELS FOR THESE SAME
 EGRESS DESIGNATION PATHS AS REQUIRED PER NFPA-101 7.8
 AND 7.9.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004.
 FBC ADMIN SECTION106.1.2, 106.3.5.1.2
  
 17) NOTE: PLEASE CLARIFY LIGHTING NOTE #2 WITH RESPECT
 TO *DIMMING* LIGHTING IN BATHROOMS.
 LS 101 7.8.
 FBC 106.1.2
  
 18) NOTE: PLEASE CLARIFY HOW PANEL *CC* MEETS 110.26,
 110.11, 240.24D, 110.3, 90.7.
 PLEASE PROVIDE MORE INFORMATION ON CLEARANCES FOR
 EQUIPMENT AND IF THIS PANEL IS LOCATED NEAR FLOOR WHICH
 IN A KITCHEN WOULD PLACE THIS PANEL NOT ONLY IN A WET
 AREA BUT ALSO NEAR DETERIORATING FACTORS IF NOT LISTED
 FOR THE LOCATION OR ENVIRONMENT INSTALLED.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 19) NOTE: PLEASE CLARIFY HOW THE LOAD IN THE PANEL
 SCHEDULE ON SHEET E3.1 IS LOWER THAN THE LOAD ON THE
 EQUIPMENT PLANS FOR THE SAME PANEL.
 PLEASE COORDINATE.
 240, 408.4, 220, 215, ETC.
 FBC 106.1.2 COORDINATION.
  
 20) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE
 ONLY. ALL LOW VOLTAGE SYSTEMS SUCH AS PHONE, CATV, AND
 DATA ETC ARE REQUIRED TO BE UNDER SEPARATE PERMITS. THE
 PLANS MAY CONTAIN THIS LOW VOLTAGE INFORMATION AND ANY
 LV PERMIT APPLICATIONS MAY REFERENCE THE BASE PLANS
 ONCE ISSUED FOR PERMIT.
 ANY LOW VOLTAGE NOT INCLUDED ON BASE BUILD OUT PLANS
 WILL REQUIRE SEPARATE PLANS.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT
 HESITATE IN CONTACTING THIS REVIEWER.
  
 21) NOTE: PLEASE KNOW AS PLANS ARE *PROVIDE PROVIDER*
 STAMPED AND REVIEWED PER FS553.791, PLANS MAY NOT BE
 STAMPED WITH *REDLINES* OR *PROVISOS* FOR CONDITIONS OF
 PERMIT ISSUANCE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved