2007-09-25 21:04:28 | |
| KONA GRILL |
| 700 S ROSEMARY AVE SUITE# 100 |
| |
| BUILDING PLAN REVIEW |
| PERMIT: 07090648 |
| ADD: 700 S ROSEMARY AVE# 100 |
| CONT: IN MOTION BUILDERS, INC. |
| TEL: (954)698-0900 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) --- VERY IMPORTANT |
| STATEMENT --- |
| PLEASE DO |
| NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A |
| RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD |
| BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE |
| SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT |
| ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM |
| BEACH ADMINISTRATIVE CODE. |
| |
| 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION |
| DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. 2)SHEET |
| T1.1,CODE ANALYSIS PLEASE UPDATE THE 2004 TO THE 2007 |
| FBC, BUILDING WITH 2007 REVISIONS. |
| |
| 3) SHEET T1.1 TYPE OF BUILDING, PLANS INDICATE THIS TO |
| BE A TYPE IIB PLEASE CORRECT TO A TYPE IB, PLEASE NOTE |
| THAT 700 S ROSEMARY IS CONSIDERED A MIXED USE BUILDING |
| THE PARKING GARAGE IS 5 STORIES AND IS CONSIDERED PART |
| OF THE MERCANTILE AND A2 RESTAURANTS FOUND IN THIS |
| BUILDING. THE LOCATION OF THE ELEVATORS AND STAIRWAY |
| ARE OVER 30? WIDE CREATING ONE LARGE BUILDING. |
| DEFINITIONS:WALKWAY , COVERED. A ROOFED, UNOBSTRUCTED |
| WALKWAY CONNECTING BUILDINGS AND USED AS A MEANS OF |
| TRAVEL BY PERSONS AND WHERE LESS THAN 50 PERCENT OF THE |
| PERIMETER IS ENCLOSED AND THE MAXIMUM WIDTH |
| PERPENDICULAR TO THE DIRECTION OF TRAVEL IS LESS THAN |
| 30 FEET (9144 MM). PLEASE CORRECT THE MINIMUM BUILDING |
| TYPE. |
| |
| 4) SHEET T1.1 SINCE THE MINIMUM BUILDING TYPE HAS |
| INCREASED THE FIRE RESISTANCE RATINGS WILL ALSO |
| INCREASE, SEE TABLE 603. |
| |
| 5) SHEET T1.1 PLEASE CORRECT THE CODE ANALYSIS THIS IS |
| NOT A SINGLE STORY BUILDING AND A 300% INCREASE CAN NOT |
| BE TAKEN, MULTI-STORY BUILDING AND ONLY A 200% INCREASE |
| CAN BE TAKEN. 506.3. |
| |
| 6) THE ARCHITECTURAL SHEETS ARE MISSING THEIR |
| CERTIFICATE OF AUTHORIZATION FOR ARIA GROUP ARCHITECTS |
| INC. 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE |
| TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN |
| ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| AUTHORIZATION |
| NUMBER.ADD THE NUMBER TO EACH SHEET. |
| |
| 7) THE ARCHITECTURAL SHEETS IN THE TITLE BLOCK THE |
| ARCHITECT OF RECORD WHICH SEALED THE PLANS HADN?T |
| PLACED THE PRINTED NAME OF THE DESIGN PROFESSIONAL. |
| 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A |
| REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| MUST: |
| - STATE THE FIRM NAME, ADDRESS AND TELEPHONE |
| NUMBER |
| XX- STATE THE FIRM LICENSE NUMBER |
| - STATE PROJECT NAME OR IDENTIFICATION |
| XX - STATE DATE PREPARED- INCLUDE AN ORIGINAL SIGNATURE |
| AND DATED SEAL, IN THE SET BEING |
| REVIEWED ONLY THE TOP SHEET OF THE |
| ARCHITECTURAL SHEETS HAS A DATE ON THEM. |
| XX - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING |
| THE PLANS. |
| |
| 8) SHEET S0.0 HART, GAUGLER & ASSOCIATES, INC. IS |
| MISSING THEIR CERTIFICATE OF AUTHORIZATION. 471.023 |
| F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK |
| FOR ANY |
| SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER |
| A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, |
| OFFERING ENGINEERING SERVICES, SHALL INCLUDE THE |
| CERTIFICATE OF AUTHORIZATION NUMBER. ADD THE NUMBER TO |
| EACH SHEET. |
| |
| 9) SHEET S0.0 THE ENGINEER OF RECORD HAS NOT: |
| 61G15-23.002(2)FL. ADMIN. CODE. |
| PLANS SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL |
| INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF |
| THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE |
| ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS |
| THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. |
| AND 471.023 F.S.). |
| |
| 10) STRUCTURAL DESIGN CALCULATIONS ARE MISSING TITLE |
| BLOCK INFORMATION AS WELL AS NOT HAVING AN INDEX OF HOW |
| MANY SHEETS ARE IN THIS REPORT. FL S S 471.025 |
| |
| 11) ARCHITECTURAL AS WELL AS STRUCTURAL PLANS INDICATE |
| STRUCTURAL WORK TO BE ACCOMPLISHED UNDER THIS PERMIT. |
| NOTE THIS BUILDING BEING A 5 STORY STRUCTURE WILL |
| REQUIRE A THRESHOLD |
| INSPECTION PLAN AND A THRESHOLD INSPECTOR. |
| |
| 11A)FL S. S. 553.71(7) " THRESHOLD BUILDING" |
| MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCYCLASSIFICATION AS DEFINED IN |
| THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE |
| A SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS |
| ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURALINSPECTION PLAN |
| PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THEENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| 11B) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION |
| SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA |
| STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER |
| INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 11C)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE |
| BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 12) THE STRUCTURAL SHEET S0.0 FOUNDATION DESIGN |
| INDICATES THERE TO BE A GEOTECHNICAL SOILS ENGINEER |
| SHALL VERIFY THAT THE SOILS OF THE DESIGN BEARING |
| CAPACITY HAVE BEEN ENCOUNTERED. 1802.2.1 QUESTIONABLE |
| SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 13) S0.0 WIND DESIGN DOES NOT INDICATE IF THIS IS TAKEN |
| FROM TABLE 1609.6 OR ASCE 7-02, NOTE AGAIN THIS IS A 5 |
| STORY BUILDING NOT A SINGLE STORY BUILDING? |
| |
| 14)SHEET S0.0 INDICATES VARIOUS STANDARDS, EXAMPLE |
| ACI 318 MOST RECENT EDITION, PLEASE SEE CHAPTER 35 |
| WHICH LIST ALL THE STANDARDS AND YEARS THAT ARE |
| REFERENCED IN THE 2004 FBC. |
| |
| 15) S0.0 ALSO HAS STANDARDS FOR THE HIGH VELOCITY |
| HURRICANE ZONE WHICH ARE UNENFORCEABLE EXCEPT DADE & |
| BROWARD COUNTIES PLEASE REMOVE. |
| 16) S0.0 INSPECTIONS REQUIRED, PLEASE UPDATE TO A |
| THRESHOLD INSPECTION PLAN AS PER FL S S 553.7(71). |
| |
| 17)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES |
| (FOR THRESHOLD BUILDINGS (3 COPIES) OF PRODUCT TESTING |
| REPORTS ,MISSING REPORTS ARE AS FOLLOWS: |
| 17A) FIXED WINDOWS, STOREFRONT |
| 17B) GLAZED EXTERIOR SWING DOOR, SINGLE AND PAIRS 17C) |
| DOORS W/ SIDELIGHTS |
| 17D) FOLDING DOOR SYSTEM |
| 17E) HURRICANE SHUTTER, HORIZONTAL ROLLER |
| 17F) TRUSS ANCHOR TYPE HARDWARE |
| 17G) LOUVER |
| 17H) ROOFING ASSEMBLIES W / INSULATION |
| |
| 18) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. |
| |
| 19) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 20) ) SHEET EX1.1 INDICATES POINTS WHERE THE EXIT IS |
| 3?-8? BUT THE WIDTH OF THE EGRESS PATH MAY BE AS LITTLE |
| AS 30? IN SOME AREAS, PLEASE PROVIDE THE EGRESS PATH |
| SHOWING THE FULL 44? WHERE IT SERVES AN OCCUPANT LOAD |
| GREATER THAN 50 AND 36? WHERE REQUIRED FOR LESS THAN |
| 50. 1024.9.1.1 THE MINIMUM WIDTH OF AISLES SERVING |
| SEATING AT TABLES SHALL BE 44 INCHES (1118 MM). |
| EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE SERVING AN |
| OCCUPANT LOAD OF NOT MORE THAN 50. |
| |
| 21) SHEET A6.2 INDICATES A NEW CANOPY WITH WOOD BEAMS |
| AND DECKING. PLEASE REFER BACK TO COMMENT # 3 |
| CLASSIFYING THIS BUILDING AS A TYPE 1B, SEE TABLE 601 |
| ROOF CONSTRUCTION FOOTNOTE ?C?, COMBUSTIBLE |
| WOOD COMPONENTS AND DECKING WILL NOT BE ACCEPTED, |
| UNLESS A 4 HOUR FIRE WALL IS INTRODUCED CREATING A |
| SEPARATE BUILDING. THERE MAY BE OTHER ISSUES THEN WITH |
| THE MEP PLANS AS WELL AS FIRE SPRINKLER AND FIRE |
| ALARM. |
| |
| 22)SHEET A6.3 INDICATES IN VARIOUS DETAILS THE USE OF |
| PLYWOOD SUB-SHEATHINGWITHIN EXTERIOR NON-LOAD BEARING |
| WALLS. SEE SECTION 603 .1.1(1.2)FIRE RETARDANT |
| ?TREATED WOOD SHALL BE PERMITTED. |
| |
| 23)SHEET A6.3 PLEASE PROVIDE PRODUCT INFORMATION ON |
| THE STUCCO TAPE TO BE USED ON STC-1 WALLS? ADDITIONAL |
| INFORMATION REQUIRED 106.1.2. |
| |
| 24)BUILDING PROVISO:A6.4 DETAIL # 2 & S5.0 FOR A |
| BRUSHED ALUMINUM CANOPY, THIS WILL REQUIRE SHOP |
| DRAWINGS, TO BE UNDER A SEPARATE PERMIT. THIS STRUCTURE |
| DOES NOT MEET THE REQUIREMENTS OF 3105, MUST MEET THE |
| 140 MPH PROVISIONS OF 1609.6. |
| |
| 25) SHEET A3.1/A6.2 BOTH INDICATE A CANOPY WITH ROOF |
| SLOPE AND A DETAIL WITH A CURB OF APPROXIMATELY 3?, IS |
| THERE TO BE ROOF DRAINS SCUPPERS AND OR OVER FLOWS? |
| ADDITIONAL INFORMATION REQUIRED |
| 106.1.2*/ 1503.4 & 1503.6. |
| |
| |
| |
| 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| REQUIREMENT, THE SPECIFIC |
| REQUIREMENT SHALL BE APPLICABLE. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| |
| |
| |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |