2008-07-10 14:14:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN **
 *** DENIED ***
  
 1)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 2) INFORMATION IN THE EQUIPMENT SCHEDULE IS INCORRECT
 (SEE YELLOW HIGH LIGHT ON PLAN). PLEASE CORRECT PER
 2004 FBC 106.1.1.
  
 3) PLEASE BE ADVISED THE CONDENSER UNIT MODEL NUMBER ON
 THE PLAN APPEARS TO BE DISCONTINUED BY THE ARI, IF SO
 PLEASE CORRECT PER 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;