2007-10-11 10:00:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 9A-1 SHOWS R4.2, SEE SECOND
 PAGE OF E-CAL'S TABLE 6C-1 MINIMUM FOR CONCRETE BLOCK
 IS R-5, ALSO SEE 2004 FBC 13-602.1.C.2, PLEASE
 CORRECT.
  
 2) ENERGY CALCULATIONS LINE 10A SHOWS R19, SEE SECOND
 PAGE OF E-CAL'S TABLE 6C-1 MINIMUM FOR ATTIC IS R-30,
 ALSO SEE 2004 FBC 13-604.1.C.2, PLEASE CORRECT.
  
 3) THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER (NELSON MARIN) AND ALSO BY THE OWNER/AGENT,
 SEE 2004 FBC'S 13-103.1.1 AND 13-600.ABC.2.
  
 4) PLEASE CORRECT PLANS PAGE A-1 TO SHOW CORRECTED
 MINIMUM INSULATION VALUES AS STATED ABOVE.
  
 5) MECHANICAL PLAN PAGE M-1 NEEDS TO BE SEALED BY THE
 ENGINEER LUIS A. LOPEZ AS HIS INFORMATION IS IN THE
 TITLE BLOCK, SEE FAC 61G15-23.002.
  
 6) PLEASE SHOW THE LOCATION OF CONDENSER UNIT #2 ON
 MECHANICAL PLAN PAGE M-1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]