Plan Review Notes For Permit 07090639 |
Permit Number |
07090639 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-10-11 10:00:22 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ENERGY CALCULATIONS LINE 9A-1 SHOWS R4.2, SEE SECOND | | PAGE OF E-CAL'S TABLE 6C-1 MINIMUM FOR CONCRETE BLOCK | | IS R-5, ALSO SEE 2004 FBC 13-602.1.C.2, PLEASE | | CORRECT. | | | | 2) ENERGY CALCULATIONS LINE 10A SHOWS R19, SEE SECOND | | PAGE OF E-CAL'S TABLE 6C-1 MINIMUM FOR ATTIC IS R-30, | | ALSO SEE 2004 FBC 13-604.1.C.2, PLEASE CORRECT. | | | | 3) THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE | | PREPARER (NELSON MARIN) AND ALSO BY THE OWNER/AGENT, | | SEE 2004 FBC'S 13-103.1.1 AND 13-600.ABC.2. | | | | 4) PLEASE CORRECT PLANS PAGE A-1 TO SHOW CORRECTED | | MINIMUM INSULATION VALUES AS STATED ABOVE. | | | | 5) MECHANICAL PLAN PAGE M-1 NEEDS TO BE SEALED BY THE | | ENGINEER LUIS A. LOPEZ AS HIS INFORMATION IS IN THE | | TITLE BLOCK, SEE FAC 61G15-23.002. | | | | 6) PLEASE SHOW THE LOCATION OF CONDENSER UNIT #2 ON | | MECHANICAL PLAN PAGE M-1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|