| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE |
| NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| OTHERWISE NOTED. |
| |
| 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| IS NEW OR EXISTING. IF NEW , PROVIDE AN AIC RATING, AND |
| LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| WITH ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A |
| RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND |
| TYPE. |
| |
| 2} NOTE #20 REQUIRES # 12 CONDUCTORS MINIMUM FOR THIS |
| PROJECT. THERE ARE #14 CONDUCTORS ON THE PANEL |
| SCHEDULE, CLARIFY TO AVOID CONFUSION DURING |
| CONSTRUCTION. 106.1.3. |
| |
| 3} THE NOTE IN THE PANEL SCHEDULE INDICATES THE PANEL |
| IS LOCATED IN THE GARAGE, THERE IS NO GARAGE ON THE |
| FLOOR PLAN. THERE IS A CARPORT SHOWN ON THE SURVEY. |
| CLARIFY ALL EQUIPMENT LOCATIONS.106.1.3. |
| |
| 4} THERE ARE TWO "BATH CIRCUITS" LISTED IN THE |
| SCHEDULE, ONE, CIRCUIT# 22, IS ON A 15 AMP BREAKER. |
| THAT CIRCUIT COULD NOT BE USED FOR THE REQUIRED GFCI AS |
| 210.11(C)(3) REQUIRES A 20 AMP CIRCUIT.PER 408.4, "THE |
| IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO ALLOW |
| EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS." |
| CLARIFY CIRCUIT DESIGNATIONS. |
| |
| 5} THE KITCHEN COUNTERTOP RECEPTACLE ADJACENT TO THE |
| PENINSULAR MUST BE GFCI PER 210.8(A)(6), INDICATE SAME |
| ON THE PLAN. |
| |
| 6} A RECEPTACLE IS REQUIRED AT THE FRONT OF THE |
| RESIDENCE PER 210.52(E). |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |