Date Text
2007-09-24 10:42:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS NEED THE JOB ADDRESS ON THEM, SEE W.P.B.
 AMEND. 106.1.3.
  
 2) PLANS NEED AN EQUIPMENT SCHEDULE ON THEM (MAKE,
 MODEL NO; SEER, TOTAL & SENSIBLE BTU'S, HEATER KW,
 ETC.) SEE W.P.B. AMEND. 106.3.5.4 (10).
  
 3) PLANS NEED THE SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN, SEE W.P.B. AMEND. 106.1.3.
  
 4) PLANS NEED TO SHOW THE LOCATION OF ALL SUPPLY AND
 RETURN AIR GRILLS, AND DUCT WORK.
  
 5) SHOW HOW RETURN AIR IS GETTING BACK TO THE AIR
 HANDLER.
  
 6) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 7) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  