 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND RECORD RETENTION PER
 106.1.3 FBC AS AMENDED.
  
 3} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 EQUIPMENT TO BE INSTALLED.
  
 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  