Plan Review Notes For Permit 07090635 |
Permit Number |
07090635 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-09-24 16:10:52 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | (3). | | | | 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | FOR CLARITY IN THE FIELD AND RECORD RETENTION PER | | 106.1.3 FBC AS AMENDED. | | | | 3} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE | | EQUIPMENT TO BE INSTALLED. | | | | 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | REVIEW PER 106.1 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|