2007-10-04 15:53:24 | DENIED |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. THE SUBMITTED GAS ISOMETRIC RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN AND IS TO LIGHT TO READ. PER |
| FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL.PLEASE REFERENCE THE RED LINE |
| CORRECTIONS OF THE GAS RISER DIAGRAM THAT REFLECTS THE |
| FOOR PLAN ON THE RESUBMITTAL. |
| |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE INDICATED |
| CORRESPONDING LENGTHS. PLEASE CORRECT THIS ON THE |
| RESUBMITTAL. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THIS COMMENT GOES ALONG WITH COMMENT NUMBER 2. |
| |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. LP GAS SPECIFY 10 |
| PSI OR 11 INCH W.C.. |
| |
| 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |