2007-11-06 12:11:31 | ** DENIED 2ND REVIEW ** |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG |
| WITH SOME NEW COMMENTS ARE IN NEED OF BEING ADDRESSED. |
| |
| 1) NOTE: PLEASE SEE THE CODES AND NOTES ON PLANS STILL |
| NEED TO BE CORRECTED. PLEASE SEE FOR EXAMPLE: THERE ARE |
| STILL CODE NOTES ON PLANS TO THE SOUTH FLORIDA BUILDING |
| CODE WHICH HAS NOT BEEN IN EFFECT SINCE MARCH 02. |
| PLEASE SEE THE ELECTRICAL LOADCALCULATIONS ETC. |
| SHEET E.3 |
| FBC 106.1.2 |
| |
| |
| 2) NOTE: PLEASE SEE SMOKE DETECTOR NOTES ON PLANS STILL |
| CALL FOR RESIDENTIAL INSTALLATIONS. |
| ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS |
| NOTES AS THESE ARE REFERENCING DWELLING UNIT |
| REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION. |
| CALLS FOR ARC FAULT PROTECTION ETC. |
| PLEASE ADJUST NOTES. |
| FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND |
| RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES. |
| |
| 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULES. PLEASE CORRELATE |
| CIRCUITING PLANS ALSO. PLEASE SEE ROOMS WHERE |
| CIRCUITING TO SPECIALTY LIGHTING AND CIRCUIT NUMBER AND |
| PANEL IS BEING REFLECTED HOWEVER THESE DO NOT CORRELATE |
| WITH THE SAME ROOMS. |
| PLEASE SEE FOR EXAMPLE, SWITCH SHOWS A GCA -26, YET THE |
| SAME ROOM SHOWS GCB 28. THIS IS THE SAME FOR SPA ROOM |
| #1, #2, ETC. |
| PLEASE SEE CIRCUITS WHICH REFERENCE TO A GCH PANEL YET |
| NO GCH PANEL SCHEDULE WAS SUBMITTED. |
| PLEASE SEE THERE ARE SEVERAL OTHER ELECTRICAL OUTLETS |
| ON PLANS WHICH CONTAIN NO CIRCUITING. |
| PLEASE SEE THAT THE PANEL SCHEDULES HAVE ALSO NOT BEEN |
| REVISED. THE CIRCUITS ARE NOT SHOWN SPECIFIC TO ROOMS |
| AND AREAS IN WHICH THEY FEED. PLEASE SEE 408.4,240.4, |
| 310.16. |
| FBC106.1.2, 106.3.5.1.2, 106.5 ETC. |
| |
| |
| 4) NOTE: LIGHTING CONTROL DEVICES ARE NOT SHOWN FOR ALL |
| LIGHTING. EXAMPLE : ALTERNATE SPA ROOM. |
| PLEASE INDICATE LIGHTING CONTROLS PER FBC CHAPTER 13 |
| FOR NEW LIGHTING CONTROL DEVICES BEING INSTALLED. |
| PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3. |
| PLEASE SEE 13-101 |
| PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS |
| SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE |
| TABLE. |
| |
| PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2 |
| ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR |
| *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE |
| NOT LIGHTING REQUIRED. |
| PLEASE EXPLAIN WHERE SOME OF THE LIGHTING ALLOWANCE |
| FIGURES ARE DERIVED. FOR EXAMPLE OFFICE LEVELS NOTED AT |
| 1.5, WHEN THE CODE STATES MAXIMUM AT 1.1. |
| PLEASE PLACE A TOTAL ON THE MAXIMUM ALLOWED COMPARED TO |
| THE MAXIMUM DESIGN. |
| PLEASE SEE THAT THE TRADE OFFS OF TOTAL SPACE IS |
| PERMITTED HOWEVER THESE FIGURES NEED TO BE CORRECTED |
| AND KNOW. |
| PLEASE SEE 13-415.2 |
| |
| 5) NOTE:THIS IS THE SAME NOTE AS PREVIOUS. |
| PLEASE SEE THE PLANS CALL FOR A STEAM ROOM DISCONNECT |
| NEXT TO STEAM ROOM HOWEVER THIS DOES NOT SHOW |
| CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE |
| COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH |
| PANELS. |
| PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN |
| CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE |
| PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE |
| EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT |
| BEEN ADJUSTED AND COMPLETED. |
| PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT |
| INCLUDED? |
| PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL |
| SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE |
| CURRENT CODES. |
| PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND |
| COMPLETED UPDATED LOAD CALCULATIONS FOR ALL |
| ELECTRICAL. |
| PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4 |
| ETC. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 6) NOTE:THIS IS THE SAME AS PREVIOUS REVIEW. THE |
| CANDELA LEVELS WERE ADDED HOWEVER NOT HORN LEVELS WHERE |
| STATED FOR ADA. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE |
| THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA |
| REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN |
| A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW |
| LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC |
| ADA. |
| . |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. |
| FBC 106.3.5.1.2, 106.1.2 ETC |
| ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL |
| AND/OR BUILDING REVIEWER MAY FOLLOW. |
| |
| 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER |
| 13-413.1.ABC.1.2 AND .2.2 |
| PLEASE SEE THE FBC FOR ACTUAL WORDING REQUIRED ON |
| CONSTRUCTION DOCUMENTS. |
| |
| |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |