Plan Review Notes
Plan Review Notes For Permit 07090593
Permit Number 07090593
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-06 12:11:31** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ALONG
 WITH SOME NEW COMMENTS ARE IN NEED OF BEING ADDRESSED.
  
 1) NOTE: PLEASE SEE THE CODES AND NOTES ON PLANS STILL
 NEED TO BE CORRECTED. PLEASE SEE FOR EXAMPLE: THERE ARE
 STILL CODE NOTES ON PLANS TO THE SOUTH FLORIDA BUILDING
 CODE WHICH HAS NOT BEEN IN EFFECT SINCE MARCH 02.
 PLEASE SEE THE ELECTRICAL LOADCALCULATIONS ETC.
 SHEET E.3
 FBC 106.1.2
  
  
 2) NOTE: PLEASE SEE SMOKE DETECTOR NOTES ON PLANS STILL
 CALL FOR RESIDENTIAL INSTALLATIONS.
 ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS
 NOTES AS THESE ARE REFERENCING DWELLING UNIT
 REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION.
 CALLS FOR ARC FAULT PROTECTION ETC.
 PLEASE ADJUST NOTES.
 FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND
 RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES.
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES. PLEASE CORRELATE
 CIRCUITING PLANS ALSO. PLEASE SEE ROOMS WHERE
 CIRCUITING TO SPECIALTY LIGHTING AND CIRCUIT NUMBER AND
 PANEL IS BEING REFLECTED HOWEVER THESE DO NOT CORRELATE
 WITH THE SAME ROOMS.
 PLEASE SEE FOR EXAMPLE, SWITCH SHOWS A GCA -26, YET THE
 SAME ROOM SHOWS GCB 28. THIS IS THE SAME FOR SPA ROOM
 #1, #2, ETC.
 PLEASE SEE CIRCUITS WHICH REFERENCE TO A GCH PANEL YET
 NO GCH PANEL SCHEDULE WAS SUBMITTED.
 PLEASE SEE THERE ARE SEVERAL OTHER ELECTRICAL OUTLETS
 ON PLANS WHICH CONTAIN NO CIRCUITING.
 PLEASE SEE THAT THE PANEL SCHEDULES HAVE ALSO NOT BEEN
 REVISED. THE CIRCUITS ARE NOT SHOWN SPECIFIC TO ROOMS
 AND AREAS IN WHICH THEY FEED. PLEASE SEE 408.4,240.4,
 310.16.
 FBC106.1.2, 106.3.5.1.2, 106.5 ETC.
  
  
 4) NOTE: LIGHTING CONTROL DEVICES ARE NOT SHOWN FOR ALL
 LIGHTING. EXAMPLE : ALTERNATE SPA ROOM.
 PLEASE INDICATE LIGHTING CONTROLS PER FBC CHAPTER 13
 FOR NEW LIGHTING CONTROL DEVICES BEING INSTALLED.
 PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3.
 PLEASE SEE 13-101
 PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS
 SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE
 TABLE.
  
 PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2
 ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR
 *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE
 NOT LIGHTING REQUIRED.
 PLEASE EXPLAIN WHERE SOME OF THE LIGHTING ALLOWANCE
 FIGURES ARE DERIVED. FOR EXAMPLE OFFICE LEVELS NOTED AT
 1.5, WHEN THE CODE STATES MAXIMUM AT 1.1.
 PLEASE PLACE A TOTAL ON THE MAXIMUM ALLOWED COMPARED TO
 THE MAXIMUM DESIGN.
 PLEASE SEE THAT THE TRADE OFFS OF TOTAL SPACE IS
 PERMITTED HOWEVER THESE FIGURES NEED TO BE CORRECTED
 AND KNOW.
 PLEASE SEE 13-415.2
  
 5) NOTE:THIS IS THE SAME NOTE AS PREVIOUS.
 PLEASE SEE THE PLANS CALL FOR A STEAM ROOM DISCONNECT
 NEXT TO STEAM ROOM HOWEVER THIS DOES NOT SHOW
 CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE
 COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH
 PANELS.
 PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN
 CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE
 PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE
 EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT
 BEEN ADJUSTED AND COMPLETED.
 PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT
 INCLUDED?
 PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL
 SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE
 CURRENT CODES.
 PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND
 COMPLETED UPDATED LOAD CALCULATIONS FOR ALL
 ELECTRICAL.
 PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4
 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE:THIS IS THE SAME AS PREVIOUS REVIEW. THE
 CANDELA LEVELS WERE ADDED HOWEVER NOT HORN LEVELS WHERE
 STATED FOR ADA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE
 THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN
 A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW
 LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC
 ADA.
 .
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2 ETC
 ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL
 AND/OR BUILDING REVIEWER MAY FOLLOW.
  
 7) NOTE: PLEASE PROVIDE NOTES ON PLANS PER
 13-413.1.ABC.1.2 AND .2.2
 PLEASE SEE THE FBC FOR ACTUAL WORDING REQUIRED ON
 CONSTRUCTION DOCUMENTS.
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  