2007-10-04 08:21:04 | DENIED; |
| 1. PAGE A.0 APLIICABLE CODES, PEASE ADD FLORIDA |
| BUILDING CODE PLUMBING 2004/2006 SUPPLEMENTS. |
| 2. PAGE A.1 FLOOR PLAN DOES NOT MATCH P.1 FLOOR PLAN. |
| A.1 IS MISSING 1 LAV AND URINAL. |
| 3. PLEASE MARK ON PLANS MENS AND WOMANS LOUNGE ON PLANS |
| . ( THE FOLLOWING COMMENTS WILL ADDRESS LOUNGE "A" AS |
| MENS LOUNGE AND LOUNGE "B" AS WOMANS LOUNGE.) |
| 4.WOMANS LOUNGE TOILETS REQUIRES A MINIMUM OF 21" FROM |
| THE FRONT OF TOILET TO THE WALL. SECTION 405.3.1. |
| 5.A HANDICAP DRINKING FOUNTAIN IS REQUIRED TO MEET |
| MINIMUM REQUIRED PLUMBING FIXTURES SEE TABLE 403.1. D/F |
| SHALL COMPLY WITH FBC BUILDING CHAPTER 11 |
| SECTIONS11-4.1.3(10) AND 11-4.15.1 THRU 11-4.15.5. |
| 6. SUBMIT MANUFACTURE CUT SHEETS FOR STEAM GENERATOR, |
| LOCATION, AND A DETAIL DRAWING SHOWING WATER SUPPLY AND |
| LOCATION OF TEMPERATURERELIEF DISCHARGE. SEE |
| SECTIONS504.6, 504.6.1, 504.7 AND 504.7.2. |
| 7. WOMANS LOUNGE SHOWS ONLY ONE LAVATORY PIPED TO |
| SANITARY PEASE CORRECT. |
| 8. SHOWERS IN WOMANS LOUNGE SHOWS SHOWERS AS EXISTING |
| AND ALSO THAT ONE TOILET WAS MOVED PLEASE EXPLAIN AND |
| SHOW ON SANITARY RISER DIAGRAM. |
| 9. THE FOLLOWING PLUMBING FIXTURES ARE REQUIRED TO MEET |
| CHAPTER 11 OF THE BUILDING CODE; |
| ( A) MENS LOUNGE, A LAVATORY IS REQUIRED IN THE |
| TOILET STALL 11-4.17.3 EXCEPTION. |
| (B) URINAL TO COMPLY WITH SECTIONS 11-4.18.1 THRU |
| 11-4.18.4. |
| (C) MEN AND WOMAN LOUNGE THE SHOWERS ARE REQUIRED |
| TO MEET SECTIONS11-4.21.1 THRU 11-4.21.8. ( ONLY ONE |
| SHOWER IN WOMANS LOUNGE MUST COMPLY). |
| (D) ALL TOILET ROOMS SHALL COMPLY WITH SECTION |
| 11-4.1.2(6). |
| (E) BREAK SINK SHALL COMPLY WITH SECTIONS |
| 11-4.24.1 THRU 11-4.24.7. |
| (F) ONE OF THE TOILETS IN WOMANS LOUNGE SHALL |
| MEET THE HANDICAP REQUIREMENTS SEE SECTIONS 11-4.16.1 |
| THRU 11-4.16.6. |
| 10. SHOW DETAILS ON PLANS OF ALL HANDICAP FIXTURES |
| SHOWING ALL REQUIRED MEASUREMENTS. |
| PLUMBING PLAN REVIEW BY; |
| JOHN LEECH |
| 805-6695 |
| |