Plan Review Notes
Plan Review Notes For Permit 07090593
Permit Number 07090593
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-04 16:15:45***DENIED***
  
 1) PLANS INDICATE SMOKE DETECTORS AS IT APPLIES TO
 RESIDENTIAL OCCUPANCIES. PLEASE REMOVE INFORMATION THAT
 IS NOT APPLICABLE TO THIS PROJECT.
  
 2) PLANS ARE SOMEWHAT CONFUSING REGARDING EXITING.
 PLEASE PROVIDE A CLEAR ILLUSTRATION AND COMMON PATH OF
 TRAVEL OF REQUIRED MEANS OF EGRESS SHOWING WHERE
 PERSONS EXIT TO.
  
 3) INDICATE THE LOCATIONS OF REQUIRED 2A-10B,C RATED
 FIRE EXTINGUISHERS THAT SHALL BE LOCATED NOT TO EXCEED
 75' TRAVEL DISTANCE.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 6) DOES THE DOOR TO THE STAIRWELL SWING IN THE CORRECT
 DIRECTION?PLANS INDICATE AN OCCUPANT LOAD OF 100.
 EXIT DOORS TO SWING IN DIRECTION OF TRAVEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756