Plan Review Notes
Plan Review Notes For Permit 07090593
Permit Number 07090593
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-01 19:21:142007-10-01 19:21:14
  
 ** DENIED ***
  
 1) NOTE: PLEASE CORRELATE WHERE WORK IS BEING PERFORMED
 AS SHEET A-2 INDICATES *ANUSKA* YET TITLE BLOCKS
 INDICATE *NUSH SPA*?
 PLEASE ADJUST AND COORDINATE.
 FBC 106.1.2, 110.1.2
 FAC 61G1-16.004
  
 2) NOTE: PLEASE SEE THE COVER SHEET DOES REFLECT THE
 RELEVANT CODES WHICH ARE TO BE PART OF PROJECT AND
 DESIGNS HOWEVER THERE ARE SEVERAL COMMENTS AND NOTES ON
 PLANS WHICH REFERENCE CODES WHICH ARE NO LONGER IN
 EFFECT. PLEASE SEE SOME OF THESE IN FACT GO BACK TO
 SOME 1996 CODES.
 PLEASE SEE EXAMPLES ON ELECTRICAL NOTES:
 #3 WHICH STATES THE SFBC, SOUTH FLORIDA BUILDING CODE.
 # 10 AND #15 WHICH REFLECTS CODE FROM THE 1996 NEC.
  
 SMOKE DETECTOR NOTES #4 WHICH GIVES CODE SECTIONS FROM
 THE 1996 NFPA-72.
  
 ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS
 NOTES AS THESE ARE REFERENCING DWELLING UNIT
 REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION.
 CALLS FOR ARC FAULT PROTECTION ETC.
 PLEASE ADJUST NOTES.
 FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND
 RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES.
  
 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY INDICATE A
 NEW ELECTRICAL PANEL HOWEVER NO ELECTRICAL RISER WAS
 SUBMITTED SHOWING THIS NEW PANEL.?? PLEASE ALSO SEE
 NONE OF THE EXISTING PANELS LIST ANY OVER CURRENT
 PROTECTION FOR THIS NEW PANEL WHICH IS NOTED AND SHOWN
 ON E-2 NEXT TO EXISTING PANELS.
 PLEASE COORDINATE AS E-1 DOES NOT INDICATE ANY NEW
 PANEL?
 FBC 106.1.2, 106.3.5.1.2
 NEC 215.5, 310.16, 240.4, 408.4 ETC
  
 4) NOTE: PLEASE INDICATE LIGHTING CONTROLS PER FBC
 CHAPTER 13 FOR NEW LIGHTING CONTROL DEVICES BEING
 INSTALLED. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND
 .1.3.
 PLEASE SEE 13-101
 PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS
 SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE
 TABLE.
  
 PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2
 ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR
 *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE
 NOT LIGHTING REQUIRED.
 PLEASE LABEL ALL LIGHTING FIXTURES AS SHOWN ON PLANS
 AND CORRELATE WITH A FIXTURE LEGEND TO BE
 SHOWN/SUBMITTED. THE SAME FIXTURE INFORMATION AS LISTED
 IN THE LPC TABLE CAN BE USED HOWEVER EACH WOULD CONTAIN
 A DESIGNATION. PLEASE KNOW AT THIS TIME THERE SEEMS TO
 BE SOME COORDINATION NEED FOR FIXTURE TYPES AND COUNTS
 FOR AREAS. PLEASE SEE POS AREA FOR EXAMPLE.
 PLEASE ADJUST NOTE.
 **PLEASE CALL TO GO OVER.
  
 5) NOTE: PLEASE SEE THE PLANS CALL FOR A STEAM ROOM
 DISCONNECT NEXT TO STEAM ROOM HOWEVER THIS DOES NOT
 SHOW CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE
 COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH
 PANELS.
 PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN
 CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE
 PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE
 EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT
 BEEN ADJUSTED AND COMPLETED.
 PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT
 INCLUDED?
 PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL
 SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE
 CURRENT CODES.
 PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND
 COMPLETED UPDATED LOAD CALCULATIONS FOR ALL
 ELECTRICAL.
 PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4
 ETC.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN
 A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW
 LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC
 ADA.
 .
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2 ETC
 ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL
 AND/OR BUILDING REVIEWER MAY FOLLOW.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN ON
 PLANS AT THIS TIME, THERE VERY WELL MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW. REVIEW NOTES CAN ONLY BE GIVEN
 FOR PLANS/DOCUMENTS AS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]