2007-10-01 19:21:14 | 2007-10-01 19:21:14 |
| |
| ** DENIED *** |
| |
| 1) NOTE: PLEASE CORRELATE WHERE WORK IS BEING PERFORMED |
| AS SHEET A-2 INDICATES *ANUSKA* YET TITLE BLOCKS |
| INDICATE *NUSH SPA*? |
| PLEASE ADJUST AND COORDINATE. |
| FBC 106.1.2, 110.1.2 |
| FAC 61G1-16.004 |
| |
| 2) NOTE: PLEASE SEE THE COVER SHEET DOES REFLECT THE |
| RELEVANT CODES WHICH ARE TO BE PART OF PROJECT AND |
| DESIGNS HOWEVER THERE ARE SEVERAL COMMENTS AND NOTES ON |
| PLANS WHICH REFERENCE CODES WHICH ARE NO LONGER IN |
| EFFECT. PLEASE SEE SOME OF THESE IN FACT GO BACK TO |
| SOME 1996 CODES. |
| PLEASE SEE EXAMPLES ON ELECTRICAL NOTES: |
| #3 WHICH STATES THE SFBC, SOUTH FLORIDA BUILDING CODE. |
| # 10 AND #15 WHICH REFLECTS CODE FROM THE 1996 NEC. |
| |
| SMOKE DETECTOR NOTES #4 WHICH GIVES CODE SECTIONS FROM |
| THE 1996 NFPA-72. |
| |
| ** PLEASE CLARIFY ELECTRICAL NOTES, AND SMOKE DETECTORS |
| NOTES AS THESE ARE REFERENCING DWELLING UNIT |
| REQUIREMENTS AND NOT THAT OF A COMMERCIAL LOCATION. |
| CALLS FOR ARC FAULT PROTECTION ETC. |
| PLEASE ADJUST NOTES. |
| FBC 106.1.2, 110.1.2 ETC ADMIN COORDINATION AND |
| RELEVANT CODES WHICH MAY NOT BE FROM OTHER CODES. |
| |
| 3) NOTE: PLEASE SEE THE PLANS SPECIFICALLY INDICATE A |
| NEW ELECTRICAL PANEL HOWEVER NO ELECTRICAL RISER WAS |
| SUBMITTED SHOWING THIS NEW PANEL.?? PLEASE ALSO SEE |
| NONE OF THE EXISTING PANELS LIST ANY OVER CURRENT |
| PROTECTION FOR THIS NEW PANEL WHICH IS NOTED AND SHOWN |
| ON E-2 NEXT TO EXISTING PANELS. |
| PLEASE COORDINATE AS E-1 DOES NOT INDICATE ANY NEW |
| PANEL? |
| FBC 106.1.2, 106.3.5.1.2 |
| NEC 215.5, 310.16, 240.4, 408.4 ETC |
| |
| 4) NOTE: PLEASE INDICATE LIGHTING CONTROLS PER FBC |
| CHAPTER 13 FOR NEW LIGHTING CONTROL DEVICES BEING |
| INSTALLED. PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND |
| .1.3. |
| PLEASE SEE 13-101 |
| PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS AS |
| SUBMITTED ACTUALLY CALL FOR *VA REQUIRED* ON THE |
| TABLE. |
| |
| PLEASE KNOW THE LIGHTING LEVELS AS STATED IN 13-415.2 |
| ON EITHER TABLE AND THE ENERGY CODE IS ACTUALLY FOR |
| *MAXIMUM* LIGHTING LEVELS. THESE TABLES IN THE FBC ARE |
| NOT LIGHTING REQUIRED. |
| PLEASE LABEL ALL LIGHTING FIXTURES AS SHOWN ON PLANS |
| AND CORRELATE WITH A FIXTURE LEGEND TO BE |
| SHOWN/SUBMITTED. THE SAME FIXTURE INFORMATION AS LISTED |
| IN THE LPC TABLE CAN BE USED HOWEVER EACH WOULD CONTAIN |
| A DESIGNATION. PLEASE KNOW AT THIS TIME THERE SEEMS TO |
| BE SOME COORDINATION NEED FOR FIXTURE TYPES AND COUNTS |
| FOR AREAS. PLEASE SEE POS AREA FOR EXAMPLE. |
| PLEASE ADJUST NOTE. |
| **PLEASE CALL TO GO OVER. |
| |
| 5) NOTE: PLEASE SEE THE PLANS CALL FOR A STEAM ROOM |
| DISCONNECT NEXT TO STEAM ROOM HOWEVER THIS DOES NOT |
| SHOW CIRCUITING OR LOADS OR LISTED IN ANY PANEL? PLEASE |
| COMPLETE PLANS WITH ALL CIRCUITING AND CORRELATE WITH |
| PANELS. |
| PLEASE SEE THE NEW LIGHTING LOADS WHICH ARE SHOWN |
| CIRCUITED AND ON PANELS GCA AND GCB ARE ADDED TO THESE |
| PANELS, HOWEVER AS THESE PANELS ARE FED FROM THE |
| EXISTING PANEL *GC1* THE LOAD CALCULATIONS HAVE NOT |
| BEEN ADJUSTED AND COMPLETED. |
| PLEASE SEE ABOVE AS STEAM UNIT ETC IS ALSO NOT |
| INCLUDED? |
| PLEASE SEE THE CODE SECTIONS REFLECTED ON THE PANEL |
| SCHEDULES FOR LOAD CALCULATIONS ARE NOT FROM THE |
| CURRENT CODES. |
| PLEASE SUBMIT COMPLETED PLANS FOR ALL ELECTRICAL AND |
| COMPLETED UPDATED LOAD CALCULATIONS FOR ALL |
| ELECTRICAL. |
| PLEASE SEE NFPA-70 2005, 220, 215.5, 310.16, 240.4 |
| ETC. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| ADA REQUIRED AREAS.NO DEVICES ARE BEING SHOWN ON |
| PLANS/LEGEND. PLEASE KNOW AS THIS BUILDING DOES CONTAIN |
| A FIRE ALARM SYSTEM, EITHER THESE DEVICES EXIST OR NEW |
| LOCATIONS WILL BE REQUIRED TO MEET THE MINIMUM PER FBC |
| ADA. |
| . |
| ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| REQUIRED ON BASE PLANS AS SHOWN. |
| FBC 106.3.5.1.2, 106.1.2 ETC |
| ** THIS IS BEING NOTED AS NOTES FROM FIRE MARSHAL |
| AND/OR BUILDING REVIEWER MAY FOLLOW. |
| |
| ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN ON |
| PLANS AT THIS TIME, THERE VERY WELL MAY BE NEW COMMENTS |
| ON THE FOLLOWING REVIEW. REVIEW NOTES CAN ONLY BE GIVEN |
| FOR PLANS/DOCUMENTS AS SUBMITTED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |