2007-10-09 11:18:17CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07090593
 BUILDING PLAN EXAMINERII
 PROJECT NUSH SPA/SALON
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 701 S. ROSEMARY, STE 200
  DATE OCTOBER 5, 2007
  
 BUILDINGPLANREVIEW
  
 CORRECTION SUBMITTAL
 WHEN RE-SUBMITTINGCORRECTED PLANS FOR PERMITTING,
 PLEASEREMOVE AND REPLACE ANY SHEETS AS NECESSARY.
 INCLUDE A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER WITH A DESCRIPTION OF THE
 REVISION MADE. IDENTIFY THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND AND INCLUDE THE OLD
 SHEETS IN THE RE-SUBMITTAL PACKAGE FOR THE PLAN
 REVIEWER?S REFERENCE.
 THIS SHALL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 COMMENT-FOR YOUR INFORMATION
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
  
 NOTE ON COVER SHEET 1
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 ACCESSIBILITYCHAPTER 11
 FBC2004 EXISTING BUILDING
 LEVEL OF ALTERATION
 TYPE OF CONSTRUCTION
 SPRINKLED / UN-SPRINKLED
 NUMBER OF STORIES
 WIND SPEED AND EXPOSURE
 WIND IMPORTANCE FACTOR
 TYPE OF OCCUPANCY
 OCCUPANT LOAD-GROSS - NET
 COMMENTS- PLEASE ADDRESS THE FOLLOWING,FBC 2004
 ACCESSIBILITY,FBC 2004EXISTING BUILDINGS,
 NUMBER OF STORIES,
  
 FBC EXISTING 503.2 CARPETING.
 NEW CARPETING USED AS AN INTERIOR FLOOR FINISH MATERIAL
 SHALL COMPLY WITH THE RADIANT FLUX REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
  
  
  
  
 FBC BUILDING CHAPTER 11ACCESSIBILITY
  
 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS,
 INFORMATION COUNTERS.
 (1)IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL
 STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE
 PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES
 TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A
 PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915
 MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915
 MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN
 ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3 . THE
 ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE
 BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS
 TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE
 COUNTER, AN AUXILIARY COUNTER MEETING THESE
 REQUIREMENTS MAY BE PROVIDED.
 COMMENTS-SHEETA.2DETAIL RECEPTION / SALES COUNTER
 FOR ACCESSIBILITY
  
 11-4.13 DOORS.SEE TEA/MED.CONSDOOR NO 4
 COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29?
 CLEAR OPENING FOR ACCESSIBILITY
  
 11-4.13 DOORS.SEE LOUNGEPOCKET DOOR NO 5
 COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29?
 CLEAR OPENING FOR ACCESSIBILITY
 11-4.13.9 DOOR HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING
 DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS
 EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO
 OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE
 MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE
 DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 HARDWARE REQUIRED FOR ACCESSIBLE DOOR PASSAGE SHALL BE
 MOUNTED NO HIGHER THAN 48 INCHES (1219 MM) ABOVE FINISH
 FLOOR.
 COMMENTS- POCKET DOOR NOT IN COMPLIANCE
  
 11-4.13 DOORS.SEE STEAM ROOMDOOR NO ?
 COMMENTS- ALL REQUIRED DOORS SHALL HAVE AT LEAST A 29?
 CLEAR OPENING FOR ACCESSIBILITY
  PLEASE IDENTIFY THIS DOOR ON THE DOOR
 SCHEDULE
  
  
 11-4.13.9 DOOR HARDWARE.
 HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING
 DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS
 EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO
 OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE
 MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE
 DESIGNS. WHEN SLIDING DOORS ARE FULLY OPEN, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.
 HARDWARE REQUIRED FOR ACCESSIBLE DOOR PASSAGE SHALL BE
 MOUNTED NO HIGHER THAN 48 INCHES (1219 MM) ABOVE FINISH
 FLOOR.
 COMMENTS- IDENTIFY HARDWARE SCHEDULE ON ALL DOORS
2007-10-01 14:31:58TO "BOB"#15