Plan Review Notes
Plan Review Notes For Permit 07090562
Permit Number 07090562
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-18 08:52:46BUILDING PLAN REVIEW
 PERMIT:07090562
 ADD: 2600 N. FLAGLER DR. #710
 CONT: K.L. BREEN BLDRS INC.
 TEL: (561) 856-0232
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 10/18/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 **NOTED, HOWEVER, THE ALTERATION LEVEL STATED IS
 INCORRECT**
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISHES AND DESIGN FEES. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES. ** NOTED HOWEVER, THE COST OF THE
 PROJECT SHALL BE A FAIR MARKET VALUE. **
  
 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE. **THIS
 INFORMATION SHALL BE INDICATED ON THE DRAWINGS. **
  
 5)WPB AMENDMENTS 106.1.3 CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN TO MINIMUM 1/8 INCH SCALE. THE
 DRAWINGS SUBMITTED DOES NOT SHOW CLEARLY THE PROPOSED
 WORK INDICATED ON THE APPLICATION. SUBMIT AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING ALL
 CHANGES TO PROVIDE CONFORMITY TO RECORD RETENTION
 PROGRAM. SUBMIT DRAFTSMAN QUALITY DRAWINGS WITH A WALL
 LEGEND OF EACH TYPE OF WALL TO BE CONSTRUCTED OR DEMO.
 **NO ADDRESSED**
 **NEW**
 A)WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER. THE PLANS SHALL BE OF DRAFTSMAN QUALITY,
 INDICATING CLEARLY THE AREA OF WORK. HAND-WRITING OR
 WHITE-OUT IS NOT ACCEPTABLE ON THE DRAWINGS. THE
 DESIGNER OF RECORD SHALL DATE, PRINT, AND SIGN THEIR
 NAME ON ALL SHEETS.
  
 B)FBC 106.1.1 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  