2007-10-18 08:52:46 | BUILDING PLAN REVIEW |
| PERMIT:07090562 |
| ADD: 2600 N. FLAGLER DR. #710 |
| CONT: K.L. BREEN BLDRS INC. |
| TEL: (561) 856-0232 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006/2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 2ND |
| ACTION: DENIED |
| 10/18/07 |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2)2004 FBC EXISTING |
| 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| SECTIONS 303, 304 AND 305 OF THIS CODE. |
| **NOTED, HOWEVER, THE ALTERATION LEVEL STATED IS |
| INCORRECT** |
| |
| 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO |
| INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISHES AND DESIGN FEES. OUR VALUATION |
| REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST |
| ANALYSIS SERVICES. ** NOTED HOWEVER, THE COST OF THE |
| PROJECT SHALL BE A FAIR MARKET VALUE. ** |
| |
| 4)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE |
| DESIGNED TO THE 2004 FLORIDA BUILDING CODE. **THIS |
| INFORMATION SHALL BE INDICATED ON THE DRAWINGS. ** |
| |
| 5)WPB AMENDMENTS 106.1.3 CONSTRUCTION DOCUMENTS SHALL |
| BE DIMENSIONED AND DRAWN TO MINIMUM 1/8 INCH SCALE. THE |
| DRAWINGS SUBMITTED DOES NOT SHOW CLEARLY THE PROPOSED |
| WORK INDICATED ON THE APPLICATION. SUBMIT AN EXISTING |
| FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING ALL |
| CHANGES TO PROVIDE CONFORMITY TO RECORD RETENTION |
| PROGRAM. SUBMIT DRAFTSMAN QUALITY DRAWINGS WITH A WALL |
| LEGEND OF EACH TYPE OF WALL TO BE CONSTRUCTED OR DEMO. |
| **NO ADDRESSED** |
| **NEW** |
| A)WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| PAPER. THE PLANS SHALL BE OF DRAFTSMAN QUALITY, |
| INDICATING CLEARLY THE AREA OF WORK. HAND-WRITING OR |
| WHITE-OUT IS NOT ACCEPTABLE ON THE DRAWINGS. THE |
| DESIGNER OF RECORD SHALL DATE, PRINT, AND SIGN THEIR |
| NAME ON ALL SHEETS. |
| |
| B)FBC 106.1.1 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |