Plan Review Notes
Plan Review Notes For Permit 07090562
Permit Number 07090562
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-05 18:56:49 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT:07090562
 ADD: 2600 N. FLAGLER DR. #710
 CONT: K.L. BREEN BLDRS INC.
 TEL: (561) 856-0232
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006/2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED 10/5/07
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST TO
 INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISHES AND DESIGN FEES. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
  
 5)WPB AMENDMENTS 106.1.3 CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN TO MINIMUM 1/8 INCH SCALE. THE
 DRAWINGS SUBMITTED DOES NOT SHOW CLEARLY THE PROPOSED
 WORK INDICATED ON THE APPLICATION. SUBMIT AN EXISTING
 FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING ALL
 CHANGES TO PROVIDE CONFORMITY TO RECORD RETENTION
 PROGRAM. SUBMIT DRAFTSMAN QUALITY DRAWINGS WITH A WALL
 LEGEND OF EACH TYPE OF WALL TO BE CONSTRUCTED OR DEMO.
  
 6)PER FLORIDA STATUTES 481.229 EXEMPTION FROM
 ARCHITECTURAL LICENSURE ONLY APPLIES TO 1FAMILY AND 2
 FAMILY RESIDENCES (R3) NOT MULTI FAMILY (R2) OR
 BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE
 REQUIRED TO BE DRAWN BY A LICENSED DESIGN
 PROFESSIONAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]